background image

3

 Check the electrical supply and verify the power supply 

is adequate for unit operation. The system must be wired 

and provided with circuit protection in accordance with 

local building codes. If there is any question concerning 

the power supply, contact the local power company.

 The indoor section (air handler, furnace, etc) should be 

installed before routing the refrigerant tubing. Refer to the 

indoor unit's installation instructions for installation details.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins 

are straight. If necessary, comb fins to remove flattened 

or bent fins. Claims for damage (apparent or concealed) 

should be filed immediately with the carrier.

 Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 

instructions before installing the unit.

Packaging Removal

NOTE: 

To prevent damage to the tubing connections, carefully 

remove the carton and user’s manual from the equipment. 

Discard the shipping carton.

Locating the Air Conditioner

• Survey the job site to determine the best location for 

mounting the outdoor unit.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance. See 

Figure 1

 for minimum clearances to 

obstructions.

•  Overhead obstructions (

Figure 1

), poorly ventilated areas, 

and areas subject to accumulation of debris should be 

avoided.

• The unit should not be placed under roofing or other 

overhangs which are not guttered; that would allow water 

or ice to fall into the unit's discharge opening.

•  Consideration should be given to availability of electric 

power, service access, noise, and shade.

Clearance Requirements

•  The general recommendation is for the units to be installed 

with 18 inches of clearance on 3 sides and with 24 inches 

of clearance for the service access side to the unit’s service 

panel.

•  For installations that are space constrained, one side of the 

unit, adjacent to the service panel, may have its air side 

clearance reduced to a minimum of 6 inches.  The other 

side adjacent to the service panel requires 24 inches for 

service access.  The remaining two sides, at a minimum 

shall require 12 inches of clearance.

• A minimum of 18 inches between two units must be 

maintained for proper performance.

Ground Installations

The unit should be installed on a solid base, that is level and 

located at least 2 inches above grade*.

Note:

 It is recommended that poured concrete mounting 

bases are not be attached or adjacent to the building 

structure or foundation.

Roof Installation

The unit may only be installed on a structure that is capable 

of supporting the total weight of the unit and its anchorage. 

The support for the base of the unit may not slope more than 

1/8 inch per foot. The minimum clearance for the base of the 

unit to the roof-line is 2 inches* for residential applications.

Note on ground and roof clearances:

 Heat pump and 

other applications should account for the accumulation 

of snow and raise the base of the unit accordingly. (At a 

minimum, a 6 inch clearance is required.)

Accessory Mounting Kits

Kits for other mounting methods and accessories can be 

found in the technical sales literature for the unit. Or the 

literature library on NortekHVAC.com.

Connecting Refrigerant Tubing Between the Indoor 

& Outdoor Unit

 CAUTION:

When connecting refrigerant line-sets together, 

it is highly recommended that dry nitrogen be 

flowing through the joints during brazing to 

prevent internal oxidation and scaling.  Copper 

oxides, internal to the system can damage the 

compressors bearings and seals, block small 

orifices and microchannels or otherwise damage 

components.

Figure 1. Clearance Requirements

24" for 

Service Access

12" or 18”

See Note

12" or 18”

See Note

DO NOT

OBSTRUCT

TOP OF UNIT

NOTE:

 Units require full perimeter clearances.

Installer must maintain 18” between two units.

18” Recommended.

(Minimum allowable clearance

of 6” to structure on

1 side of the unit only.)

Summary of Contents for SA3BF4M2SN Series

Page 1: ...llation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE INSTALLATION INSTRUCTIONS IMPORTANT SAFETY INFORMATION 2 AIR CONDITIONER INSTALLATION 2 General Information 2 Before You Install this Unit 2 Packaging Removal 3 Locating the Air Conditioner 3 Clearance Requirements 3 Ground Installations 3 ...

Page 2: ...ions Consult local building codes and the National Electrical Code ANSI for special installation requirements All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Electric Code Part 1 CSA C 22 1 This equipment contains liquid and gaseous refrigerant underhighpressure DONO...

Page 3: ...learancefortheserviceaccesssidetotheunit sservice panel Forinstallationsthatarespaceconstrained onesideofthe unit adjacent to the service panel may have its air side clearance reduced to a minimum of 6 inches The other side adjacent to the service panel requires 24 inches for service access The remaining two sides at a minimum shall require 12 inches of clearance A minimum of 18 inches between two...

Page 4: ...panel and sized as shown on the unit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity MCA and maximum overcurrent protection MOP limits CAUTION When performing brazing operations always protect the system components and seals from the possibility of heat damage Remove all caps plugs and Schrader valve cores on piping system components just...

Page 5: ...y branch circuits for both the indoor and outdoor equipment is the proper voltage for the equipment and that the overcurrent protection device is properly sized and that the supply wiring is the correct gauge Verifythatthelowvoltageandthermostatwiringaresecurely connected to the proper terminals for all equipment Verify that the low voltage transformer has been properly connected with that unit s ...

Page 6: ... and Figure 3 page 6 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or grease to motors unequipped with oil tubes or grease fittings Most outdoor unit motors are manufactured with sealed permanently lubricated bearings that are designed for the life of the equipmen...

Page 7: ...s perform the following steps 1 Determinetherecommendedchargeaddition ifapplicable for the system being installed This information is in the unit s QRD Quick Reference Data sheet 2 Calculate the amount of additional refrigerant needed for thelinesetlengthoftheactualinstallation Thisinformation is on the first page of the unit s QRD Quick Reference Data sheet 3 Weigh in the additional charge amount...

Page 8: ...see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Caution The low voltage wiring should not be grounded to this unit 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 volt a la terre 103...

Page 9: ...Phase 60 Hz WIRING DIAGRAM 10398310 Replaces 7110150 7 21 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR L FAN RELAY CC OFR NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For rep...

Page 10: ...Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 ci...

Page 11: ...11 ...

Page 12: ...d serial number of the unit when ordering replacement parts ELECTRICAL Capacitors Temperature Limit Switches Compressors Thermostats Contactors Time Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPONENTS Blower Assembly Fan Grille Cabinet Panels Filter Driers Expansion Valves Specifications illustrationssubjecttochangewithoutnoticeorincurringobligations 07 22 O...

Reviews: