16
STATUS LED
STATUS LED DESCRIPTION
STATUS LED TROUBLESHOOTING INFORMATION
Yellow “ALERT”
Flash Code 8
Welded Contactor
Compressor always runs
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
Yellow “ALERT”
Flash Code 9
Low Supply Voltage
Voltage below 18V
1. Control Circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low)
LOCKOUT FLASH CODES
Red
“LOCKOUT”
Flash Code 2
Yellow Off
Compressor (Pressure) Trip
Compressor is locked out
after 4 consecutive or 10 total
compressor (pressure) trip events
1. Condenser fan is not running
• Check fan capacitor
• Check fan wiring and connectors
• Check fan motor for failure or blockage
2. High head pressure
• Check high pressure switch if present in system
• Check if system is overcharged with refrigerant
• Check for non-condensable in system
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Return air duct has substantial leakage
Red
“LOCKOUT”
Flash Code 3
Yellow Off
Pressure Switch Cycling
Compressor is locked out after 4
consecutive or 10 total pressure
cycling events
1. Time delay relay or control board defective
2. If high pressure switch present go to Flash Code 2 information
Red
“LOCKOUT”
Flash Code 4
Yellow Off
Locked Rotor
Compressor is locked out after 10
consecutive locked rotor events
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
• Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
• Measure compressor oil level
Red
“LOCKOUT”
Flash Code 5
Yellow Off
Compressor (Moderate Run)
Trip
1. Evaporator blower is not running
• Check blower relay coil and contacts
• Check blower motor capacitor
• Check blower motor for failure or blockage
• Check evaporator blower wiring and connectors
• Check indoor blower control board
• Check thermostat wiring for open circuit
2. Faulty metering device
• Check TXV bulb installation (size, location and contact)
• Check if TXV/fi xed orifi ce is stuck closed or defective
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Low refrigerant charge
Red
“LOCKOUT”
Flash Code 6
Yellow Off
Open Start Circuit
Current only in run circuit
1. Run capacitor has failed
2. Open circuit in compressor start wiring or connections
• Check wiring and connectors between supply and the compressor “S” terminal
3. Compressor start winding is damaged
• Check compressor motor winding resistance
Red
“LOCKOUT”
Flash Code 7
Yellow Off
Open Run Circuit
Current only in start circuit
1. Open circuit in compressor run wiring or connections
• Check wiring and connectors between supply and the compressor “R” terminal.
Confirm proper wire routing as shown in
2. Compressor run winding is damaged
• Check compressor motor winding resistance
Red
“LOCKOUT”
Flash Code 10
Over Current Protection
Current to PROT is greater than
2A mps
1. Check for contactor shorted to ground
2. Check for mis-wiring to the PROT terminal
* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated. Trip and alert LED’s flashing at same time
means control circuit voltage is too low for operation.
Table 1. CoreSense
TM
Diagnostics & Troubleshooting - Continued