for the unit. Incoming field wiring and minimum size of 

electrical conductors and circuit protection must be in 

compliance with information listed on the outdoor unit 

data label. Any other wiring methods must be acceptable 

to authority having jurisdiction.

•  The outdoor unit requires both power and control circuit 

electrical connections. Refer to the wiring diagrams (

Figure 

14

Figure 15

Figure 16

, & 

Figure 17

)for identification and 

location of outdoor unit field wiring interfaces. Make all 

electrical connections in accordance with all applicable 

codes and ordinances.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to applicable local codes. See 

the unit rating plate for minimum circuit ampacity and 

maximum overcurrent protection limits.

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Connect the 

line-voltage leads to the terminals on the contactor inside 

the control compartment.

•  Use only copper wire for the line voltage power supply 

to this unit as listed in 

Table 1

. Use proper code agency 

listed conduit and a conduit connector for connecting 

the supply wires to the unit. Use of rain tight conduit is 

recommended.

•  208/230 Volt units are shipped from the factory wired for 

230 volt operation. For 208V operation, remove the lead 

from the transformer terminal marked 240V and connect 

it to the terminal marked 208V.

•  Optional equipment requiring connection to the power or 

control circuits must be wired in strict accordance of the 

NEC (ANSI/NFPA 70), applicable local codes, and the 

instructions provided with the equipment.

Grounding

 WARNING:

The unit cabinet must have an uninterrupted or 

unbroken electrical ground to minimize personal 

injury if an electrical fault should occur. Do not 

use gas piping as an electrical ground!

3. Check the actual size of the new orifice. 

NOTE:

 The size 

is stamped on its side. Do not use pin gauges to measure 

the orifice diameter.

4. Insert the new orifice into the valve body, with the rounded 

end facing into the valve. See 

Figure 2 (page 4)

.

 CAUTION:

To prevent damage to the unit or internal 

components, it is recommended that two 

wrenches be used when loosening or tightening 

nuts. Do not over tighten!

5. Realign the assembly nut on the valve body and hand 

tighten both components. Mark a line on both bodies and 

then tighten an additional ¼ turn using two wrenches. The 

movement of the two lines will show how much the nut is 

tightened.

ELECTRICAL WIRING

 WARNING:

ELECTRICAL SHOCK OR FIRE HAZARD

To avoid risk of electrical shock, personal injury, 

or death, disconnect all electrical power to the unit 

before performing any maintenance or service. The 

unit may have more than one electrical supply.
Label all wires prior to disconnection when servicing 

the unit. Wiring errors can cause improper and 

dangerous operation

•  All electrical connections must be in compliance with all 

applicable local codes and ordinances, and with the current 

revision of the National Electric Code (ANSI/NFPA 70).

•  For Canadian installations the electrical connections and 

grounding shall comply with the current Canadian Electrical 

Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

  Verify that the voltage, frequency, and phase of the supply 

source match the specifications on the unit rating plate.

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

Refer to the unit wiring label for proper high and low 

voltage wiring.

  Verify factory wiring is in accordance with the unit wiring 

diagram. Inspect for loose connections. See 

Figure 14 

(page  16)

Figure 15 (page 17)

, 

Figure 16 (page 

18)

, & 

Figure 17 (page 19)

.

Line Voltage

•  A wiring diagram is located on the inside cover of the 

electrical box of the outdoor unit. The installer should 

become familiar with the wiring diagram before making 

any electrical connections to the outdoor unit.

• 

An electrical disconnect must be located within sight 

of and readily accessible to the unit.

 This switch shall 

be capable of electrically de-energizing the outdoor unit.

•  Line voltage to the unit should be supplied from a dedicated 

branch circuit containing the correct fuse or circuit breaker 

COPPER WIRE SIZE — AWG

(1% VOLTAGE DROP)

SUPPLY WIRE LENGTH-FEET

SUPPLY

CIRCUIT

AMPACITY

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

Table 1. Copper Wire Size

Summary of Contents for SH1BF4M1SP Series

Page 1: ...ANT CHARGING 8 Charging the Unit in AC Mode 9 Charging the Unit in Heating Mode 9 Charging Charts Application Notes 9 Figure 8 Charging Chart for 2 Ton Models 10 Figure 9 Charging Chart for 2 5 Ton Models 10 Figure 10 Charging Chart for 3 Ton Models 11 Figure 11 Charging Chart for 3 5 Ton Models 11 Figure 12 Charging Chart for 4 Ton Models 12 Figure 13 Charging Chart for 5 Ton Models 12 Heat Mode ...

Page 2: ...lation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious personal injury or death The installer must comply with all local codes and regulations which govern the installation of this type of equipment Local codes and...

Page 3: ...diately with the carrier Please consult your dealer for maintenance information and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine the best location for mounting the outdoor unit Overheadobstructions poorlyventilatedareas andareas subject to accumulation of debris should be avoided See Figure 1 S...

Page 4: ...ces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dryer must be installed in strict accordance with the manufacturer s installation instructions Optional equipment such as liquid line solenoid valves low ambient etc should be installed in strict accordance with the manufacturer s installation instruc...

Page 5: ...o the unit or internal components it is recommended that two wrenches be used when loosening or tightening nuts Do not over tighten 5 Realign the assembly nut on the valve body and hand tighten both components Mark a line on both bodies and then tighten an additional turn using two wrenches The movement of the two lines will show how much the nut is tightened ELECTRICAL WIRING WARNING ELECTRICAL S...

Page 6: ...omfireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat manufacturer s instruction sheet for detailed mounting and installation information Outdoor Fan Motor If the unit utilizes a 2 speed condenser fan motor this motor will operate on low speed when in low cooling and on high speed when in high cooling A relay within ...

Page 7: ...em mode to COOL and the fan modetoAUTO Graduallylowerthethermostattemperature setpoint below room temperature and verify the outdoor unit and indoor blower energize 2 Verify blower wheel is spinning in direction indicated by arrow Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen foranyunusualnoises Ifunusualsoundsoccur determine the so...

Page 8: ... pan in order to clear the bottom flange from the base pan See Figure 6 3 Swing the bottom of the panel out and pull the panel down to remove it from the unit Panel Installation 1 Insert the top corners of side panel flanges into the corner post channels as shown in Detail A in Figure 7 2 Slide the panel up into the top pan You may need to push on the center of the panel at the top in order to cle...

Page 9: ...il the system is correctly charged If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant andrepeatSteps1through3untilthesystemiscorrectly charged Charging the Unit in Heating Mode Applies to SH1BF4M2SX 5 Ton Units only 1 Evacuate the unit to 350 500 microns 2 Weigh in the proper charge ...

Page 10: ...below curve SH1BF4M1SP30K Charging Chart Cooling Figure 9 Charging Chart for 2 5 Ton Models TXV Matches Figure 8 Charging Chart for 2 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when below curve S...

Page 11: ...elow curve SH1BF4M1SP36K Charging Chart Cooling Figure 10 Charging Chart for 3 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when below curve SH1BF4M1SP42K Charging Chart Cooling Figure 11 Charging ...

Page 12: ...below curve SH1BF4M1SP48K Charging Chart Cooling Figure 12 Charging Chart for 4 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F SH1BF4M2SX60K Charging Chart Cooling Remove refrigerant when above curve Add refrigerant when below curve Figure 13 Charging...

Page 13: ...he rating label However if an inspection with these verification charts does not line up with the values shown and the ambient temperature is above 50 F then a more accurate way to inspect the system for proper charge is with the cooling mode charging charts Switch the unit into cooling mode and allow it to operate and stabilize for a few minutes then inspect the unit operation with the cooling mo...

Page 14: ... 264 108 83 282 290 118 116 340 348 130 150 397 406 141 57 253 262 76 60 255 264 86 63 257 266 96 66 259 268 106 84 289 297 116 117 347 355 125 151 404 413 135 58 260 269 74 61 261 270 84 64 262 271 94 67 263 271 104 85 296 304 113 118 354 362 121 152 411 420 129 59 267 276 72 62 267 276 82 65 267 275 92 68 266 275 102 86 303 311 110 119 361 369 116 153 418 427 123 60 274 283 70 63 273 282 80 66 2...

Page 15: ...ESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP 35 212 223 134 49 235 245 135 64 257 267 136 78 280 290 138 94 293 303 146 111 321 331 160 128 348 359 174 36 219 230 132 50 241 251 133 65 262...

Page 16: ...n systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en c...

Page 17: ...ll power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transforme...

Page 18: ...supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 1 Couper le courant avant...

Page 19: ...nections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 1 Couper le courant avant de faire let...

Page 20: ... NO Is the heat anticipator setting correct If Applicable YES NO REFRIGERATION SYSTEM Wasunitgiven24hrwarmupperiod for crankcase heaters YES NO Stage 1 Liquid Pressure high side Stage 1 Suction Pressure low side REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ordering replacement parts ELECTRICAL Capacitor...

Reviews: