Chapter 12 – Adding an expansion cabinet
Page 97 of 536
Option 11C Compact
Planning, Installation, Fault Clearing and CCBR Guide
Procedure 5
Adding an expansion cabinet
1
Mount the expansion cabinet as described in
“Chapter 9 – Mounting the cabinets” on page 79
Make sure that it is mounted according to the equipment layout plan.
Make sure that it is securely mounted.
Note: The distance between the cabinets is limited by the length of
the A0632902 Plastic Fiber Optic Cable, which is 10 m (33 ft) long.
2
Install the cabinet ground wire as described in
“Chapter 10 – Installing the system ground” on page 85
.
Make sure that a minimum #6 AWG ground wire is used.
Make sure to test the ground.
3
Install the power supply as described in
.
Make sure the circuit breaker on the power supply is in the OFF
position.
Check the option switches on the power supply to make sure that they
are correctly set.
CAUTION
Static electricity can damage the components of power supplies
and circuit cards. Wear an anti-static wrist strap or, if one is not
available, touch the frame of the cabinet before handling the
power supplies or other circuit cards.
Summary of Contents for Meridian Meridian 1
Page 3: ...553 3121 210 Standard 3 0 January 1999 ...
Page 17: ...xiv Contents 553 3121 210 Standard 3 0 January 1999 ...
Page 97: ...Page 78 of 536 Chapter 8 Installing a new system 553 3121 210 Standard 3 0 January 1999 ...
Page 107: ...Page 88 of 536 Chapter 10 Installing the system ground 553 3121 210 Standard 3 0 January 1999 ...
Page 113: ...Page 94 of 536 Chapter 11 Installing the power supply 553 3121 210 Standard 3 0 January 1999 ...
Page 125: ...Page 106 of 536 Chapter 12 Adding an expansion cabinet 553 3121 210 Standard 3 0 January 1999 ...
Page 209: ...Page 190 of 536 Chapter 18 Connecting the trunks 553 3121 210 Standard 3 0 January 1999 ...
Page 323: ...Page 304 of 536 Chapter 21 Installing Hospitality 553 3121 210 Standard 3 0 January 1999 ...
Page 419: ...Page 400 of 536 Chapter 23 Pre programmed data 553 3121 210 Standard 3 0 January 1999 ...
Page 555: ...Page 536 of 536 Chapter 25 Fault locating and clearing 553 3121 210 Standard 3 0 January 1999 ...