40
DC power supply installation
Job aid: Bezel models
Figure 6
Bezel models 312096-A and 321325-A
Removing the power filler panel
A power filler panel maintains the proper cooling airflow in the Ethernet
Routing Switch 8600 chassis. You must remove the power filler panel from
the power bay when you install a power supply in a bay for the first time.
ATTENTION
To remove a power filler panel from the 8010co chassis with bezel model
312096-A installed, you must remove the bottom front bezel (see
"Bezel models 312096-A and 321325-A" (page 40)
). For instructions, see
“Removing the bottom bezel 312096-A of the 8010co chassis” (page 38)
.If you
replaced bezel 312096-A with the modified bezel model 321325-A, you need
not remove the bezel.
CAUTION
To maintain proper cooling, never operate the Ethernet Routing
Switch 8600 with an empty power supply bay. If you are
replacing a failed power supply and you do not have a power
filler panel, leave the failed power supply installed until a
replacement power supply is available.
Use the following procedure to remove the power filler panel.
Nortel Ethernet Routing Switch 8600
Installation — DC Power Supply
NN46205-307
02.02
19 December 2008
Copyright © 2008 Nortel Networks
.
Summary of Contents for 8004DC
Page 69: ......