Nortek FS4BF Installation Instructions Manual Download Page 6

6

Start Up & adJUStmentS

pre-Start check list

 Verify the indoor unit is level and allows proper 

condensate drainage.

  Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/

control panels are in place.

  Verify air filters are cleaned and properly installed.

  Verify duct work is sealed to prevent air leakage. 

  Verify line voltage power leads are securely connected 

and the unit is properly grounded.

   Verify low voltage wires are securely connected to the 

correct leads on the low voltage terminal strip.

  Verify power supply branch circuit overcurrent protection 

is sized properly.

  Verify the thermostat is wired correctly.

Start-Up procedures

The thermostat's function mode should be set to OFF and 

the fan mode should be set to AUTO. Close all electrical 

disconnects to energize the sy stem.

Air Circulation - Indoor Blower

1. Set the thermostat system mode on OFF and the fan 

mode to ON.

2. Verify the blower runs continuously. Check the air 

delivery at the supply registers and adjust register 

openings for balanced air distribution. If insufficient air 

is detected, examine ductwork for leaks or obstructions.

3. Set the thermostat fan mode to AUTO and verify the 

blower stops running.

System Cooling

1. Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostat 

temperature setpoint below room temperature and 

verify the outdoor unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by 

arrow. Feel the air being circulated by the indoor blower 

and verify that it is cooler than ambient temperature. 

Listen for any unusual noises. If unusual sounds 

occur, determine the source of the noise and correct 

as necessary.

3. Verify HI and LO refrigerant pressures.

4. Allow the system to operate for several minutes 

and then set the temperature selector above room 

temperature. Verify the fan and compressor cycle off 

with the thermostat. 

note:

 The blower should also 

stop unless fan mode is set to the ON position.

System Heating (optional)

1. Set the thermostat's system mode to HEAT and the 

temperature mode above room temperature.

2. Verify the optional heating equipment (furnace or 

electric heat) and indoor blower energize. Feel the air 

being circulated by the indoor blower and verify that 

it is warmer than ambient temperature. Listen for any 

unusual noises. If unusual sounds occur, determine 

the source of the noise and correct as necessary.

NOTE: FOR THE MATCH 
*S4BF-024KA + C6B(A,H)-X30(C,U)-C + *G7T-C
*S4BF-024KA + C6B(A,H)-X30(C,U)-C + *G7S-C+*SHE

 Only connect Y2 from thermostat to OD Y2

Furnace

Air Conditioner 

OD Section

(Without CoreSense)

W2 

W1 

Y/Y2 

Thermostat

O Y2 Y G RC RH C W2 W/E

Y1

Y/Y2 

Y1

Figure 3. typical 2-Stage air conditioner 

(without coreSense) with gas Furnace

thermostat connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and 

the indoor equipment. Typical AC and thermostat 

hookups are shown in 

Figure 3

.

•  The outdoor unit is designed to operate from a 24 VAC 

Class II control circuit. The control circuit wiring must 

comply with the current provisions of the NEC (ANSI/

NFPA 70) and with applicable local codes having 
jurisdiction.

•  The low voltage wires must be properly connected to 

the units low voltage terminal block. Recommended 

wire gauge and wire lengths for typical thermostat 

connections are listed in 

Table 2

.

•  The  thermostat  should  be  mounted  about  5  feet 

above the floor on an inside wall. DO NOT install the 

thermostat on an outside wall or any other location 

where its operation may be adversely affected by radiant 

heat from fireplaces, sunlight, or lighting fixtures, and 

convective heat from warm air registers or electrical 

appliances. Refer to the thermostat manufacturer’s 

instruction sheet for detailed mounting and installation 

information.

table 2. thermostat Wire gauge

thermoStat

Wire gaUge

maXimUm recommended

 thermoStat Wire length (Ft)

24

25

22

45

20

70

18

110

Summary of Contents for FS4BF

Page 1: ...NCE Installation Instructions important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General Information 3 Before You Install this Unit 3 Locating the Air Conditioner 3 Packaging Removal 3 Grou...

Page 2: ...autions in the literature on tags and on labels provided with the equipment Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operati...

Page 3: ...g the unit Locating the Air Conditioner Survey the job site to determine the best location for mounting the outdoor unit The outdoor unit should be installed no closer than 18 inches from the outside...

Page 4: ...the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes Pre Ele...

Page 5: ...c key is also imprinted on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 17 Compressor Protection Th...

Page 6: ...re Verify the fan and compressor cycle off with the thermostat NOTE The blower should also stop unless fan mode is set to the ON position System Heating optional 1 Set the thermostat s system mode to...

Page 7: ...tionsfromratedairflowsor non listedcombinationsmayrequiremodificationtothe expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charge can be...

Page 8: ...ary over the range of operation Reference the charts to determine the ideal amount of sub coolingforagivenliquidpressure Unitschargedto other values will not perform at the rated unit efficiency EER o...

Page 9: ...110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F S4BF 036KB Charging Chart Cooling Figure 6 Charging Chart for 4 Ton Models Add refrigerant when below curve Remove refrigerant when a...

Page 10: ...when below curve Remove refrigerant when above curve 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure...

Page 11: ...onductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circu...

Page 12: ...R C S S C R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Cr...

Page 13: ...le Phase 60 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR...

Page 14: ...tection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avan...

Page 15: ...R C S L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR CSC C Y2 Y LPS HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdo...

Page 16: ...class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducte...

Page 17: ...system 6 Thermostat is malfunctioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrige...

Page 18: ...ssor bearings are seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blo...

Page 19: ...19...

Page 20: ...____________________________ Unit Installed Minimum clearances per Figure 1 page 3 YES NO INSTALLER NAME CITY________________________ STATE_________________ REFRIGERATION SYSTEM Was unit given 24 hr w...

Reviews: