January 2007
Replacing basic chassis components
1002rp Server Maintenance and Diagnostics
129
Replacing the fuse (AC system only)
The fuse is located below the power input socket on the rear panel. When
the server fuse blows, the server stops operating.
Requirements
You require the following:
an approved fuse for replacement
Two different types of fuses exist: one for North America, and one
for international use. Ensure that the fuse you are replacing has been
approved by Nortel for your region.
a flat-blade screwdriver
To replace the fuse
1
Power off the server.
2
Unplug the power cable from the wall outlet.
3
Unplug the power cable from the power input socket on the server.
4
Unscrew the fuse receptacle (see A in Figure 23 on page 130).
.
CAUTION
Risk of equipment damage and personal injury
Disconnect power from the server before replacing a fuse.
Summary of Contents for 1002rp
Page 6: ...Standard 1 11 6 CallPilot...
Page 14: ...Contents Standard 1 11 14 CallPilot...
Page 30: ...Troubleshooting your CallPilot system Standard 1 11 30 CallPilot...
Page 92: ...Using CallPilot Manager to monitor hardware Standard 1 11 92 CallPilot...
Page 108: ...Using CallPilot system utilities Standard 1 11 108 CallPilot...
Page 138: ...Replacing basic chassis components Standard 1 11 138 CallPilot...
Page 156: ...Replacing media drives Standard 1 11 156 CallPilot...
Page 190: ...Replacing voice processing boards Standard 1 11 190 CallPilot...
Page 216: ...Index Standard 1 11 216 CallPilot...
Page 217: ......