FDU-80 Annunciator
SW1 DIP Switch Settings
12
Document 51264 Rev A2 6/14/00 P/N 51264:A2
.
Note: SW1 DIP switch settings as illustrated in Figure 1-3 are as
follows:
1. DIP switch 1: On = Key-switch disabled (membrane function
switches are always enabled with key-switch having no affect on
their function).
2. DIP switch 2: Off = piezo sounder disabled (requires approval of
LAHJ)
3. DIP switch 3: Off = Receive Only. This setting is used for all
annunciators except the last or only FDU-80 Annunciator on the
EIA-485 line
4. DIP switches 4 through 6: Off = Configured for operation with
the AFC-600 or AFP 300/400 FACP
5. DIP switches 7 and 8: Off (these switches are not used)
Figure 1-3: DIP Switch Settings Example
switch 1 shown
in ON position
switches 2 through 8
shown in Off position