background image

12

DISPLAY

CODE

CURRENT MODE

-

Standby is a Rotating Segment
Cooling Mode (Y input active)
Heating Mode (W input active)
Circulate Fan Mode (G input active)
Dehum Cooling Mode (DEHUM input active along with Y)
(one) A Motor Fault has Occurred (BMF active for more than 

30 seconds)
(lower case t) Over Temperatures (The value of the TS input 

has exceeded 80C all outputs are stopped.)
Lockout (Ten (10) or more Motor Faults or Over Temperature 

events have occurred. All outputs are set to off for one hour.

Basic Cooling / Heat Pump Airflow for Variable & Fixed 
Speed

The basic cooling/heat-pump airflow is controlled by setting 

switches 5 - 8 on the motor control board (mounted on the 

blower). All airflows for other modes of operation (except 

electric heat) are determined by this basic setting. FAN ONLY 

would deliver 50% of the selected cooling airflow. 

Table 8, 

(page 18)

 lists the CFM airflow values recommended for 

each nominal system capacity. To determine dip switch 

settings, refer to 

Table 6, (page 16)

 for FSHE applications and 

Table 9, (pages 19 and 20)

 for VSHE applications.

•  When operating in the heat pump mode, a higher basic 

airflow setting will increase the energy efficiency and 

capacity but will also decrease the supply air temperature.

• For maximum capacity and energy efficiency, select an 

airflow at or near the top of the range for that nominal 

capacity. See 

Table 8, (page 18)

.

•  For maximum dehumidification, select an airflow near the 

middle or bottom of the range for that nominal capacity. 

Additional information on humidity control can be found 

in the Dehumidication Options section on 

page 10

.

• For thermostats with a dehumidifier output, use a field 

supplied wire to connect the thermostat’s dehumidifier 

output to the terminal marked 

DHUM

. The thermostat 

should be set so that the 

DHUM

 output should be high 

(energized) when dehumidification is needed. See also 

Dehumidification Options section.

IMPORTANT!

 If coil icing is observed, the basic cooling/

heat-pump airflow selected may be too low. Verify the setting 

selected is within the range shown in 

Table 8 (page 18)

 and 

that the the system is properly charged. Please refer to the 

instructions supplied with the outdoor unit. If icing continues 

to occur, raise the selected airflow one or two steps.

NOTE:

 Variable speed air handlers with SEER ratings higher 

than 15 are matched with a 2-stage cooling outdoor unit. 

They are programmed to operate at 75% of the selected 

airflow while the system is in the lo-cool mode and 100% 

of the selected airflow while in hi-cool mode.
Units with an FSHE control scheme (B64EM) have a control 

board that includes a 7 segment display to help the installer 

identify what mode the air handler is running in as well 

as troubleshooting if the unit is not functioning properly. 

Table 2, 

 contains a list of the codes that may appear on the 

7 segment display. The display code will only show what 

mode the air handler is currently in. There is not a history 

of fault codes that have occurred in previous operation.

TROUBLESHOOTING

If the air handler fails to operate, check the following:

•  Is the electric turned on?

•  Is the thermostat operating properly?

•  Are the blower compartment door(s) in place?

•  Is the air handler disconnect closed?

•  Has the circuit breaker tripped or the control board fuse 

burned open?

•  Are any manual reset switches open?

•  Is the filter dirty or plugged?

•  Is the LED on both control boards constantly ON? If not, 

refer to 

Table 3

 or 

Table 4

 to determine fault condition.

UNIT MAINTENANCE

Proper maintenance is most important to achieve the best 

performance from a air handler. Some of the components 

and their locations are shown in 

Figure 9 (page 15)

If 

any component of the air handler must be replaced, use 

only factory authorized replacement parts specified in the 

Replacement Parts List provided online.

 WARNING:

ELECTRICAL SHOCK, FIRE OR

EXPLOSION HAZARD

Failure to follow safety warnings exactly could 

result in serious injury or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.
•  Before servicing, disconnect all electrical power 

to the indoor blower.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

• These maintenance instructions are primarily intended 

to assist qualified technicians experienced in the proper 

maintenance and operation of this appliance.

•  Always reinstall the doors on the air handler after servicing 

or cleaning/changing the filters. 

Do not operate the air 

handler without all doors and covers in place.

Table 2. FSHE Motor Control Board Display Codes

RED LED (AN2)

DIAGNOSTIC

OFF

Control Fault (No Power)

Flash

Blower Fault

ON

Normal Operation

Table 3. Air Handler Control Board Fault Conditions

DIAGNOSTIC FAULT CONDITIONS

FOR VARIABLE SPEED FURNACES

GREEN

LED

RED

LED

Control Fault (No Power)

Off

Off

Normal Operation

On

On

Motor Fault

On

Flash

Communications Fault

Flash

Flash

Table 4. VSHE Motor Control Board Display Codes

Summary of Contents for B64EM Series

Page 1: ...well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury...

Page 2: ...wer Continuously 11 Selecting Continuous Low Speed Fan Operation 11 Turning the Blower Off 11 System Cooling 11 System Heating 11 Selecting Minimum Electric Heat Airflow 11 Blower Configurations 11 De...

Page 3: ...ation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in p...

Page 4: ...ment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationoftheto...

Page 5: ...needed gaskets and grommets around penetrations into the air handler such as for electrical wiring AIR HANDLER INSTALLATION B64 series air handlers are shipped ready for vertical upflow installation a...

Page 6: ...Right Installations 1 Remove the coil access door Unscrew the line set tube close off plate from the front left cabinet rail 2 Slide the coil and drain pan assembly out of the unit 3 Remove the sheet...

Page 7: ...ntact with valve when gas is escaping Always ensure adequate ventilation is present during the depressurization process Address any uncertainties before proceeding Failure to comply with this warning...

Page 8: ...ondensables to prevent low efficiency operation or damage to the unit The suggested range of evacuation is 350 500 microns 9 Charge the system with refrigerant Refer to the outdoor unitinstallationman...

Page 9: ...ation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in p...

Page 10: ...5 Connect blue blower limit wires according to Heater Kit Installation Instructions and the corresponding Wiring Diagram If a heater kit is not installed 1 Remove the 2 wire plug of the air handler b...

Page 11: ...n B64EM models B64VM models automatically set the heating speed based on the amount of installed heat The A B switch must be set appropriately for the unit cabinet size For C sized cabinets the A B sw...

Page 12: ...cted airflow while the system is in the lo cool mode and 100 of the selected airflow while in hi cool mode Units with an FSHE control scheme B64EM have a control board that includes a 7 segment displa...

Page 13: ...or on the blower and motor as part of the annual inspection Blower Fan Wheel Inspect the blower wheel blades for accumulations of dirt and clean if necessary Inspect mounting nut for tightness when do...

Page 14: ...typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A CABINET SIZE H W A DETAIL D A 43 5 16 14 3 16 12 3 4 No B 43 5 16 19 11 16 18 1 4 No Tall...

Page 15: ...l Drain Pan Coil Assembly Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Uppe...

Page 16: ...0 795 720 685 0 1 1 0 1095 1040 995 950 900 850 805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0...

Page 17: ...TON 560 560 1200 3 5 TON 600 600 1250 625 650 2 TON 1300 4 TON 700 2 TON 700 1350 750 750 1400 800 2 5 TON 800 2 5 TON 1450 850 850 1500 875 875 1550 890 950 1600 5 TON 930 1050 3 TON 1650 950 1150 3...

Page 18: ...ING 0 OFF 1 ON AIRFLOW CFM 5 6 7 8 0 0 0 0 1100 0 0 0 1 1200 0 0 1 0 1250 0 0 1 1 1300 0 1 0 0 1350 0 1 0 1 1400 0 1 1 0 1450 0 1 1 1 1500 1 0 0 0 1550 1 0 0 1 1600 1 0 1 0 1650 1 0 1 1 1700 1 1 0 0 1...

Page 19: ...W1 W2 EHEAT ON 5 KW Stage 1 Heat on instantly Heat blower on after 3 second delay 8 KW 10 KW Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 2 Heat on after 5 seconds delay 15 KW...

Page 20: ...fter 5 seconds delay 15 KW Stage 1 Heat on instantly Cool blower on after 3 second delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 30 seconds delay 20 KW Stage 1 Heat on instantly Co...

Page 21: ...cal Heat Pump with 2 Stage Air Handler G R W2 C O Y1 Thermostat O Y1 R C G R W E Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with 2 Stage Air Handler Typical 2 Stage Heat Pump with 2 Stage A...

Page 22: ...1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 12 Single Stage Control Board C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 13 Two Stage Contro...

Page 23: ...R ECM BLOWER Figure 14 Fixed Speed Motor Control Board GND SENSOR DEHUM Y1 H L2 OUT L2 IN L1 IN L1 OUT Y1 Y Y2 W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTP...

Page 24: ...entation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac ut...

Page 25: ...e tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cuivre 105 C du m me gabarit WIRING DIAGRAM CONNECT TO W1...

Page 26: ...tterthanyourcustomer This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the...

Page 27: ...27...

Page 28: ...10436960 NEW Specifications illustrations subject to change without notice or incurring obligations 08 22 O Fallon MO Nortek Global HVAC LLC 2022 All Rights Reserved...

Reviews: