Section 2 Installation
18
PN 50702:B2 4/14/03
Configuring the APS-6R
The APS-6R may be configured for the following:
• 8-hour delay for reporting loss of AC: cut jumper JP2.
• 16-hour delay for reporting loss of AC: cut jumper JP2 and JP3.
• 240 VAC operation: See WARNING below. Cut jumper JP1
before applying power.
The figure below illustrates the location of the jumpers:
Figure 9 Configuring the APS-6R
JP
1
J2
J9
J3
J1
TB
2
JP
3
JP
2
JP3
JP2
JP1
AP
S-
6R
co
nfi
g
.c
dr
WARNING: HIGH VOLTAGE!
Cut JP1 before applying power
for 240 VAC operation.