Nortek PPG3HE Series Installation Instructions Manual Download Page 20

20

unit data label. To determine the firing rate, follow the 

steps below:

1. Obtain the gas heating value (HHV) from the gas supplier.

2. Shut off all other gas fired appliances.

3. Start the unit in LOW heating mode and allow it to run 

for at least 3 minutes.

4. Measure the time (in seconds) required for the gas 

meter to complete one revolution.

5. Convert the time per revolution to cubic feet of gas per 

hour using 

Table 15 (page 33)

.

6.Multiply the gas flow rate in cubic feet per hour by the 

heating value of the gas in Btu per cubic foot to obtain 

the firing rate in Btu per hour. See 

Example

.

EXAMPlE

(INPUT --> hIgh = 100,000 / LOW = 65,000)

•  Time for 1 revolution of a gas meter with a 1 cubic foot dial 

= 58 seconds.

•  From 

Table 15

, read 62 cubic feet gas per hour.

•  Local heating value of the gas (obtained from gas supplier) 

= 1,040 Btu per cubic foot.

•  Low Input rate = 1,040 x 62 = 64,480 Btuh = PASS

7. Record your findings and move unit operation to HIGH 

heating mode and Repeat Steps 3-6.

8. Adjust the manifold pressure if necessary by following 

the steps in the Measuring & Adusting the Manifold 

sections. For additional information about elevations 

above 2,000 feet, see High Altitude Conversion section 
(

page 16

).

Measuring the Manifold Pressure

The manifold pressure must be measured for both LOW 

and HIGH fire by installing a pressure gauge (Manometer, 

Magnehelic Meter, etc.) to the outlet end of the gas valve 

as follows:

1. Turn off all electrical power to the appliance.

2. Shut OFF the gas supply at the manual shutoff valve 

located outside of the appliance.

3. Using a 3/16” Allen wrench, remove the manifold 

pressure tap plug located on the outlet side of the gas 
valve (

Figure 7

).

4. Install an 1/8” NPT pipe thread fitting, that is compatible 

with a Manometer or similar pressure gauge.

5. Connect the Manometer or pressure gauge to the 

manifold pressure tap.

6. Set the room thermostat 1 degree above room 

temperature  To start the furnace on LOW fire.

7. Allow the furnace to operate for 3 minutes and then 

check the manifold pressure. Compare the measured 
value with the value shown in 

Table 3 (page 17)

 for 

Natural Gas and 

Table 4 (page 17)

 for LP/Propane 

gas. If the manifold  pressure is not set to the appropriate 

pressure, then it must be adjusted.

8. Record your findings and move unit operation to HIGH  

heating mode and Repeat Steps 3-6.

Adjusting the Manifold Pressure

notE:

 If adjustment must be made to either LOW or 

HIGH fire settings perform the following steps:

1. Remove the cap screw from the top of the gas valve 

regulator (

Figure 7

).

2. Using a screwdriver or Allen wrench (where appropriate), 

slowly turn the adjustment screw till the appropriate 
manifold pressure listed in 

Table 3

 or 

Table 4

, or the 

LOW and/or HIGH firing rate for your specific gas HHV 

is achieved.

 notE:

 Turning the screw clockwise increases the 

pressure, turning the screw counter-clockwise 

decreases the pressure. To prevent the screw from 

backing all the way out from the valve, turn the screw 

slowly.

3. Replace and tighten the cap screw or the plastic cap 

over the adjustment screw.

Removing the Manometer/Pressure Gauge

After the LOW and HIGH manifold pressures are properly 

adjusted, the Manometer or pressure gauge must be  

removed from the gas valve.

1. Turn the thermostat to its lowest setting.

2. Turn OFF the main gas supply to the unit at the manual 

shut-off valve, which is located outside of the unit.

3. Turn OFF all of the electrical power supplies to the unit.

4. Remove the pressure gauge adapter from the gas valve 

and replace it with the 1/8” NPT manifold pressure plug 

that had been removed earlier. 

notE:

 Make sure the 

plug is tight and not cross-threaded.

5. Turn ON the electrical power to the unit.

6. Turn ON the main gas supply to the unit at the manual 

shut-off valve.

Verifying Over-Temperature Limit Control 
Operation

1. Verify the louvered control access panel is in place and 

that there is power to the unit.

2. Block the return airflow to the unit by installing a close-

off plate in place of or upstream of the filter.

Inlet

Pressure

Tap

Manifold

pressure

Tap

2-STAGE GAS VALVE

Model VR9205Q1127

ON / OFF

Switch

High Input

Adjusting

Screw

Lo Input 

Adjusting

Screw

Cap

Screws

Figure 7. Regulator Capscrew & Tap Locations

Summary of Contents for PPG3HE Series

Page 1: ...RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra ner des blessures graves la mort ou des dommages mat riels L installation et l entretien doivent tre effec...

Page 2: ...Stage Operation 23 De Humidification Control 23 Fan Mode 23 COMPONENT FUNCTIONS 23 equipment MAINTENANCE 24 Heat Exchanger Burner Maintenance 24 Cleaning of Burners 25 REPLACEMENT PARTS 25 Troublesho...

Page 3: ...ion maintenance or repair may expose you to fiberglass insulation Breathing this material may cause respiratory irritations Fiberglass insulation may also cause eye irritation skin sensitization or ot...

Page 4: ...e 28 Table 10 page 29 Table 11 page 30 Table 12 page 31 Table 13 page 32 and the rating plate for the proper circulating air flow and temperature rise It is important that the duct system be designed...

Page 5: ...reas and areas subject to accumulation of debris should be avoided Do not place the unit in a confined space or recessed area where discharge air from the unit to re circulate into the condenser air i...

Page 6: ...outdoors No additional venting shall be used Do not vent the unit through a conventional venting system The vent and drain assembly must be installed to assure proper operation of the unit Figure 2 sh...

Page 7: ...the unit for ventilation or to improve indoor air quality the system must be designed so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor...

Page 8: ...ved duct sealing methods to ensure an air and watertight seal is achieved Rooftop Rooftop installations must be located according to local building codes or ordinances and these requirements The roof...

Page 9: ...filter sizes refer to Table 1 page 10 Allreturnairmustpassthroughthefiltersbeforeentering the evaporator coil It is important that all filters be kept cleanandreplacedfrequentlytoensureproperoperatio...

Page 10: ...imate Filter Area Sq In 30 20 2 14 x25 700 1300 700 24 1 12 x20 and 1 16 x25 640 34 20 2 16 x25 900 1400 800 24 1 12 x20 and 2 10 x25 740 38 20 2 18 x25 1100 1600 900 24 1 12 x20 and 2 12 x25 840 42 2...

Page 11: ...g requirements Verify factory wiring is in accordance with the unit wiring diagram Figure 13 page 37 Figure 14 page 38 Figure 15 page 39 Make sure the connections didn t loosen during shipping or inst...

Page 12: ...cal thermostat connection The control circuit wiring must comply with the current provisions of the NEC ANSI NFPA 70 and with applicable local codes having jurisdiction Thermostat connections should b...

Page 13: ...icing continues raise the selected airflow to the next higher tap For maximum dehumidification and energy efficiency select an airflow near the middle or bottom of the CFM range for that nominal capa...

Page 14: ...all for dehumidification If a humidistat is not available it is an acceptable option to directly jumper the R DEHUM on the blower control board NOTE This option will always operate the blower at 75 th...

Page 15: ...ground joint union external to the unit The shut off valve should be readily accessible for service and or emergency use Consult the local utility or gas supplier for additional requirements regarding...

Page 16: ...theinputrate must be reduced 4 per 1 000 feet of altitude Example 12 at 3 000 feet 16 at 4 000 feet etc Deration is necessary to compensate for low atmospheric pressure at high altitudes LP Propane Ga...

Page 17: ...Gas Orifice Size Rise Range oF Max Outlet Air Temp Maximum External Static Pressure E S P in WC Net Cooling Capacity BTUH Blower Size Motor HP X24K060 X XA 10 0 4 5 3 5 60 000 57 000 39 000 37 050 45...

Page 18: ...han 12 hrs Failure to comply may result in damage or cause premature failure of the system Air Circulation Leave the thermostat system mode on OFF and set the fan mode to ON Blower should run continuo...

Page 19: ...ide must be shielded against direct radiation from the heat exchanger to avoid false readings 2 Adjust all registers and duct dampers to the desired position Run the unit for 10 to 15 minutes before t...

Page 20: ...manifold pressure Compare the measured value with the value shown in Table 3 page 17 for Natural Gas and Table 4 page 17 for LP Propane gas Ifthemanifold pressureisnotsettotheappropriate pressure the...

Page 21: ...de to AUTO Gradually lower the thermostat temperaturesetpointbelowroomtemperatureandverify the compressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify...

Page 22: ...on High speed for the first 15 seconds of any heating cycle After this 15 second period the control switches the gas valve to Low fire and inducer to Low speed if no second stage W2 demand is present...

Page 23: ...e low voltage field connection board and connect the other side to the DEHUM terminal on the blower control board Wire the humidistat to close on rise in humidity For dehumidification the DEHUM input...

Page 24: ...potentially hazardousconditionsincludingcarbonmonoxide poisoning that could result in personal injury or death Maintain heat exchanger and burners The furnace should operate for many years without exc...

Page 25: ...ower Assembly Fan Grille Burner Manifold Filter Driers Burners Orifices Gaskets Cabinet Panels Heat Exchanger Expansion Valves Table 5 Furnace Control Board Fault Conditions Diagnostic Description Gre...

Page 26: ...DUCT OPENING HORIZONTAL RETURN DUCT OPENING 4 0 1 75 9 75 24 75 CONDENSING COIL C 30 89 13 5 16 0 13 5 16 0 4 0 4 0 13 5 16 0 13 5 55 8 12 45 9 75 24 75 1 75 8 75 12 45 17 50 C 16 0 HORIZONTAL SUPPLY...

Page 27: ...34 26 0 27 0 35 31 3 55 8 47 5 R8HE X48C096X 455 482 27 5 26 5 43 39 3 55 8 47 5 R8HE X48D096X 472 499 27 0 27 0 43 39 3 55 8 47 5 R8HE X60C096X 485 510 28 0 26 5 47 43 3 55 8 47 5 R8HE X60D096X 502 5...

Page 28: ...Rise CFM Rise 1 2 3 4 CFM Rise CFM Rise 0 0 0 0 600 57 800 66 0 0 0 0 885 55 1180 64 1 0 0 0 656 52 875 60 1 0 0 0 938 52 1250 61 0 1 0 0 694 49 925 57 0 1 0 0 990 49 1320 58 1 1 0 0 750 46 1000 53 1...

Page 29: ...0 60 0 70 0 80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 783 67 740 71 696 76 645 82 594 89 554 95 514 103 472 112 429 123 1 0 0 0 851...

Page 30: ...0 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1218 58 1175 60 1132 62 1097 64 1062 66 1024 69 986 71 950 74 914 77 1 0 0 0 1270 55 1230 57 119...

Page 31: ...0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1308 55 1252 57 1196 60 1139 63 1082 66 1025 70 967 74 915 78...

Page 32: ...80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1308 67 1252 70 1196 74 1139 77 1082 81 1025 86 967 91 915 96 863 102 1 0 0 0 1363 65 1309...

Page 33: ...IC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692...

Page 34: ...ir la compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais uti...

Page 35: ...mum Circuit Ampacity Maximum Over current Protection RLA Min Max RLA LRA R8HE X36C080X High 80 000 0 30 208 230 3 60 187 253 11 6 73 1 5 7 0 23 0 30 Low 52 000 R8HE X36D080X High 80 000 0 30 460 3 60...

Page 36: ...WER OFF DELAY THERMOSTAT CONNECTIONS NEUTRALS FLAME 3 AMP FUSE INPUTS ON Figure 12 Ignition Control Board 624817 Figure 10 Two Stage Heating Single Stage Cooling Configuration TERMINAL STRIP THERMOSTA...

Page 37: ...Fault On Flash Communications Fault Flash Flash Blower Control Diagnostic Description Green LED Red LED 711318C Replaces 711318B 11 14 Y2 E O Y1 2 W 1 W 1 A C G R COM 230 24V 208 IGNITOR FLAME SENSOR...

Page 38: ...n remove wire from 230V tap and place on 208V tap SEE NOTE 6 711383A Replaces 7113830 11 14 Y2 E O Y1 G C A1 W1 W2 R COM 230 24V 208 IGNITOR FLAME SENSOR 2 STAGE GAS VALVE HIGH TEMP LIMIT FLAME ROLL O...

Page 39: ...7113840 11 14 460V 230V COM FUSE Y2 E O Y1 2 W 1 W 1 A C G R COM 230 24V 208 IGNITOR FLAME SENSOR 2 STAGE GAS VALVE HIGH TEMP LIMIT FLAME ROLL OUT LIMIT INDUCER LIMIT HIGH PRESSURE SWITCH 11 4 1 8 7...

Page 40: ...move refrigerant when above curve Add refrigerant when below curve Figure 16 Charging Chart for 2 Ton Units 260 280 300 320 340 360 380 400 420 440 460 480 500 80 85 90 95 100 105 110 115 120 Liquid T...

Page 41: ...ant when below curve Remove refrigerant when above curve 220 240 Figure 18 Charging Chart for 3 Ton Units 280 300 320 340 360 380 400 420 440 460 480 500 80 85 90 95 100 105 110 115 120 Liquid Tempera...

Page 42: ...t when above curve Add refrigerant when below curve Figure 20 Charging Chart for 4 Ton Units 260 280 300 320 340 360 380 400 420 440 460 480 500 90 95 100 105 110 115 120 125 130 Liquid Temperature F...

Page 43: ...43 1 Inch Filter Installations 2 Inch Filter Installations Figure 22 Filter Comversion Internal Filter Conversion...

Page 44: ...t on standard 2 concrete pad NOTE For a trench style drain installation page 3 you will also need 4 x36 min corrugated flexible pipe w drain holes a 2 x4 PVC reducer 4 corrugated piping connection 2 x...

Page 45: ...f the limestone rock chat or lime pellets if required by code with the initial rock base 2 Measure the distance between the top of the rock base and bottom of drain fitting 3 Cut the field supplied 2...

Page 46: ...onnection at bottom of 2 PVC Tee and secure with spring hose clamp 8 Install flexible insulation over the entire length of drain tube and cut away any excess then secure at the top with wire tie provi...

Page 47: ...E VENT AND DRAIN SYSTEM Figure 23 Condensate Disposal Using A Vertical Drainage Pit 30 36 OR GREATER 3 3 2 4 4 PIPE DRAIN BACK FILL ROCK ROCK BASE SEE NOTE GRADE LEVEL 2 PAD GRADE LEVEL NOTE SLOPE 1 1...

Page 48: ...of curb and 1 2 in from the long side of curb See Figure 25 If drilling a hole is not an option routing the condensate drainhoseovertotheductpassageopeningwithenough slope is acceptable as long as dra...

Page 49: ...position of the condensate drain valve be changed from the horizontal H to downflow D position The condensate drain valve is located in the bottom left corner of the heat exchanger collector box to t...

Page 50: ...Degree Elbow 1 4 Mesh Screen 1 2 ID x 84 Drain Hose Flexible Insulation Optional Condensate Drain Valve D Position for Downflow Applications Only To building drain per State and Local Codes J Trap Hei...

Page 51: ...51...

Page 52: ...VOLTS 3 Phase Units Rated Voltage VOLTS L1 L2 Volts VOLTS L1 L3 Volts VOLTS L2 L3 Volts VOLTS Avg Volts VOLTS Max deviation of voltage from avg volts VOLTS Volt Imbalance VOLTS VENTING SYSTEM Is the h...

Reviews: