3
3.
Quick Connect Multi System Installation
• The Quick Connect Multi System allows the installation of two units together utilizing only the Quick
Connect Cord.
Typical Plumbing
The Quick Connect Cord is 2m (6'). long. Install the units 50 - 450mm (2-18") apart from each
other to ensure the cord will be able to reach between the units. (See Typical Plumbing diagram).
(If the distance between the two units is too great, not only will the cord not be able to reach,
but the water temperature may also become unstable because of the difference in pipe length
between the two units).
* When connecting two units, disconnect
the remote controller connector from the
other unit.
Note: Connect the remote
controller to only one
of the units.
System Diagram
• Insulate the hot water piping to prevent heat loss. Insulate and apply heating materials to the cold
water supply piping to prevent heat loss and freezing of pipes when exposed to excessively cold
temperatures.
Distance at center:
406 - 812mm (16-32").
Distance on sides
50 - 450mm
(2-18").
Leave enough clearance around the plumbing
to apply insulation. It will be necessary to add
bends to the piping to ensure that this
clearance is available.
Size the piping to allow for the maximum
flow rates of the units.
Union
Hot Water
Shutoff
Valve
Cold Water
Make this distance as short as possible.
* The hot water temperature will
become unstable as the pipe
length increases.
Union
Quick Connect
Cord
Pressure
Relief
Valve
Shutoff
Valve
Union
Gas Valve
Shutoff Valve
G
Quick Connect
Cord
Gas Supply Piping
Cold Water Supply
Hot Water
Remote Controller
*1
Cord
Connector
Cord
Connector