Configuring the ACPS-2406
Panel Programming Requirements
24
ACPS-2406 PN 51304:B 09/02/2003
3.
If the output is a +24 V relay, activating the second associated address has no effect, but the
address must be in communication with the panel.
Dual Stage Panel Programming
All second stage timing is controlled by the FACP. All addresses must be programmed in the
FACP. Null control-by-event (CBE) should be employed for unused second-stage points. Figure
3.3 illustrates the panel CBE programming.
Figure 3.3 Canadian Dual Stage for the AM2020/AFP1010
The sequence of operations is as follows.
•
A general alarm activates FCM L1M1 (Type code APND).
•
L1M2, which has been programmed via CBE for OR(L1M1), activates. (Type code FORC).
•
L1M3 (Type code NONA) physically monitors L1M2 contacts. L1M3 activates.
•
Software Zone Z200 (RZON) is programmed to activate after a 5 minute delay with the equation Z200 =
DEL(00.05.00(L1M3)). Z200 will clear (or never activate) if L1M1 is acknowledged or if the system is
reset before the 5 minute timer expires.
•
Software Zone Z201 (RZON) is programmed to activate after a 0 delay when Z200 activates.
Z201 will only clear from a system reset.
•
Alert Software Zone Z1 will activate when the Z1 equation is satisfied. ALERT = OR(Z1). A CBE
(Control-by-event) in this equation refers to any local CBE that is programmed into this point. It could be a
CBE that programs four cross-zoned detectors, for example.
General Alarm
FCM
Type
APND
L1M1
FMM
Type
NONA
L1M2
OR(L1M1)
Physical Connection
L1M3
Z200
Z200 = DEL(00.05.00(LIM3))
Z201 = SDEL(00.00.00(Z200))
EVAC
Outputs
CBE for EVAC Outputs = OR(Z2,Z201)
CBE for ALERT Outputs = OR(Z1)
FCM
Type
FORC
Z201
ALERT
Outputs
Tracking = YES
Z1 = Zone programmed to activate
the alert stage.
Z2 = Zone programmed to activate
the evacuation stage in the
event of a second alarm.