Figure 26: Drain Valve Actuator Assembly
Installing the New Cylinder
1
Insert cylinder into drain valve. Tilt cylinder forward and fit end of steam hose to steam
outlet. Tip cylinder back into place.
2
Secure cylinder with the reusable cable tie. Tighten hose clamp being careful not to over
tighten and crush the plastic cylinder steam outlet.
3
Attach color-coded cylinder plugs to the corresponding color-coded cylinder pin. Push down
completely. Connect high water sensor plug. Spring-loaded plugs should fit snuggly onto
the cylinder pin. Replace if they are loose or damaged.
4
If enclosed plumbing option is installed replace the humidifier cover and secure with screw.
5
Turn on power to humidifier with the external disconnect.
6
Open supply water shut off valve.
7
Turn the humidifier On/Off /Drain switch to On.
Sleeve
and
Solenoid
Spring
Plunger
(Note Orientation)
CAUTION:
Make sure the new cylinder is the same model as the one that was
removed. Model number is on top left corner of cylinder label.