MAINTENANCE & SERVICE

 WARNING:

ELECTRICAL SHOCK, FIRE OR EXPLOSION 
HAZARD

Failure to follow safety warnings exactly could 

result in serious injury or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.
• Before servicing, disconnect all electrical 

power to the furnace and outdoor condensing 

unit.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

 CAUTION:

Do not operate the system without a suitable 
filter in the return air duct system. Always 
replace the filter with the same size and type.

To ensure optimum performance and to minimize possible 

equipment failure, the following maintenance tasks should 

be performed periodically on this equipment:
1. The air filter installed with the system should be checked 

and cleaned or replaced twice per year.

2. Check the coil, drain pan, and condensate drain line 

for cleanliness at the start of each heating and cooling 
season. Clean as needed.

Condensate Drain

 CAUTION:

The coil must be level to ensure proper 
condensate drainage. Improper condensate 
disposal may result in structural damage, 
premature equipment failure, or possible 
personal injury.

•  Methods for disposing of condensate vary according 

to local codes. Refer to local codes or authority having 
jurisidiction for restrictions and proper condensate 
disposal requirements.

•  All condensate pans have primary and secondary drain 

connections to meet FHA requirements. If the application 
is located in or above a living space where damage 
may result from condensate overflow, a separate 3/4 
inch drain must be provided from the secondary drain 
connection and a secondary drain pan must be installed 
under the entire unit. Run secondary drain lines to a 
place where they are noticeable if used.

• The coil condensate pan is designed with 3/4” 

NPSC drain connections. Use a PVC or similar 
material fitting to attach the drain line to the pan.  

NOTE:

 The fitting should be hand tightened only. 

Overtightening may crack the drain pan and cause 
condensate to leak.

•  The drain pan MUST be drained with field supplied 

tubing and looped to form a trap.

 IMPORTANT:

 Failure to install a trap may result in 

condensation overflowing the drain pan, resulting in 
substantial water damage to surrounding area.

•  Prime the trap with water. Insulate the drain if it is located 

in an unconditioned space, and test the condensate line 
for leaks. Consult local codes for additional restrictions 
or precautions.

•  Route the lines to a suitable drain, avoiding sharp bends 

and pinching of the lines. The drain should maintain a 
minimum horizontal slope in the direction of discharge 
of not less than 1” vertical for every 10 ft of horizontal 
run.

• During system checkout, inspect the drain line and 

connections to verify proper condensate drainage.

Air Filter

Air filters are not supplied as an integral part of this 

coil; however, an air filter kit is available. Refer to the 

Replacement Parts List for available part numbers.
The filter must be installed upstream of the coil and 
inspected frequently. When the filter becomes clogged 
with dust or lint, it should be replaced (disposable type) 
or cleaned (washable type). It is recommended that filters 
be inspected and replaced at least twice during the year. 
Generally it is best to replace or clean the filters at the 
start of each heating and cooling season.

Summary of Contents for C84QA Series

Page 1: ...well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury...

Page 2: ...s conditions which may result in personal injury or property damage Unless otherwise noted in these instructions only factory authorized kits or accessories may be used with this product WARNING PROPO...

Page 3: ...oor coil COIL INSTALLATION WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Improper servicing could result...

Page 4: ...installation instructions for assembly details 3 Remove the interior coil panel Install the coil and level it as needed to ensure proper condensate drainage 4 Remove the knockout for the refrigerant...

Page 5: ...overflow a separate 3 4 inch drain must be provided from the secondary drain connectionandasecondarydrainpanmustbeinstalled under the entire unit Run secondary drain lines to a place where they are n...

Page 6: ...in 18 1 8 18 1 8 18 1 8 18 1 8 18 1 8 18 1 8 18 1 8 H Height in 18 18 18 18 25 25 29 D Depth in 19 1 2 19 1 2 19 1 2 19 1 2 19 1 2 19 1 2 19 1 2 Connection Liquid Line in 3 8 3 8 3 8 3 8 3 8 3 8 3 8...

Page 7: ...7...

Page 8: ...AVE THESE INSTRUCTIONS WITH THE EQUIPMENT OWNER 10441310 Replaces 1040997A Specifications illustrationssubjecttochangewithoutnoticeorincurringobligations 10 22 O Fallon MO Nortek Global HVAC LLC 2022...

Reviews: