background image

AM2020/AFP1010 Combination Fire/Security Protective Signaling System Operator’s Instructions

F

r

ame and mount these Oper

ator’

s

Instr

uctions adjacent to the

AM2020/AFP1010 f

or ready

ref

erence

.

The Displa

y Interface Assembl

y

 (DIA-1010/DIA-2020)

A.C. Power:

A green LED will illuminate to indicate that the system is
operating from the primary power supply.

Fire Alarm:

A red LED will flash to indicate that the panel has de-
tected at least one fire alarm condition in the system.  The
red LED will light steadily when all fire alarms have been
acknowledged.  The panel display will provide detailed in-
formation on any alarms received.

Trouble/Security

A yellow LED will flash to indicate any unacknowledged

Alarm:

change of status in the system.  The panel display will
provide detailed information about each change of status
signal received.  After all change of status conditions have
been acknowledged, and while at least one trouble condi-
tion still exists, the Trouble/Security Alarm LED will illumi-
nate steadily.  NOTE: Security alarms are considered
trouble conditions in this combination fire alarm/security system.

Display Trouble:

A  yellow  LED will illuminate when a trouble condition is detected in the display assembly.  When this LED is illuminated, all
display information should be considered invalid.

Signal Silence:

A yellow LED will illuminate steadily when all the control modules in the system which can be silenced have been silenced.  A
flashing yellow LED indicates a partial signal silence condition (some of the control modules that can be silenced have been
silenced).

Piezo Sounder:

The local panel piezo sounder provides an audible indication of the system alarm or trouble conditions.  The sounder will pulse
to indicate the detection of at least one fire alarm condition in the system, and will sound steadily when the system is in trouble.
The sounder is silenced when all conditions have been acknowledged.  If the sounder sounds steadily, and it cannot be silenced
by the acknowledgment of all system alarm/trouble conditions, CALL YOUR SERVICE REPRESENTATIVE IMMEDIATELY.

ACK/STEP:

This Key is used to acknowledge system alarm or trouble conditions.  When depressed, the operator acknowledges the new
status of the device indicated on the display.  Depression of this key will also step the display to the next device in alarm or trouble.
After all such system alarm and trouble conditions have been acknowledged, the ACK/STEP key may be used to step the display
through the existing system alarm and trouble conditions.

SIGNAL SILENCE:

This key, during a fire alarm condition, will deactivate all activated control modules that have been programmed to permit signal
silencing.

SYSTEM RESET:

This key is used to clear all system alarm and trouble conditions.  If an alarm or trouble condition still exists after System Reset,
that alarm/trouble condition will resound.

SYSTEM TEST:

This key is used to automatically perform a test of all intelligent detectors in the system.  Results of the system detector test are
then indicated on the panel display.

LAMP TEST:

This  key is used to perform a test of LEDs on the control panel and to test the panel display.  The test will illuminate the panel
LEDs in sequence for a timed period and flash the panel display.  When the test has been completed, the panel LEDs and the
panel display will return to their prior states.

A

CM-16A

T and A

CM-32A Annunciator

s

System Trouble:

This  yellow  LED illuminates to indicate a trouble in the system.

On Line:

This green LED flickers to show that the annunciator is communicating with the control panel.

ACKNOWLEDGE:

The Local Silence/Acknowledge Key lights all the LEDs on the ACM-16AT and acknowledges all
status changes for both the annunciator and the expanders.  Flashing LEDs on the annunciator will
latch on solid and the piezo sounder will be silenced.  Note: On and expander (AEM-16AT or  AEM-
32A), this key serves as a Lamp Test only.

Point LEDs:

The red LED associated withe each pint will flash or will illuminate steadily to indicate activation of that
point (alarm or energizing).  The yellow LED associated with each annunciator point will flash or illumi-
nate steadily to indicate a trouble condition on that point (ACM-16AT or AEM-16AT only).

Point Control

Input circuits:  Each key serves to Acknowledge its respective point.  Pressing the control key after the

Switches:

onset of a trouble condition will cause the flashing yellow trouble LED to illuminate steadily.

(A

CM-16A

T

,

Output circuits:  The control key does not serve as an Acknowledge for this point.  Pressing the control

AEM-16AT only)

key toggles the state of the output circuit (if the circuit is ON, pressing the key turns the circuit OFF and
vice versa).
Software Zones:  The control key serves as an Acknowledge for the software zone.

AMG-1 A

udio Messag

e

 Generator

Audio Level:

This green LED is illuminated when the audio level is correct.

All Call:

This green LED toggles on and off with each depression of the All Call Switch.

On Line:

This green LED indicator is normally illuminated to show that the control panel is commu-
nicating with the Audio Message Generator.

Trouble:

This yellow LED illuminates to indicate the presence of a trouble in local audio subsystem
equipment (AMG, AA-30, FFT-7).

ALL CALL SWITCH:

The All Call Switch, when pressed, is used to activate all speaker circuits.  These speaker
circuits will deactivate when the All Call Switch is pressed again (toggle function), provided
an alarm is not present.  If an alarm is present, the speaker circuit will remain activated until
manually turned off or until the system is reset.  For dual-channel applications, either All
Call Switch can be pushed with the same result.

SPEAKER VOLUME:

The Local Speaker Volume control adjusts the volume of the speaker located on the AMG. It will not affect the
volume of the speakers installed throughout the building.  If necessary, turn the volume down to prevent feedback
during paging.

MICROPHONE:

The microphone is used for paging.  To page, select the speaker circuit(s) that you wish to page through by using the control keys
on ACM-16AT Annunciators or by using the All Call Switch.  Depress the switch on the side of the microphone and speak into the
microphone.  Talk loudly enough to cause the green Audio Level LED to illuminate.  If the Audio Level LED is allowed to remain off
for 30 seconds system trouble will result.

Speaker Circuit Select:

To turn a speaker circuit ON, press the control key on the annunciator point mapped to that speaker circuit.  The red LED on the

(A

CM-16A

T only)

point selected will illuminate.  The control key toggles the state of its circuit.  If the speaker circuit has been previously activated
automatically by the control panel, pushing the control key will cause the yellow LED on the annunciator point and the AM2020’s
Signal Silence LED to flash, indicating that a partial silence has been effected.

Tone/Message Select:

To select an audio output function (voice message or audio tone), press the control key on the annunciator.  Note:  An active
audio function may have to be deactivated before selection of the next function.

Dual-Channel Select:

To select a channel, press the control key on the annunciator point mapped to the desired channel.  The red LED on that point

(A

CM-16A

T only)

will illuminate.  The control key toggles the selection of the channel.  Channels must be selected for each speaker zone in a dual-
channel system.

A

TG-2 A

udio 

T

one Generator

The ATG-2  provides user-selected tones for single or dual-channel output.  When acti-
vated, the ATG-2 generates either a slow whoop, Hi/Lo or steady tone on the primary
(EVAC) channel.  In dual-channel operation, the ATG-2 also generates either chime or a 20
pulses-per-minute tone on the secondary (ALERT) channel.

On Line:

This green LED indicator is normally illuminated to show that the AM2020/AFP1010 is
communicating with the Audio Tone Generator.

Evac Channel:

This green LED illuminates to show that manual paging will occur over the EVAC channel.

Alert Channel:

This green LED illuminates to show that manual paging will occur over the ALERT chan-
nel.

Trouble:

This yellow LED illuminates to indicate the presence of a trouble in local audio subsystem equipment (ATG, AA-30 FFT-7).

PAGE SELECT SWITCH: The Page Select Switch, when pressed, is used to choose between EVAC and ALERT channels for paging.  The respective LED

will illuminate when the channel has been selected.

MICROPHONE:

The microphone is used for paging.  To page, select the desired channel by pressing the Page Select Switch until the respective
LED illuminates.  Depress switch on the side of the microphone and speak into the microphone.

Speaker Circuit Select:

To turn a speaker circuit ON, pres the control key on the annunciator point mapped to that speaker circuit.  The red LED on the

(A

CM-16A

T only)

point will illuminate.  The control key toggles the state of its circuit.  If the speaker circuit has been previously activated automati-
cally by the control panel, pushing the control key will cause the yellow LED on the annunciator point and the AM2020/AFP1010’s
Signal Silence LED to flash, indicating that a partial silence has been effected.

ALL CALL SWITCH:

To turn on all speaker circuits, press the All Call Switch (provided separately).

FFT

-7 & FFT

-7S Fire Fighter

s

 

T

elephone

Page Mode: 

(FFT

-7 only)

This green LED illuminates when the Page Switch is depressed.

On Line:

This green LED illuminates to show that power is applied to the Fire Fighters Tele-
phone system.

Phone Trouble:

This  yellow  LED illuminates to indicate an internal circuit trouble.

Line Trouble:

This  yellow  LED illuminates to indicate an external circuit trouble.

Page Switch:

The Page Switch allows a firefighter to page form a Fire Fighters Telephone.  To

(FFT

-7 only)

page, select the speaker circuit(s) that will carry the page by using the control keys
on ACM-16AT annunciators, or by using the All Call Switch on the AMG-1 next to the
FFT-7.  Depress the Page Switch and talk loudly enough into the handset to cause
the green Audio Level LED on the AMG-1 to illuminate.

Incoming Calls:

The yellow LED on an annunciator point mapped to telephone circuit will flash, the
red LED will illuminate steadily, and the piezo will beep.  Do not press the Acknowledge Key in this case!  To answer the incoming
call, pick up the master handset and press the control key next to these annunciator LEDs.  Wait until the caller has been
connected (audible click in the receiver).  To disconnect the call, momentarily press the telephone circuit annunciator point control
key again.

Remote Phone Paging:

Answer the incoming call from the telephone circuit as described above.  Press the Page switch on the FFT-7, illuminating the

(FFT

-7 only)

yellow Page Mode LED.  Select speaker circuits by pressing control keys on the annunciator or by depression of the All Call
Switch on the AMG-1 next to the FFT-7.  Any fireman connected via the telephone circuit annunciator control key can page
through the selected speaker circuits.

In the e

v

ent of troub

le

, contact the f

ollo

wing

Notifier Local Ser

vice Representativ

e

:

Name: _____________________________________

Company: __________________________________

Address: __________________________________

Telephone Number: _________________________

Document 15337, Re

v C (r

ight)  11/04/97  ECN 93-382  P/N 15337:C2

Document 15337, Re

v C  (left) 11/04/97  ECN93-382  P/N 15537:C2