3. Install the appropriate LP/Propane gas burner orifices into 

the gas manifold assembly.

NOTE:

 To prevent cross threading, hand tighten the orifices into 

the gas manifold assembly until snug, then tighten with a wrench.

 WARNING:

Do  not  use  Teflon  tape  or  pipe  joint  compound 

on the orifice threads. The hole in the orifice may 

become blocked and cause fire, explosion, property 

damage,  carbon  monoxide  poisoning,  personal 

injury, or death.

4. Reinstall the gas manifold assembly to the burner assembly 

with the 4 screws, that were removed earlier. 

NOTE:

 It is 

important that the center of the orifices are aligned with the 

center of the burners.

5. Reconnect the gas piping to the gas valve inlet.

6. Reconnect the wires to the gas valve terminals.

GAS PRESSURE ADjUSTMENT

Measuring the Supply Gas Pressure

1. Turn OFF the gas supply at the manual valve located on the 

outside of the unit.

2. Using a 3/16“ Allen wrench, remove the plug from the inlet 

pressure tap (INLET side of gas valve). See Figure 3.

3. Install an 1/8” NPT pipe thread fitting, which is  compatible 

with a Manometer or similar pressure gauge.

4.  Connect the Manometer or pressure gauge to the Inlet Pressure 

Tap.

5. Turn ON the main gas supply at the manual valve.

6.  Check and adjust the incoming gas line pressure to 11.0-14.0 

inches Water Column for LP/Propane gas.

7. Turn OFF the gas supply at the manual valve.

8. Disconnect the Manometer or pressure gauge.

9. Remove the NPT fitting and reinstall the INLET pressure tap 

plug. Hand tighten the plug first to prevent cross-threading. 

Tighten with 3/16” Allen wrench.

High Fire

Cap Screw

High Fire 

Adjustment Screw

Low Fire

Cap Screw

Low Fire 

Adjustment Screw
Spring

Spring

Figure 2. Gas Valve Conversion

Figure 3. Inlet & Manifold Pressure Tap Locations

Inlet

Pressure

Tap

Manifold

pressure

Tap

Model VR9205Q1127

ON/OFF

Switch

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could 

result in serious injury or property damage.

Never test for gas leaks with an open flame. 

Use a commercially available soap solution 

made  specifically  for  the  detection  of  leaks 

to check all connections. A fire or explosion 

may result causing property damage, personal 

injury or loss of life.

 WARNING:

RISQUE D’INDENDIE OU D’EXPLOSION

Le non-respect des avertissements de sécurité 

pourrait d’entraîner des blessures graves, la mort 
ou des dommages matériels.

Ne jamais utiliser une flamme nue por 

vérifier  la  présence  des  fuites  de  gaz.  Pour  la 

vérification de tous les joints, utiliser plutôt une 

solution  savonneuse  commerciale  fabriquée 

spécifiquement pur la détection des fuites de gaz. 

Un incendie ou une explosion peut entraîner des 

dommages matériels, des blessures ou la mort.

 

AVERTISSEMENT

:

HIGH ALTITUDE CONVERSION

(FOR NATURAL GAS INSTALLATIONS AT 

ALTITUDES BETWEEN 2,000 & 4,500 FT)

When converting to high altitude with natural gas, conversion 

requires replacement of the burner orifices and/or adjustment 

of the manifold pressure. For detailed instructions, refer to the 

“High Altitude Application” section of the Installation Instructions 

supplied with the furnace.