The HeatmiserNeo Driver
13
Description
Reference Type
Integration Cooling Setpoint
Driver generated value containing the
cooling setpoint used when the neoStat is
not in standby, hold, away, or holiday
mode.
When the interface is started, this value
will not be available until Standby Mode is
off.
CP
Obj\Num: 7…35; Adjustable
Heating Mode
V23
Obj\NoYes
Heating Demand
V13
Obj\OffOn
Heating Setpoint
Current heating temperature setpoint in
use for the mode.
This setpoint can be temporarily
overridden until the next programmed
comfort level, or change of mode
We recommend this setpoint is adjusted
using the Integration Heating Setpoint
(SP)
V9
Obj\Num: 18…35; (Adjustable)
Cool Mode
V2
Obj\NoYes
Cooling Demand
V3
Obj\OffOn
Cooling Setpoint
Current cooling temperature setpoint in
use for the mode.
We recommend this setpoint is adjusted
using the Integration Cooling Setpoint
(CP).
Available with neoStat HC only.
V4
Obj\Num: 18…35; (Adjustable)
Fan Control
Set the desired fan speed/mode.
Available with neoStat HC only.
V55
Obj\ENum; Adjustable
Values: 0=Off, 1=Low, 2=Medium, 3=High, 4=Auto
Fan Speed
Reports the current fan speed.
Available with neoStat HC only
V56
Obj\ENum
Values: 0=Off, 1=Low, 2=Medium, 3=High
Frost Protection Setpoint
Temperature maintained in standby,
holiday or away modes
V109
Obj\Num: 7…17; Adjustable
Hold Mode
Indicates if hold mode is active. The hold
function manually overrides the current
program for a period of time
V49
Obj\NoYes
Hold Temperature
Setpoint temperature when hold mode is
active. Set to activate hold temperature
for Default Hold Time, or ‘0’ to cancel hold
V24
Obj\Num; Adjustable
Hold Time Remaining (mins)
The time remaining in hold mode, if active.
Set a time to activate or extend the hold
time, or ‘0’ to cancel hold
V25
Obj\Num; Adjustable
Temporary Setpoint Active
Setpoint has been temporarily adjusted
using Hold Temperature, Integration
Setpoint, or Heating Setpoint
V62
Obj\NoYes
Floor Limit Reached
Indicates the floor has reached the floor
limit temperature
V20
Obj\NoYes
Floor Temperature Limit
Set an upper floor limiting temperature
V108
Obj\Num: 20…45; Adjustable