Noritz NR50-OD Installation Manual Download Page 17

17

9.

 Water Piping

This appliance is suitable for potable water and space heating applications. Do not use this appliance if any part 

has been underwater.  Immediately call a qualified service technician to inspect the appliance and replace any part 

of the control system and gas control which has been under water.

If the water heater is installed in a closed water supply system, such as one having a backflow preventer in the 

cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local 

plumbing inspector on how to control this situation.
A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying with 

either The Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, or 

The ANSI/ASME Boiler and Pressure Vessel Code, Section IV  ( Heating Boilers ). This pressure relief valve must be 

capable of an hourly Btu rated temperature steam discharge of 180,000 Btuh (140,000 Btuh for NR66 series, 120,000 

Btuh for NR50 series.) Multiple valves may be used. The pressure relief capacity must not exceed 150 psi. No valve 

shall be placed between the relief valve and the water heater. The relief valve must be installed such that the dis-

charge will be conducted to a suitable place for disposal when relief occurs. No reducing coupling or other restriction 

may be installed in the discharge line. The discharge line must be installed to allow complete drainage of both the 

valve and the line. If this unit is installed with a separate storage vessel, the separate vessel must have its own tem-

perature and pressure relief valve. This valve must also comply with The Standard for Relief Valves and Automatic 

Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22. (in the U.S. only). A temperature relief valve is not 

required, but if one is used, do not install the valve with the probe directly in the flow of water. This may cause unwar

-

ranted discharge of the valve.
Piping and components connected to the water heater shall be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.

A water heater used to supply potable water may not be connected to any heating system or components previ-

ously used with a nonpotable water heating appliance.

When water is required in one part of the system at a higher temperature than in the rest of the system, means 

such as a mixing valve shall be installed to temper the water to reduce the scald hazard.
•  Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.

•  Perform the following insulation measures for prevention of freezing. 

•  Take appropriate heat insulation measures (e.g., wrapping with heat 

insulation materials, using electric heaters) according to the climate 

of the region to prevent the pipe from freezing.

•  Make sure that there are no water leaks from the cold and hot water 

supply pipes, then insulate the pipes completely.  

•  Be sure to also completely insulate the water supply valve and the 

cold and hot water connections on the water heater (refer to the fig

-

ure on the right).  

•  Do not cover the water drain plug with insulation so that water in the 

pipe can be drained. (Refer to the figure in the right.)  

• 

Use a union coupling or flexible pipe for connecting the pipes to reduce the force applied to the piping.

•  Do not use piping with a diameter smaller than the coupling.

•  When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measure.

•  Avoid using joints as much as possible to keep the piping simple.

•  Avoid piping in which an air holdup can occur.

•  If installing the unit on a roof:

•  About lower-level hot water supply

  If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied 

to the unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water 

pressure is maintained at this level.

  Check the pressure before putting the unit into operation.

  Failure to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, and 

may cause the unit to shut down frequently.

Installation and service must be performed by a qualified plumber.  In the 

Commonwealth of Massachusetts, this product must be installed by a licensed 

plumber or gas fitter in accordance with the Massachusetts Plumbing and Fuel 

Gas Code 248 CMR Sections 2.00 and 5.00. Observe all applicable codes.

Completely insulate 

the water inlet and 

outlet fittings.

Insulate the water 

supply valve completely.

Do not cover the water 

drain plug with insulation

so that water in the pipe 

can be drained.

Summary of Contents for NR50-OD

Page 1: ...ge personal injury or death NORITZ AMERICA CORPORATION Installation Manual TANKLESS GAS WATER HEATER DANGER indicates an imminently hazardous situation which if not avoided will result in death or ser...

Page 2: ...t Part Shape Q ty 1 1 Remote Controller Cord 26ft 1 Isolation Valves includes pressure relief valve Pipe Cover PC 1S 1 1 Cross Recess Head Screw OD type only Owner s Guide Warranty Installation Manual...

Page 3: ...he water with approved methods in order to ensure full warranty coverage WARNING CAUTION Check the Gas Check that the rating plate indicates the correct type of gas Check that the gas supply line is s...

Page 4: ...upply opening causing the performance of the device fan to drop and incomplete combustion to occur as a result Avoid installation in places where special chemical agents e g hair spray or spray deterg...

Page 5: ...outdoor instal lation use high temperature sealant around the flue collar for rain protection Avoid installation where the unit will be exposed to excessive winds Before installing make sure that the...

