49
Document 15949 Rev. E 4/12/95 P/N 15949:E
Table 5-1: AIM-200 Event Codes
Device Type
Status
P
Photo Detector
Normal, med. sensitivity
PL
Photo Detector
Normal, low sensitivity
PH
Photo Detector
Normal, high sensitivity
PA
Photo Detector
Alarm
PF
Photo Detector
Trouble
PE
Photo Detector
No answer
Pd
Photo Detector
Disabled
PU
Photo Detector
Unsatisfactory (failed automatic self-test)
I
Ion Detector
Normal, med. sensitivity
IL
Ion Detector
Normal, low sensitivity
IH
Ion Detector
Normal, high sensitivity
IA
Ion Detector
Alarm
IF
Ion Detector
Trouble
IE
Ion Detector
No answer
Id
Ion Detector
Disabled
IU
Ion Detector
Unsatisfactory (failed automatic self-test)
H
Heat Detector
Normal
HA
Heat Detector
Alarm
HF
Heat Detector
Trouble
HE
Heat Detector
No answer
Hd
Heat Detector
Disabled
HU
Heat Detector
Unsatisfactory (failed automatic self-test)
G
Monitor Module
Normal
GA
Monitor Module
Alarm
GF
Monitor Module
Trouble
GE
Monitor Module
No answer
Gd
Monitor Module
Disabled
C
Control Module (NAC)
Normal
CA
Control Module (NAC)
Alarm output
CF
Control Module (NAC)
Trouble
CE
Control Module (NAC)
No answer
Cd
Control Module (NAC)
Disabled
CO
Control Module (Relay)
Open (OFF)
CC
Control Module (Relay)
Closed (ON)
CF
Control Module (Relay)
Trouble
Cd
Control Module (Relay)
Disabled
LF
Line Fault (Style 6)
SF
CPU loss of communication
EP
Enter Password
AP
Auto Program
Note:
Invalid device type =
E
(left digit)
Maintenance Alert =
F
(left digit)
Technical Manuals Online! - http://www.tech-man.com