Model: NSC0250-FROST 

Owners Manual 

|

 

P a g e

 

www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119 

Advanced settings adjustment 

1.

 

Press and hold 

 button then press 

 and hold for 5 seconds until “0” is displayed 

2.

 

Press 

 button to switch from 0 to 8 (default password) 

3.

 

Press 

 to press enter after setting the correct password. F0 will be displayed. 

4.

 

Press 

 or 

 to select the parameter to be changed 

5.

 

Press 

 when a parameter is selected to see the current value and make changes 

6.

 

Press 

 or 

 to change the parameter to the desired value 

7.

 

Press 

 to save and exit parameters. If no button is pressed for 20 seconds the screen will return to the default 

screen and exit without saving parameter changes. 

Parameter List 

Parameter 

Description 

Range 

Factory 
Default 

Notes 

Constant Temperature Mode 

 

 

Intelligent Mode 

 

F0 

Temperature Setting 

F8 – F9 

45°F 

Constant Temperature 

F1 

Temperature Difference 

setting 

-27 - +9 

-3.6°F 

Intelligent Mode (ambient tracking) 

F2 

Cooling differential 

0.2 – 5.4 

0.5 

 

F3 

Control Method 

0 – 1 

Constant Temperature (0) or 

Intelligent Mode (1) 

F4 

High water temperature 

alarm 

2°F - 36°F 

18°F 

 

F5 

Low water temperature 

alarm 

2°F - 36°F 

27°F 

 

F6 

High ambient (room) 

temperature alarm 

104°F - 122°F 

113°F 

 

F7 

Password 

0 – 99 

 

F8 

Max target temp limit 

F0 - 104°F 

86°F 

 

F9 

Min target temp limit 

33.8°F - F0 

40°F 

WARNING: 

Do not run chiller 

lower than 40°F. This will damage 

the chiller and void your warranty.

 

 

Flow Alarm 

 

Condition 

Normal Flow Indicator 

Flow Alarm Indicator 

Buzzer 

Circulating Pump works properly 

 

 

 

Blockage in cooling water circulation line 

 

 

 

Low water level 

 

 

 

Circulation pump failure 

 

 

 

 