APPENDIX G - NFS-3030
28
PN 50702:B2 4/14/03
APPENDIX G - NFS-3030
Mounting an APS-6R in a Chassis
An Auxiliary Power Supply is mounted on a CHS-4 Series chassis.
See “Mounting in CAB-3/CAB-4 Series Cabinets” on page 12..
Connecting to the AMPS-24 and CPU-3030
Make the following connections as shown in the figure below.
• Connect primary power from
TB1
on the APS-6R to
TB3
HOT,
NEUT and EARTH on the AMPS-24.
• Connect secondary power from
TB3
BATT(+) and BATT(-)on
the APS-6R to
TB5
(BAT IN +) and
TB4
(BAT OUT-)
respectively on the AMPS-24.
• Connect trouble input from
J3
on the APS-6R to the
J5
Trouble
bus connection
on the CPU-3030.
Figure 19 Wiring to AMPS-24 and CPU-3030
J2
J9
J3
J1
TB2
TB3
TB1
JP3
JP2
To battery
backup
+
-
AMPS-24
CPU-3030
AP
S-
6R
to
N
F
S-
30
30
.cdr
www.PDF-Zoo.com
firealarmresources.com