background image

10

Ambient Sensor Mounting

For optimum performance of the heat pump system, the 

ambient sensor must be mounted on the outside of the 

unit. See 

Figure 6 (page 10)

.

1. Remove the mounting bracket wire tied to the control 

bracket and all hardware included in the packet.

2. Remove star bushing from 7/8” hole in corner panel of 

the unit. See 

Figure 6

.

3. Route the ambient sensor through the 7/8” hole in the 

corner panel of the unit, and then through the 7/8” hole 

in the mounting bracket.

4. Route the sensor through the star bushing. Use the star 

bushing to secure the mounting bracket to the unit.

5. Secure the ambient sensor inside the plastic clip and 

secure it to the mounting bracket with the screw and 

nut provided.

6. Install one spacer nut between the plastic clip and 

mounting bracket.

7. Bend the mounting bracket into position and screw the 

mounting bracket to the corner panel.

Defrost Board Operation

1. Heat Pump operates in heating mode until the 

combination of outdoor ambient and outdoor coil 

temperatures initiate a defrost cycle. The outdoor coil 

temperature must be at or below 25.5°F before the 

defrost cycle begins.

2. There must be a minimum of 35 minutes between 

defrost cycles. After this time, coil temperature & outdoor 

ambient will drive a call for defrost after conditions are 

met continuously for 30 seconds before a defrost cycle 

is initiated. 

3. Outdoor fan is off during defrost operation.

4. The defrost cycle ends when the outdoor temperature 

reaches 50°F-80°F, dependent on TERM TEMP jumper 

position (default 70°F-no jumper) or if the defrost 

terminate time of 11 minutes is reached.

See "Control Board Status Indicators" for operation 

and fault codes, 

Table 4 (page 19).

Forced Defrost When the Following Conditions 
are Met:

•  LPS and HPS are closed 

•  Y1 input is active 

•  O input is either active or inactive 

•  TEST terminals shorted for more than three seconds 

Compressor will start and unit will operate in DEFROST 

mode.

Unit will run in DEFROST mode after pins have been 

shorted at least 3 seconds regardless of whether short 

is removed or not. 
Qualifying conditions of minimum ambient or coil 

temperature do not need to be met when the unit is forced 

into defrost. If the short across the TEST pins exist, the 

unit will stay in DEFROST as long as the short remains 

or until the TERMINATE TIME is reached (11 minutes). 

This will happen regardless of coil temperature. 
W2 OUT is active during this time if the O input is inactive. 
If after 11 minutes the short remains, the unit shall not 

run in any mode and the display shall flash 'DF' until the 

short is removed. 
W2 OUT shall remain on during the whole time that the 

short exists, if the O input is inactive.

Crankcase Heater (CCH) Operation

The outdoor temperature is measured by the ambient 

temperature sensor. The CCH is enabled during first 2 

minutes after board power up regardless of any other 

condition.

•  The CCH is disabled during compressor operation. 

•  The CCH is disabled when OD temperature > 70F. 

•  The CCH is enabled when OD temperature < 71F.

Optional Outdoor Thermostat (Field Supplied)

An outdoor thermostat can be installed in the field with 

2-stage electric heat by removing the orange wire from the 

W2

 terminal on the unit terminal block and re-connecting 

it to the outdoor thermostat. Connect the other side of 

the outdoor thermostat to 

W2

 on the unit terminal block

.

.

Optional Electric Heater Kits

Optional electric heater kits are available in 5 kw through 

20 kw heating capacities. Single package heat pumps 

are designed to allow optional electric heat to be field 

installed as required by the building’s particular heating 

load. The options available for each unit are shown in the 

heater kit installation instructions. A heating/cooling 24V 

thermostat should be used when an electric heater kit is 

installed. 

NOTE:

 A 2-stage heating thermostat is required 

if installing a 2-stage heater kit. As previously noted, a 

field installed circuit breaker kit is available as a means 

of electrical disconnect for the unit. Install the heater kits 

as directed by the instructions supplied with the heater 

kit. Follow all cautions and warnings as directed.

Figure 6. Ambient Sensor Mounting

Bolt

Nut

Nut

Ambient Sensor

Plastic Clip

Star Bushing

Summary of Contents for Q104SD Series

Page 1: ...mon sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety wa...

Page 2: ...ing an R 410A Unit in AC Mode 12 Charging an R 410A Unit in Heating Mode 12 Verification of charge in Heat Mode 12 HEAT PUMP MAINTENANCE 12 FIGURES TABLES 13 Figure 7 Q104SD Heat pump Dimensions 13 Ta...

Page 3: ...oorfan compressor andblowermotorwill all cycle on and off to maintain the indoor temperature at the desired cooling level NOTE If the temperature level is re adjusted or the system mode is reset the f...

Page 4: ...selector setting HEAT PUMP MAINTENANCE CAUTION Shut off all electrical power to the unit before performing any maintenance or service on the system Failure to comply may result in personal injury or d...

Page 5: ...asoline and any other flammable vapors and liquids in the vicinity of the unit WARNING The safety information listed below must be followed during the installation service and operation of this unit U...

Page 6: ...ng load of the area to be conditioned must be calculatedandasystemofthepropercapacityselected It is recommended that the area to be conditioned be completely insulated and vapor sealed Check the elect...

Page 7: ...beneath the unit Rigging Hoisting WARNING To avoid the risk of property damage personal injury or death it is the rigger s responsibility to ensure that whatever means are used to hoist the unit are s...

Page 8: ...ning the correct fuse or circuit breaker for the unit Incoming field wiring and minimum size of electrical conductors and circuit Units require horizontal roof curb and return air kit for horizontal i...

Page 9: ...the system when very high pressures occur during abnormal conditions Under normal conditions the switch is closed If the discharge pressure rises above 650 psig then the switch will open and de energi...

Page 10: ...seconds regardless of whether short is removed or not Qualifying conditions of minimum ambient or coil temperature do not need to be met when the unit is forced into defrost If the short across the TE...

Page 11: ...ify the unit is level and allows condensate to drain Verify the outdoor coil and top of the unit are free from obstructions and debris and all equipment access control panels are in place Verifythatth...

Page 12: ...he unit rating plate Return to the system when the outdoor temperature is 60 degrees F or higher and follow the steps defined in Charging an R410A Unit in AC Mode NOTE Unit charge MUST be verified in...

Page 13: ...2 29 5 26 0 43 0 39 3 X60K 530 29 5 26 0 43 0 39 3 FIGURES TABLES Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT O...

Page 14: ...t Defrost Board L 24V Output Fault Monitor See thermostat manual for compatibility Brown Orange Accesory Heat Plug Indoor Thermostat Sub Base Unit Terminal Block 1 2 3 4 5 6 7 8 9 to Blower Relay Cool...

Page 15: ...See installation instructions in the branding kit 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la...

Page 16: ...16 Figure 10 Charging Chart for 2 Ton Units Figure 11 Charging Chart for 2 5 Ton Units Charging Charts Cooling...

Page 17: ...17 Figure 13 Charging Chart for 3 5 Ton Units Figure 12 Charging Chart for 3 Ton Units...

Page 18: ...18 Figure 14 Charging Chart for 4 Ton Units Figure 15 Charging Chart for 5 Ton Units...

Page 19: ...9 1380 22 9 1315 24 0 1215 26 0 Tap T5 1850 17 1 1795 17 6 1740 18 2 1710 18 5 1640 19 3 1595 19 8 1540 20 5 1475 21 4 X48K Tap T1 950 33 2 900 35 1 865 36 6 730 43 4 670 47 0 585 54 2 510 62 2 Tap T...

Page 20: ...VOLTS Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct YES NO REPLACEMENT PARTS Replacement parts are available through your distributor...

Reviews: