Noritz proTough NR98SV Installation Manual Download Page 16

16

10.

 Water Piping

This appliance is suitable for potable water and space heating applications. Do not use this appliance if any part has
been underwater.  Immediately call a qualified service technician to inspect the appliance and replace any part of the
control system and gas control which has been under water.

If the water heater is installed in a closed water supply system, such as one having a backflow preventer in the cold
water supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local plumb-
ing inspector on how to control this situation.

A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying with
either The Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, or
The ANSI/ASME Boiler and Pressure Vessel Code, Section IV ( Heating Boilers ). This pressure relief valve must
be capable of an hourly Btu rated temperature steam discharge of 199,900 Btuh. Multiple valves may be used. The
pressure relief capacity must not exceed 150 psig. No valve shall be placed between the relief valve and the water
heater. The relief valve must be installed such that the discharge will be conducted to a suitable place for disposal
when relief occurs. No reducing coupling or other restriction may be installed in the discharge line. The discharge line
must be installed to allow complete drainage of both the valve and the line. If this unit is installed with a separate
storage vessel, the separate vessel must have its own temperature and pressure relief valve. This valve must also
comply with The Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI
Z21.22. (in the U.S. only). A temperature relief valve is not required, but if one is used, do not install the valve with the
probe directly in the flow of water. This may cause unwarranted discharge of the valve.

Piping and components connected to the water heater shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.
A water heater used to supply potable water may not be connected to any heating system or components previously
used with a nonpotable water heating appliance.
When water is required in one part of the system at a higher temperature than in the rest of the system, means such
as a mixing valve shall be installed to temper the water to reduce the scald hazard.

Installation and service must be performed by a qualified plumber.  In the
Commonwealth of Massachusetts, this product must be installed by a licensed
plumber or gas fitter in accordance with the Massachusetts Plumbing and Fuel
Gas Code 248 CMR Sections 2.00 and 5.00. Observe all applicable codes.

• Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.
• Perform the following insulation measures for prevention of freezing.

• Take appropriate heat insulation measures (e.g., wrapping with heat

insulation materials, using electric heaters) according to the climate of
the region to prevent the pipe from freezing.

• Make sure that there are no water leaks from the cold and hot water

supply pipes, then insulate the pipes completely.

• Be sure to also completely insulate the water supply valve and the

cold and hot water connections on the water heater (refer to the figure
on the right).

• Do not cover the water drain plug with insulation so that water in the

pipe can be drained. (Refer to the figure in the right.)

• Use a union coupling or flexible pipe for connecting the pipes to reduce the force applied to the piping.
• Do not use piping with a diameter smaller than the coupling.
• When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measure.
• Avoid using joints as much as possible to keep the piping simple.
• Avoid piping in which an air holdup can occur.
• If installing the unit on a roof:
• About lower-level hot water supply

If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied to
the unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water pressure
is maintained at this level.
Check the pressure before putting the unit into operation.
Failure to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, and may
cause the unit to shut down frequently.

Completely insulate  
the water inlet and  
outlet fittings. 

Insulate the water  
supply valve completely.

Do not cover the water  
drain plug with insulation   
so that water in the pipe  
can be drained.

Summary of Contents for proTough NR98SV

Page 1: ...the customer along with the Owner s Guide WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or death NORITZ AMERI...

Page 2: ...troller Cord 10ft 1 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation Outdoor Vent Cap VC4 1 1 Quick Connect Cord Q ty Shape Par...

Page 3: ...tween the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent he...

Page 4: ...rwise impure treat the water with approved methods in order to ensure full warranty coverage WARNING CAUTION Check the Gas Check that the rating plate indicates the correct type of gas Check that the...

Page 5: ...e Dust may block the air supply opening causing the performance of the device fan to drop and incomplete combustion to occur as a result Avoid installation in places where special chemical agents e g...

Page 6: ...ove the roof line in an outdoor instal lation use high temperature sealant around the flue collar for rain protection Avoid installation where the unit will be exposed to excessive winds Before instal...

Page 7: ...8 or more on either side of the unit to facilitate inspection If possible leave 24 or more in front of the unit to facilitate maintenance and service if necessary If possible leave 3 or more above an...

Page 8: ...lk or paved driveway located on public property Under veranda porch deck or balcony 7 M indicates clearances required in Canada Maintain clearances in accordance with local installation codes and the...

Page 9: ...t into any building 3 above any forced air inlet within 10 Vent Clearances When Heater is In stalled Outdoors With a Vent Cap All clearance requirements are in accordance with ANSI Z21 10 3 and the Na...

Page 10: ...be done to prevent the transfer of vibration Do not drop or apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a ve...

Page 11: ...r will be required to properly connect the vent to this appliance Consult the manufacturer s instructions for the proper appli ance adapter Vent Piping Noritz N Vent is suggested for the vent system I...

Page 12: ...section is recommended to prevent debris from falling into the water heater Install a condensation drain in the horizontal section of the venting For installations in tight spaces where there is not e...

Page 13: ...is installed in a mechanical closet provide a 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per m...

Page 14: ...the gas line consult local codes or the National Fuel Gas Code ANSI Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz NR98 SV 199 900 Btuh Clothes Dryer 35 000 Btuh Barbecue 5...

Page 15: ...Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 10 20 30 40 50 60 70 80 90 100 150 200 206 383 614 1261 2934 147 269 418 888 2078 1...

Page 16: ...stem or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mix...

Page 17: ...wet the floor If neces sary provide drain piping or use a drain hose to remove the water Hot water piping Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or ot...

Page 18: ...SV Cold to Water Heater Optional Sediment Filter Water Treatment Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush...

Page 19: ...ump 4 Set the flow switch to deactivate the Air Handler when the domestic hot water flow reaches 3 GPM Adjust as necessary to prevent cycling 5 If the system requires water for space heating at a high...

Page 20: ...eater may cause electrical interference and faulty operation Disconnect Power Electrical Shock Hazard Do not turn power on until electrical wiring is finished Disconnect power before servicing Failure...

Page 21: ...or as shown on the right 5 Replace the front cover of the water heater 4 screws 6 Reconnect electrical power to the water heater but do not turn it on 7 Press and hold the FLOW METER ALARM SET button...

Page 22: ...and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of sl...

Page 23: ...hich 120VAC will be supplied directly from a wall circuit to the pump 5 Replace the front cover Supplies Power for Circulating Pump Use a Relay for Larger Pumps Pump Wiring This feature is not availab...

Page 24: ...lack 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3...

Page 25: ...r a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do...

Page 26: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Page 27: ...1 4 8 2 8 4 5 5 9 7 8 3 1 1 4 7 0 GAS INLET 3 4 4 0 5 2 0 3 x 0 6 OBLONG HOLE HEIGHT OF EACH FITTINGS FROM BOTTOM OF CASE HOT WATER OUTLET COLD WATER INLET GAS INLET WIRING THROUGHWAY WATER DRAIN VAL...

Page 28: ...otes on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locat...

Page 29: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Page 30: ...he wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wa...

Reviews: