Nortek P7RE Series Installation Instructions Manual Download Page 8

8

•  The unit requires both power and control circuit electrical 

connections. Refer to the wiring diagrams (

Figure 10 

(page  13)

 & 

Figure 11 (page 14)

) for identification 

and location of unit field wiring interfaces. Make all 

electrical connections in accordance with all applicable 

codes and ordinances.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to applicable local codes. 

See the unit rating plate for minimum circuit ampacity 

and maximum overcurrent protection limits.

•  Use only copper wire for the line voltage power supply 

to this unit as listed in 

Table 1

. Use proper code agency 

listed conduit and a conduit connector for connecting 

the supply wires to the unit. Use of rain tight conduit is 

recommended.

•  208/230 Volt units are shipped from the factory wired 

for 230 volt operation. For 208V operation, remove the 

lead from the transformer terminal marked 240V and 

connect it to the terminal marked 208V.

•  Optional equipment requiring connection to the power 

or control circuits must be wired in strict accordance of 

the NEC (ANSI/NFPA 70), applicable local codes, and 

the instructions provided with the equipment.

grounding

 Warning:

the unit cabinet must have an uninterrupted or 

unbroken electrical ground to minimize personal 

injury if an electrical fault should occur. do not 

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with 

local codes or, in the absence of local codes, with the 

National Electrical Code (ANSI/NFPA 70) or CSA C22.1 

Electrical Code. Ground the air conditioning unit using 

the green grounding screw provided in the control panel.

overcurrent Protection

Generally, the best fuse or breaker for any air conditioner 

is the smallest size that will permit the equipment to run 

under normal usage and provide maximum equipment 

protection. Properly sized fuses and breakers also prevent 

nuisance trips during unit startup. 

if a fuse blows or a 

breaker trips, always determine the reason. do not 

arbitrarily install a larger fuse or breaker and do not, 

in any case, exceed the maximum size listed on the 

data label of the unit.

Thermostat / Low Voltage Connections

•  The unit is designed to operate from a 24 VAC Class 

II control circuit. The control circuit wiring must comply 

with the current provisions of the NEC (ANSI/NFPA 

70) and with applicable local codes having jurisdiction. 

Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and 

the indoor equipment.

•  The  low  voltage  wires  must  be  properly  connected. 

Route 24V control wires through the sealing grommet 
near the power entrance. See 

Figure 7 (page 7)

Recommended wire gauge and wire lengths for typical 

thermostat connections are listed in 

Table 2, (page 

9)

.

•  Single  stage  or  two-stage  heating  thermostats  can 

be used with this equipment depending on optional 

accessories installed with the unit. Select a thermostat 

that operates in conjunction with the installed 

accessories.

•  The thermostat should be mounted about 5 feet above 

the floor on an inside wall. DO NOT install the thermostat 

on an outside wall or any other location where its 

operation may be adversely affected by radiant heat 

from fireplaces, sunlight, lighting fixtures or convective 

heat from warm air registers or electrical appliances. 

Refer to the thermostat manufacturer’s instruction sheet 

for detailed mounting information.

Cooling Only Thermostat

Connect the 

red

 & 

yellow

 wires from the unit to the 

r

 

Y

 terminals on the thermostat subbase. Connect the 

green

 wire to the 

yellow

 wire at the unit. See 

Figure 8

.

Figure 8. 

Low Voltage Connections

RED

R

YELLOW

Y

GREEN

G

BROWN

*

W1

ORANGE

RED

R

YELLOW

Y

GREEN

G

BROWN

*

W

ORANGE

4 WIRE HEAT/COOL THERMOSTAT

Two Stage Heating T-Stat

Single Stage Electric Heat

RED

R

YELLOW

Y

GREEN

2 WIRE COOLING

(ONLY) THERMOSTAT

CONTROL WIRE LEGEND:
GREEN - Blower Relay
RED - Transformer (24V)
YELLOW - Cooling 1st Stage
BROWN - Heating 1st Stage
ORANGE - Heating 2nd Stage

*

W2

*Connected when Optional Electric Heating Kit is Installed.

coPPer Wire SiZe — aWg

(1% VoLTage Drop)

SuPPlY Wire length-Feet

SuPPlY

circuit

aMPacitY

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

table 1. copper Wire Size

Summary of Contents for P7RE Series

Page 1: ...e plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings c...

Page 2: ...tions 8 Cooling Only Thermostat 8 Heat Cool Thermostat 10 Blower Speed ECM Motor 10 START UP ADJUSTMENTS 10 Pre Start Checklist 10 Start Up Procedure 10 System Cooling 10 System Heating 10 Refrigerant...

Page 3: ...he information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equip...

Page 4: ...ly and return ducts If practical place the air conditioner and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest The length of the supply and return...

Page 5: ...ollar so the edge of the unit opening fits between the flange and the bead 2 Overlap the collar ends keeping the small screw holes underneath 3 Align the holes in the crimped area and install one scre...

Page 6: ...n the air box Connecting the Return Supply Air Flexible Ducts Flexible ducts can be connected to the corresponding fittings with the clamps provided with the ducts See Figure 9 Table 4 page 12 NOTE To...

Page 7: ...installer should become familiar with the wiring diagram before making any electrical connections to the unit Anelectricaldisconnectmustbelocatedwithinsight of and readily accessible to the unit This...

Page 8: ...reaker and do not in any case exceed the maximum size listed on the data label of the unit Thermostat Low Voltage Connections The unit is designed to operate from a 24 VAC Class II control circuit The...

Page 9: ...27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1...

Page 10: ...Cool Thermostat For the highest efficiency the use of a 2 stage Heating Cooling thermostat is recommended The heat cool thermostatpreventssimultaneousoperationoftheheating and cooling units and is eq...

Page 11: ...valve 2 Measure the liquid refrigerant temperature F at the service valve 3 For the temperature measured determine the required liquid refrigerant pressure from Table 5 page 15 Table 6 page 15 Table 7...

Page 12: ...12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton Model Nu...

Page 13: ...ment des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1...

Page 14: ...vant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Pack...

Page 15: ...358 150 146 294 137 316 141 338 145 359 150 381 154 148 317 141 338 145 360 149 381 154 404 158 150 317 141 339 145 361 149 382 153 404 158 152 340 145 362 149 383 153 405 157 154 363 149 384 153 406...

Page 16: ...55 146 357 182 378 171 398 162 415 160 148 380 181 401 172 421 164 150 403 181 423 173 152 426 182 154 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp...

Page 17: ...147 378 172 399 172 421 172 443 172 149 403 176 424 177 446 177 151 428 181 449 181 153 453 185 155 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Li...

Page 18: ...40 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when...

Page 19: ...19...

Page 20: ...uid Pressure high side _________________________ Stage 1 Suction Pressure low side _________________________ ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO...

Reviews: