Nortek P7RE Series Installation Instructions Manual Download Page 4

4

general inForMation

This packaged air conditioner is designed only for outdoor 

ground level installations and can be readily connected 

to the high static duct system of a home. This unit has 

been tested for capacity and efficiency in accordance 

with AHRI Standards and will provide many years of safe 

and dependable comfort, providing it is properly installed 

and maintained. Abuse, improper use, and/or improper 

maintenance can shorten the life of the appliance and 

create unsafe hazards.

To achieve optimum performance and minimize equipment 

failure, it is recommended that periodic maintenance be 

performed on this unit. The ability to properly perform 

maintenance on this equipment requires certain 

mechanical skills and tools.

before You install this unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. If there is any question 

concerning the power supply, contact the local power 

company.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 

prior to installing the equipment at the job site. Verify 

coil fins are straight. If necessary, comb fins to remove 

flattened or bent fins. Claims for damage (apparent or 

concealed) should be filed immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 

all instructions before installing the unit.

locating the air conditioner

•  Survey the job site to determine the best location for 

mounting the outdoor unit. Select a solid, level position, 

preferably on a concrete slab, slightly above the grade 

level, and parallel to the home. If possible, select a site 

for the unit that is as close as possible to the proposed 

return grille location. Unit dimensions are shown in 

Figure 9 

Table 4, (page 12)

do not Place unit 

under the hoMe.

•  The  unit  should  be  located  with  consideration  of 

minimizing the length of the supply and return ducts. If 

practical, place the air conditioner and its ducts in an 

area where they will be shaded from the afternoon sun, 

when the heat load is greatest.

•  The length of the supply and return ducts should be 

kept to a minimum with no sharp radius bends.

•  Overhead  obstructions,  poorly  ventilated  areas,  and 

areas subject to accumulation of debris should be 

avoided. The hot condenser air must be discharged up 

and away from the home, and if possible, in a direction 

with the prevailing wind. Do not place the unit in a 
confined space. See 

Figure 9 

Table 4, (page 12)

 

for unit dimensions.

•  Sufficient  clearance  for  unobstructed  airflow  through 

the outdoor coil must be maintained in order to achieve 

rated performance.

•  Consideration  should  also  be  given  to  availability  of 

electric power, service access, noise, and shade.

Minimum clearance requirements

Sufficient clearance for unobstructed airflow through the 
outdoor coil must be maintained in order to provide room 
for proper servicing and achieve rated performance. See 

Figure 1

 for minimum clearances to obstructions.

Service Access Clearances

Blower access panel side ..........................................24”

Electrical compartment access panel side ................12”

Clearance between overhang & top of unit ...............72”

Clearance around condenser coil area to wall or

shrubs (excludes duct panel side) .............................12”

Clearances to Combustible Materials

Supply and return air ducts ..........................................0”

Duct connection side ...................................................0”

12"

12"

24"

TOP OF UNIT

TO

 BE

UNOBSTR

UCTED

0"

Figure 1. Minimum unit clearances

air duct System

Air ducts must be installed in accordance with the standards 

of the National Fire Protection Association “Standard for 

Installation of Air Conditioning and Ventilation Systems” 

(NFPA 90A), “Standard for Installation of Residence Type 

Warm Air Heating and Air Conditioning Systems” (NFPA 

90B), these instructions, and all applicable codes. NFPA 

publications are available by writing to: National Fire 

Protection Association, Batterymarch Park, Quincy, ME 

02269 or visit www.NFPA.org on the web.

•  Design the duct work according to methods described 

by the Air Conditioning Contractors of America (ACCA). 

•  The  supply  duct  system,  including  the  number  and 

type of registers, will have much more effect on the 

performance of the system than any other factor. The 

duct must be sufficiently large to conduct an adequate 
amount of air to each register. See 

Figure 2 (page 5)

.

Summary of Contents for P7RE Series

Page 1: ...e plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings c...

Page 2: ...tions 8 Cooling Only Thermostat 8 Heat Cool Thermostat 10 Blower Speed ECM Motor 10 START UP ADJUSTMENTS 10 Pre Start Checklist 10 Start Up Procedure 10 System Cooling 10 System Heating 10 Refrigerant...

Page 3: ...he information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equip...

Page 4: ...ly and return ducts If practical place the air conditioner and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest The length of the supply and return...

Page 5: ...ollar so the edge of the unit opening fits between the flange and the bead 2 Overlap the collar ends keeping the small screw holes underneath 3 Align the holes in the crimped area and install one scre...

Page 6: ...n the air box Connecting the Return Supply Air Flexible Ducts Flexible ducts can be connected to the corresponding fittings with the clamps provided with the ducts See Figure 9 Table 4 page 12 NOTE To...

Page 7: ...installer should become familiar with the wiring diagram before making any electrical connections to the unit Anelectricaldisconnectmustbelocatedwithinsight of and readily accessible to the unit This...

Page 8: ...reaker and do not in any case exceed the maximum size listed on the data label of the unit Thermostat Low Voltage Connections The unit is designed to operate from a 24 VAC Class II control circuit The...

Page 9: ...27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1...

Page 10: ...Cool Thermostat For the highest efficiency the use of a 2 stage Heating Cooling thermostat is recommended The heat cool thermostatpreventssimultaneousoperationoftheheating and cooling units and is eq...

Page 11: ...valve 2 Measure the liquid refrigerant temperature F at the service valve 3 For the temperature measured determine the required liquid refrigerant pressure from Table 5 page 15 Table 6 page 15 Table 7...

Page 12: ...12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton Model Nu...

Page 13: ...ment des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1...

Page 14: ...vant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Pack...

Page 15: ...358 150 146 294 137 316 141 338 145 359 150 381 154 148 317 141 338 145 360 149 381 154 404 158 150 317 141 339 145 361 149 382 153 404 158 152 340 145 362 149 383 153 405 157 154 363 149 384 153 406...

Page 16: ...55 146 357 182 378 171 398 162 415 160 148 380 181 401 172 421 164 150 403 181 423 173 152 426 182 154 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp...

Page 17: ...147 378 172 399 172 421 172 443 172 149 403 176 424 177 446 177 151 428 181 449 181 153 453 185 155 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Li...

Page 18: ...40 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when...

Page 19: ...19...

Page 20: ...uid Pressure high side _________________________ Stage 1 Suction Pressure low side _________________________ ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO...

Reviews: