3URJUDP &KDQJH
Point Programming
12
AFP-300/AFP-400 Programming PN 50259:C1 06/19/97
3URJUDPPLQJ D &RQWURO
0RGXOH &0;
Programming a CMX module is similar to MMX modules—except the default zone is
always set to Zone 00 (General Alarm). Figure 16 shows a sample display for editing a
CMX module:
)LJXUH &RQWURO 0RGXOH 3URJUDPPLQJ 6FUHHQ
The Type Code selection blinks, indicating that you can press the Next or Previous
Selection keys to scroll through the CMX Type Code selections (listed in Table 12).
You can also do the following:
1.
Use the arrow and alphanumeric keys to modify point information, such as the
CBE equation.
2.
When finished modifying a point, press <Enter>; then use the Next and Previous
keys to select another point.
7\SH &RGHV IRU &RQWURO
0RGXOHV &0;
Table 12 contains a comprehensive list of Control Module Type Codes. The Type
Codes that display, however, depend on the configuratio
Q
Table 12 Control Module (CMX) Type Codes
:DON 7HVW 6HOHFWLRQ RII
GHIDXOW : VHOHFWHG
6ZLWFK ,QKLELW , VHOHFWHG
GHIDXOW RII
%OLQNLQJ W\SH FRGH VHOHFWLRQ
6LOHQFHDEOH 6 VHOHFWHG
GHIDXOW RII
352*50 &21752/
02'8/( $''5
=2 = = = =
,6 0
Type Code
Special Function
Control
Supervised NAC
Relay
Relay output
Bell Circuit
Supervised NAC
Strobe Ckt
Supervised NAC
Horn Circuit
Supervised NAC
Audible Ckt
Supervised NAC
Speaker
Supervised NAC
Rel End Bell
Supervised NAC
blank label
Supervised NAC (use when no other Type Code applies)
Release Ckt
Releasing Circuit, nonpower-limited, supervised for opens, shorts, and
ground faults (always non-silenceable)
Rel Ckt ULC
Releasing Circuit, power-limited, supervised for opens, shorts, and ground
faults
Relea. Form C
Relay output, contacts operate upon release
Rel Audible
NAC, activated upon release
NonReset Ctl
Relay output, unaffected by “System Reset” command
Telephone
Standard telephone circuit