Page 6: ...ore on either side of the unit to facilitate inspection If possible leave 24 or more in front of the unit to facilitate maintenance and service if necessary If possible leave 3 or more above and below...

Page 7: ...84 Maintain the following clearance from both combustible and non combustible materials indicates the distance when installing a heat insu lating board incombustible material other than metal with thi...

Page 8: ...k or paved driveway located on public property Under veranda porch deck or balcony 7 M indicates clearances required in Canada Maintain clearances in accordance with local installation codes and the r...

Page 9: ...ty air inlet into any building 3 above any forced air inlet within 10 Vent Clearances When Heater is In stalled Outdoors With a Vent Cap All clearance requirements are in accordance with ANSI Z21 10 3...

Page 10: ...For Installations in Canada clearances are as follows To windows doors gravity air inlets 36 To forced air inlets 6 3 1 1 1 Outdoor Clearances to Opening into Any Building 1 below 1 horizontally from...

Page 11: ...apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes...

Page 12: ...nt to this appliance Consult the manufacturer s instructions for the proper appliance adapter Vent Piping Noritz N Vent is suggested for the vent system If N Vent is not used a UL listed category III...

Page 13: ...section is recommended to prevent debris from falling into the water heater Install a condensation drain in the horizontal section of the venting For installations in tight spaces where there is not...

Page 14: ...t is installed in a mechanical closet provide a 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per...

Page 15: ...the furthest outlet and the Btuh required by everything after that section Sample Gas Line Sample Calculation Outlet A 45 Use 50 50 000 Btuh requires 1 2 Outlet B 40 65 000 Btuh requires 1 2 Section...

Page 16: ...per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 10 20 30 40 50 60 70 80 90 100 150 200 206 383 614 1261 2934 147 269 418 888 2078 121 2...

Page 17: ...connected to any heating system or components previ ously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of t...

Page 18: ...her means to en sure that the supply water pressure to the inlet of the heater does not fall below 29 psi when the maximum amount of water is being demanded Also install a pressure meter on the inlet...

Page 19: ...ent Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush Frequency Soft 0 1 gpg 1 3 gpg 0 17 mg L None None None None...

Page 20: ...ommends the use of an Isolation Kit with the installation These kits include an integrated shut off and serv ice valve with unions and a pressure relief valve 1 Noritz recommends the use of an Isolati...

Page 21: ...interference and faulty operation Disconnect Power Electrical Shock Hazard Do not turn power on until electrical wiring is finished Disconnect power before servicing Failure to do so may result in de...

Page 22: ...OFF button on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display When setting the maximum temperature to 125 160 F 1 Turn the water heater...

Page 23: ...Part RC CORD26 or use 18AWG wire Install according to the National Electrical Code and all applicable local codes Connecting Remote Controller Cord to Unit Keep the remote controller cord away from th...

Page 24: ...needs to be cleaned it must be performed by a qualified service technician Do not obstruct the flow of combustion and ventilation air The pressure relief valve must be operated once a year to ensure...

Page 25: ...s stop and follow the instruc tions on page 3 of Owner s Guide 6 Turn the gas control manual valve counterclockwise to the on position 7 Turn on electric power to the unit 8 The unit will now operate...

Page 26: ...0 6 OBLONG HOLE HOT WATER OUTLET 3 4 COLD WATER INLET 3 4 GAS INLET 3 4 WIRING THROUGHWAYS b n k c g n s f r 4 0 5 2 0 3 x 0 5 OBLONG HOLE 4 7 2 0 3 3 2 4 3 3 4 7 3 0 3 x 0 6 OBLONG HOLE 0 4 24 5 0 4...

Page 27: ...OTTOM OFCASE BOTTOM OFCASE VIEW FROM TOP UPPER WALL MOUNT BRACKETS LOWER WALL MOUNT BRACKETS AIR INLET AIR INLET GAS INLET COLD WATER INLET WATER DRAIN VALVE HOT WATER OUTLET WATER FILTER WATER DRAIN...

Page 28: ...ING THROUGHWAYS 13 3 13 1 13 8 20 5 0 4 19 2 0 4 6 7 1 2 0 4 21 4 4 7 2 4 3 3 0 4 4 7 COLD WATER INLET 3 4 HOT WATER OUTLET 3 4 7 0 4 3 1 5 3 8 1 6 GAS INLET 1 2 10 0 3 9 7 2 2 2 VIEW FROM TOP WIRING...

Page 29: ...otes on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the con troller Avoid loca...

Page 30: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Page 31: ...the wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside w...

Reviews: