Userguide CableTroll 210 March 2020 

01021000/11/12/13

 

4. Application/Mounting 

 

4.1 Sensor Mounting 

The Rogowski Coil/Current transformer should be mounted between the end termination and the point 
where the cable screen is extracted. The CT may be  mounted on the screened  part of the cable. The 
screen should then be fed back through the Rogowski Coil/CT to prevent earth fault currents or screen 
transients exceeding the trip level setting and activating the indicator erroneously. 
 

Product number: 01021000/11/12/13 

 

 

Rogowski Coil/Current Transformer Mounting.   

 

5. Battery Status 

5.1 Low battery (Lithium battery) 

When there is less than 20% remaining capacity on the battery, the low battery relay will close and 
remain closed until battery counter is reset. 
 
Pushing the Test-/Reset button for less than 1 sec., the battery status LED will indicate the status of the 
Lithium battery.

 

 

Alternating Red and Green flash:  

Battery OK 

 

Red flash only: 

 

 

Less than 20% remaining capacity. 

 

The power consumption during idle and flashing is stored in the EFI and can be read with a cellphone 
with a NFC function (Near Field Communication). 
 
 

 

Battery Status LED 

Summary of Contents for 01021000

Page 1: ...Userguide CableTroll 210 March 2020 010121000 11 12 13 CableTroll 210 User Guide for product nr 01021000 11 12 13...

Page 2: ...updated 6 20 09 19 Programming table updated 7 25 09 19 Technical drawing with dimensions updated 8 15 09 19 Updated with Rogowski coil sensor 9 28 01 20 Pictures updated with black Rogowski coil 10...

Page 3: ...6 3 2 CAPACITIVE DISCHARGE CURRENTS 6 3 3 EARTH FAULT DETECTION 7 4 APPLICATION MOUNTING 8 4 1 SENSOR MOUNTING 8 5 BATTERY STATUS 8 5 1 LOW BATTERY LITHIUM BATTERY 8 5 2 TO REPLACE THE BATTERY 9 5 3 R...

Page 4: ...and suitable for use in tropical weather conditions with high humidity of 65 to 95 The CableTroll 210 will indicate earth faults locally by a flashing diode and remotely through a relay contact 1 1 De...

Page 5: ...closed NC Pulse relay may be available from factory on request 2 4 Rogowski coil Current Transformer CT Earth fault element The indicator uses one direct type Rogowski coil for detection of earth faul...

Page 6: ...rough the sensor element seen from the feeder The capacitive discharge current from behind the Rogowski coil CT earth fault element must not exceed the trip level setting of the indicator The capaciti...

Page 7: ...e met Ic It where Ic capacitive current down stream of the indicator It CableTroll 210 programmed trip level sensitivity To estimate the capacitive discharge current at any line point you must calcula...

Page 8: ...e indicator erroneously Product number 01021000 11 12 13 Rogowski Coil Current Transformer Mounting 5 Battery Status 5 1 Low battery Lithium battery When there is less than 20 remaining capacity on th...

Page 9: ...en replaced the battery counter must be reset This is done by pushing the Test Reset button and hold it pressed for more than 30 seconds Observe the following sequence Push the Test Reset button and h...

Page 10: ...ion diagram CT210 Terminal from left 1 Mains reset 220 240VAC 2 Mains reset 220 240VAC 3 SCADA reset 9 110VDC Hot 4 SCADA reset 9 110VDC Ground 5 LED 6 Red 6 LED 6 Black 7 Earth fault Relay 1 NC1 8 Ea...

Page 11: ...fixed trip level 0 0 1 160A fixed trip level 1 0 1 240A fixed trip level Table 1 Switch setting overview trip level NOTE NORTROLLs Earth Fault Indicator and Earth Fault Element are tuned in to consti...

Page 12: ...urs 0 1 16 hours 1 1 32 hours Table 3 Switch overview reset time settings 7 4 Setting Auto reset Select Auto Reset with switch number 8 0 OFF 1 ON 8 Auto reset 0 Auto reset Disabled 1 Auto reset Enabl...

Page 13: ...the CT sensor Auto Reset from sensor Inactive Fault LED flashes rapidly in burst Auto Reset from sensor Active Fault LED illuminates constant Press longer than 5 sec Simulated fault indication with bo...

Page 14: ...r CT Timer 4 8 16 or 32 hours DIP Switch Manual Reset button Remote SCADA supervisory reset 9 110VDC Indication Red High intensity LED s for earth fault Red Amber and Green LED for battery status Exte...

Page 15: ...1 12 13 11 Dimensions 11 1 Housing Overall dimensions 85 x 94 x 51 6 mm 4 x 4 2mm Mounting holes on 74 x 74 mm centres as shown below 11 2 Split core Rogowski coil CT Overall dimensions 40x45x28 mm sh...

Page 16: ...tion Prod no 01021000 CT210 with Lithium battery CT 3m cable and short coil Prod no 01021011 CT210 with Lithium battery CT 16m cable and short coil Prod no 01021012 CT210 with Lithium battery CT 3m ca...