Noritz NC250-SV-ASME Installation Manual Download Page 52

52

Do not connect electrical power to the unit until all electrical wiring has been completed.

Consult a qualified electrician
for the electrical work.

12.

 

Electrical Wiring

This appliance must be electrically grounded in accordance with local codes, or in the absence of local codes,
with the National Electrical Code, ANSI/NFPA 70. In Canada, the latest CSA C22.1 Electrical Code.

Caution:

 Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper

and dangerous operation.

Verify proper operation after servicing.

Field wiring to be performed at time of appliance installation.

• The electrical supply required by the water heater is

120VAC at 60 Hz.
The power consumption may be up to 250W or higher if
using optional accessories.
Use an appropriate circuit.

• Do not disconnect the power supply when not in use. When

the power is off, the freeze prevention in the water heater
will not activate, resulting in possible freezing damage.

• Do not let the power cord contact the

gas piping.

Tie the redundant power cord out-
side the water heater. Putting the
redundant length of cord inside the
water heater may cause electrical
interference and faulty operation.

Disconnect  Power

Electrical Shock Hazard
Do not turn power on until electrical wiring is finished. Disconnect power before servicing.

Failure to do so may result in death or serious injury from electrical shock.

WARNING

Electrostatic discharge can affect electronic components. Take precautions to prevent electrostatic discharges from
personnel or hand tools during the water heater installation and servicing to protect product’s electronic control.

CAUTION

Ground

• To prevent electrical shock, provide a ground

with resistance less than 100   . An electrician
should do this work.

• A grounding screw is provided on the back in

the junction box.

Do not connect the ground to the city water
or gas piping. Do not tie the ground to a tele-
phone line.

Breaker Installation

• Mount a device which shuts off the electrical

path automatically (leakage breaker) when
electrical leakage is detected.

1. Remove the screw (one) of the junction box and

open the cover of the junction box.

2. Connect the grounding wire to the ground screw in

the cover.

3. Crimp the outdoor power cable to the power cable of

the unit.

Junction Box

Power Cord

Ground

Summary of Contents for NC250-SV-ASME

Page 1: ...on the warranty and to hand the warranty to the customer along with the Owner s Guide WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property...

Page 2: ...er s Guide Warranty Installation Manual this document 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation Outdoor Vent Cap VC4 1 1...

Page 3: ...n the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent heat l...

Page 4: ...approved methods in order to ensure full warranty coverage WARNING CAUTION Check the Gas Check that the rating plate indicates the correct type of gas Check that the gas supply line is sized for 250...

Page 5: ...r materials Avoid places where fires are common such as those where gasoline benzene and adhesives are handled or places in which corrosive gases ammonia chlorine sulfur ethylene compounds acids are p...

Page 6: ...installation Do not install the water heater where the exhaust will blow on outer walls or material not resistant to heat Also consider the surrounding trees and animals The heat and moisture from the...

Page 7: ...ove that has the possibility of generating steam that contains fats or oils use a dividing plate or other measure to ensure that the unit is not exposed to air containing such impurities The dividing...

Page 8: ...if within 3m 10 1 8m 6 0 9m 3 above if within 3m 10 1 8m 6 L Above paved sidewalk or paved driveway located on public property Under veranda porch deck or balcony 2 1m 7 M indicates clearances require...

Page 9: ...e outdoor vent cap If it is necessary to vent above the roof line in an outdoor installation also use the base of the vent cap for rain protection Vent Clearances When Heater is Installed Outdoors Wit...

Page 10: ...be done to prevent the transfer of vibration Do not drop or apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a ve...

Page 11: ...to this appliance Consult the manufacturer s instructions for the proper appli ance adapter Vent Piping Noritz N Vent is suggested for the vent system If N Vent is not used a UL listed category III ve...

Page 12: ...mmended to prevent debris from falling into the water heater Install a condensation drain in the horizontal section of the venting For installations in tight spaces where there is not enough room to i...

Page 13: ...n a mechanical closet provide a 600mm 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 90 cubic feet of fresh air per minute Sup...

Page 14: ...NSI Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Tankless Gas Water Heater 250 000 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000 Btuh 3m 10 3...

Page 15: ...1 1114 75 132 194 440 1042 71 125 181 415 983 67 118 171 393 933 55 94 137 320 762 48 82 116 277 661 R Maximum Capacity of Flex TracPipe in Thousands of Btuh Liquified Petroleum 0 5 WC Pressure Drop L...

Page 16: ...stem or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mix...

Page 17: ...wet the floor If neces sary provide drain piping or use a drain hose to remove the water Hot water piping Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or ot...

Page 18: ...Optional Sediment Filter Water Treatment Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush Frequency Soft 0 1 gpg 1...

Page 19: ...he water heater and Air Handler 3 Check valve required if it is not included with the pump 4 Set the flow switch to deactivate the Air Handler when the domestic hot water flow reaches 11 3 L min 3 GPM...

Page 20: ...e water heater Putting the redundant length of cord inside the water heater may cause electrical interference and faulty operation Ground To prevent electrical shock provide a ground with resistance l...

Page 21: ...stall the remote controller according to the instructions in the Installation Guide p 31 The Noritz Tankless Gas Water Heater can be programmed so that it will default to one of four tempera tures if...

Page 22: ...ode and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of...

Page 23: ...hich 120VAC will be supplied directly from a wall circuit to the pump 5 Replace the front cover Supplies Power for Circulating Pump Use a Relay for Larger Pumps Pump Wiring This feature is not availab...

Page 24: ...lack 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3...

Page 25: ...r a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do...

Page 26: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Page 27: ...2 2 GAS INLET 56mm 2 2 468mm 18 4 448mm 17 6 619mm 24 4 LED AIR INLET 450mm 17 7 GAS INLET 95mm 3 7 40mm 1 6 10mm 0 4 240mm 9 4 29mm 1 1 586mm 23 1 69mm 2 7 AIR INLET mm inch 36mm 1 4 70mm 2 8 100mm...

Page 28: ...ize the water supply piping to allow for maximum flow rates of the units Hot Water 1 1 4 2 Water supply Also disconnect this connector on units 2 6 Disconnect this Connector Expansion Tank Unit 6 Unit...

Page 29: ...2 pumps in parallel The system controller will stop the units from heating when the tank is up to temperature and the unit will cut the flow through it to 9 8 L min 2 6 GPM Install the plumbing so tha...

Page 30: ...2345678 B5 B5 System Controller No 5 No 4 No 3 No 2 Remote Control terminal block Remote control terminal block System select connectors Disconnect this Connector Disconnect this Connector Disconnect...

Page 31: ...es on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locatio...

Page 32: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Page 33: ...taining the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wall Wall packing...

Page 34: ...follow the installation instructions Failures and damage caused by erroneous work or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly...

Page 35: ...m 10 1 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation Q ty Shape Part Part Shape Q ty Flue Terminal VT4 TL 1 Remote Controlle...

Page 36: ...en the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent heat...

Page 37: ...es and possibly scalding If absolutely necessary use mixing valves to ensure output temperatures do not get to scalding levels Do not use a solar pre heater with the quick connect multi system Precaut...

Page 38: ...result Avoid installation in places where special chemical agents e g hair spray or spray detergent are used Ignition failures and malfunction may occur as a result Carbon Monoxide Poisoning Hazard Do...

Page 39: ...nal noises while it is running Before installing make sure that the exhaust flue termination will have the proper clearances according to the National Fuel Gas Code ANSI Z223 1 State of California The...

Page 40: ...a where an effective shield makes a clearance of 600mm 24 or more in front of the exhaust outlet Check Illustration Securing of space for repair inspection 600mm 24 or more 200mm 8 or more Outdoor Cle...

Page 41: ...ht 4 5m 15 above meter regulator assembly I Service regulator vent outlet 0 9m 3 J Nonmechanical air supply inlet or combustion air inlet to any other appliance K Mechanical air supply inlet L Above p...

Page 42: ...Locating Screw Holes Mounting Structure When installing with bare hands take caution to not inflict injury Be careful not to hit electrical wiring gas or water piping while drilling holes Item CAUTIO...

Page 43: ...om the outside Vent terminal Vent terminal not far enough too far Snow drift Tree Avoid installing the terminal where obstacles will block it Elbows Elbow Vent terminal sloping down Intake pipe Exhaus...

Page 44: ...ownwards 1 4 for every 300mm 12 towards the termination Use only UL listed Category III venting products Connect the vent pipe firmly so that it will prevent exhaust gases from leaking Steam or conden...

Page 45: ...om falling into the water heater Install a condensation drain in the horizontal section of the venting Slope the horizontal section 1 4 for every 300mm 12 toward the drain tee 0 3 0 6m 1 2 1 8m 6 0 6m...

Page 46: ...NSI Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Tankless Gas Water Heater 250 000 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000 Btuh 3m 10 3...

Page 47: ...1 1114 75 132 194 440 1042 71 125 181 415 983 67 118 171 393 933 55 94 137 320 762 48 82 116 277 661 R Maximum Capacity of Flex TracPipe in Thousands of Btuh Liquified Petroleum 0 5 WC Pressure Drop L...

Page 48: ...stem or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mix...

Page 49: ...wet the floor If neces sary provide drain piping or use a drain hose to remove the water Hot water piping Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or ot...

Page 50: ...Optional Sediment Filter Water Treatment Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush Frequency Soft 0 1 gpg 1...

Page 51: ...he water heater and Air Handler 3 Check valve required if it is not included with the pump 4 Set the flow switch to deactivate the Air Handler when the domestic hot water flow reaches 11 3 L min 3 GPM...

Page 52: ...e water heater Putting the redundant length of cord inside the water heater may cause electrical interference and faulty operation Disconnect Power Electrical Shock Hazard Do not turn power on until e...

Page 53: ...stall the remote controller according to the instructions in the Installation Guide p 63 The Noritz Tankless Gas Water Heater can be programmed so that it will default to one of four tempera tures if...

Page 54: ...ode and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of...

Page 55: ...m a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Con nect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Page 56: ...lack 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3...

Page 57: ...r a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do...

Page 58: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Page 59: ...WAYS GAS INLET 3 4 COLD WATER INLET 3 4 HOT WATER OUTLET 3 4 366mm 14 4 279mm 11 65mm 2 6 135mm 5 3 70mm 2 8 136mm 5 4 159mm 6 3 175mm 6 9 155mm 6 1 100mm 3 9 195mm 7 7 73mm 2 9 170mm 6 7 140mm 5 5 10...

Page 60: ...ize the water supply piping to allow for maximum flow rates of the units Hot Water 1 1 4 2 Water supply Also disconnect this connector on units 2 6 Disconnect this Connector Expansion Tank Unit 6 Unit...

Page 61: ...2 pumps in parallel The system controller will stop the units from heating when the tank is up to temperature and the unit will cut the flow through it to 9 8 L min 2 6 GPM Install the plumbing so tha...

Page 62: ...connect this Connector Disconnect this Connector Disconnect for system controller Disconnect for system controller Disconnect this Connector Remote Controller Cord PCB Power PCB PCB Power PCB Disconne...

Page 63: ...es on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locatio...

Page 64: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Page 65: ...nstallation doit tre conforme aux r glementations locales ou en l absence de r glementation locale au National Fuel Gas Code la norme ANSI Z223 1 NFPA 54 derni re dition et ou CSA B149 1 au Natural Ga...

Page 66: ...pr sent s ci dessous ne sont pas inclus avec l unit mais peuvent tre n cessaires l installation Guide de l utilisateur Garantie Manuel d installation ce document Bouchon d vent ext rieur VC4 1 1 Cord...

Page 67: ...de deux appareils n utilisez qu une seule t l commande Sch ma du syst me Remarque Raccordez la t l commande un seul des appareils Plomberie type Isolez les conduites d eau chaude pour emp cher la pert...

Page 68: ...z le gaz V rifiez que la plaque signal tique indique le type de gaz correct V rifiez que la conduite d alimentation de gaz est calibr e pour 250 000 Btuh pour cette unit V rifiez l alimentation L alim...

Page 69: ...itif de ventilation et une combustion incompl te pourrait en r sulter Evitez l installation dans des endroits o des agents chimiques sp ciaux ex des produits coiffants en a rosol ou des d tergents en...

Page 70: ...murs mitoyens car celui ci met des bruits d op ration pendant son fonctionnement Assurez vous que l emplacement permet l installation de la conduite d vacuation comme sp cifi Pour l installation ext r...

Page 71: ...la vapeur contenant des graisses ou de l huile utilisez une plaque de division ou autre mesure pour assurer que l unit ne soit expos e de l air contenant de telles impuret s La plaque de division dev...

Page 72: ...e terrasse ou balcon C D E F G H I J K L M 300mm 12 300mm 12 1 2m 4 au dessous ou sur le c t de l ouverture ou 0 3m 1 au dessus de l ouverture 900mm 36 0 9m 3 dans la limite d une hauteur de 4 5m 15 a...

Page 73: ...r toutes les situations ci dessus Int rieur Ext rieur avec bouche d vent Exigences de d gagement des bouches de l vent par rapport aux ouvertures du b timent 1 2m 4 dessous 1 2m 4 horizontalement part...

Page 74: ...rieure 3 D terminez les positions des quatre vis restantes deux pour l applique sup rieure et deux pour l inf rieure puis d posez l unit Le poids de l appareil sera appliqu sur le mur Si la force du...

Page 75: ...e vous utilisez des quipements autres que le N Vent 100mm 4 25mm 1 25mm 1 250mm 10 c t s 375mm 15 haut 150mm 6 bas La premi re section verticale partir du haut du chauffe eau ne doit pas tre plus long...

Page 76: ...u besoin Dans l tat du Commonwealth of Massachu setts un d tecteur de monoxyde de carbone est n cessaire pour tout quipement fonctionnant au gaz et a r horizontalement sur mur lat ral Reportez vous au...

Page 77: ...nt la circulation de l air comburant Chaque ouverture doit tre de 250 pouces carr s si elles fournissent l air int rieur et 100 pouces carr s pour l air ext rieur Si l unit est install e dans un placa...

Page 78: ...en connectant un manom tre avec un tube en silicone soit en retirant la vis 1 8 NPT avec une cl six pans m les et en connectant la jauge de pression appropri e Compteur gaz S lectionnez un compteur ga...

Page 79: ...TracPipe en pied cubique par heures de gaz naturel Gravit sp cifique 0 60 Perte de pression 0 5 WC 3 4 1 1 1 4 1 1 2 2 3m 10 6m 20 9m 30 12m 40 15m 50 18m 60 21m 70 24m 80 27m 90 30m 100 45m 150 3m 1...

Page 80: ...ifi e de la soupape Les conduites et pi ces raccord es au chauffe eau doivent convenir une utilisation avec de l eau potable Des produits chimiques nocifs comme ceux utilis s dans l entretien des chau...

Page 81: ...sol Au besoin placez une tuyauterie de vidange ou utilisez un flexible de vidange pour retirer l eau Conduite d eau chaude N utilisez pas de plomb PVC acier ou de tuyaux trait s au chromate scellement...

Page 82: ...u Type d eau Niveau de duret Niveau de duret Appareil de traitement Fr quence de purge Appareil de traitement Fr quence de purge Type d eau Doux 0 1 gpg 1 3 gpg 0 17 mg L Aucun Aucun Aucun Aucun Aucun...

Page 83: ...utilis e Si le signal de commande de la pompe n est pas utilis un aquastat doit tre utilis pour commander la pompe 3 Utilisez un aquastat si le chauffe eau ne commande pas la pompe R glez l aquastat...

Page 84: ...moment de l installation de l appareil AVERTISSEMENT L alimentation requise par le chauffe eau est de 120VCA 60 Hz La consommation lectrique peut tre sup rieure ou gale 250W lors de l utilisation d ac...

Page 85: ...indiqu en dessous La temp rature par d faut est 50 C 122 F lorsque le c ble de s lection de temp rature n est pas branch 4 Remettez le couvercle avant du chauffe eau en place 4 vis 5 R tablissez l ali...

Page 86: ...en cuivre peut rouiller et provoquer des probl mes Veillez serrer la main lors du serrage sur le bornier de raccordement Des outils peuvent endommager le bornier de raccordement 1 Assurez vous que le...

Page 87: ...nn que le signal pour fermer un relais normalement ouvert par lequel 120VCA sera appliqu directement d un circuit mural la pompe 5 Remettez en place le couvercle avant Etiquette du c ble de commande d...

Page 88: ...sez un cordon de raccordement rapide vendu s par ment Branchement du cordon de raccordement rapide aux deux unit s 1 Mettez hors tension 2 D posez le couvercle avant du chauffe eau 4 vis 3 Faites pass...

Page 89: ...uli rement pour une couleur bleue et une consistance ad quates Si la flamme ne semble pas normale le br leur a peut tre besoin d tre nettoy Si le br leur a besoin d tre nettoy ce doit tre effectu par...

Page 90: ...le devant du chauffe eau 2 Coupez compl tement l alimentation lectrique de l unit 3 Ne tentez pas d allumer le br leur manuellement 4 Tournez la soupape manuelle d admission du gaz externe l unit dan...

Page 91: ...VIDANGE DE L EAU ENTR E D EAU FROIDE ENTR E DE GAZ 3 4 ENTR E D EAU FROIDE 3 4 OUVERTURES POUR C BLES VUE PARTIR DE DESSUS Hauteur de chaque aller de bas du coffret ENTR E DE GAZ SORTIE D EAU CHAUDE...

Page 92: ...z l interrupteur DIP 3 sur OFF Voir Manuel d installation SC 201 6M Tuyau de gaz Calibrez la tuyauterie d eau pour permettre les vitesses d coulement maximales des unit s Alimentation en eau 1 1 4 2 P...

Page 93: ...r Alimentation en eau chaude T l commande Lors de l installation de deux pompes en parall le Le r gulateur du syst me emp chera les unit s de chauffer lorsque le r servoir augmente de temp rature et l...

Page 94: ...system controller Disconnect for system controller Cordon de t l commande PCI PCI d alimentation PCI PCI d alimentation Disconnectforsystemcontroller Bornier de raccordement de la t l commande PCI PC...

Page 95: ...benz ne d tergents gras ou huileux sont utilis s Evitez de l installer l ext rieur ou encore l int rieur dans un endroit o elle serait expos e aux rayons du soleil Ne d sassemblez pas la t l commande...

Page 96: ...bomb e cruciforme Ancrage pour mur 3 Retirez le couvercle de la t l commande marquez l emplacement des trous de vis et percez les trous pour les ancrages pour mur 4 Ins rez les ancrages pour mur visse...

Page 97: ...la garniture de la bo te de d rivation et la bo te de d rivation par dessus les c bles de la t l commande et la protub rance du tuyau du mur partir du mur ext rieur Garniture du mur Tuyau du mur Faite...

Page 98: ...eur L installation doit tre conforme aux r glementations locales ou en l absence de r glementation locale au National Fuel Gas Code la norme ANSI Z223 1 NFPA 54 derni re dition et ou CSA B149 1 au Nat...

Page 99: ...cessoires optionnels Les accessoires pr sent s ci dessous ne sont pas inclus avec l unit mais peuvent tre n cessaires l installation Qt Forme Pi ce Pi ce Forme Qt Clapets d isolement comprenant une so...

Page 100: ...dement rapide G 3 Installation du multisyst me par raccordement rapide Le multisyst me raccordement rapide permet d installer deux unit s ensemble en utilisant uniquement le cordon raccordement rapide...

Page 101: ...atteignent pas des niveaux bouillants N utilisez pas un r chauffeur solaire avec le multisyst me raccordement rapide 4 Avant l installation ATTENTION AVERTISSEMENT Pr cautions relatives au remplaceme...

Page 102: ...s une salle de bains sous peine de l endommager ou de provoquer un incendie Consultez le client pour l emplacement de l installation Installez le chauffe eau dans un endroit pr servant un d gagement a...

Page 103: ...d op ration pendant son fonctionnement Avant l installation assurez vous que la bouche du carneau d vacuation aura le d gagement ad quat selon le National Fuel Gas Code ANSI Z223 1 Etat de Californie...

Page 104: ...applique pas dans une zone o une protection efficace maintient un d gagement d au moins 600mm 24 en face de la sortie d chappement Garantir un espace pour r paration inspection D gagement ext rieur p...

Page 105: ...ouvert sur un minimum de deux c t s sous le sol 7 Installation Fixation au mur D gagement Au dessus d une pente v randa porche terrasse ou balcon Fen tre ou porte qui peuvent tre ouvertes Fen tre touj...

Page 106: ...rieure et deux pour l inf rieure puis d posez l unit Placer les trous de vis Illustration V rification Placez les trous de vis Montage Structure Rubrique H IG H E L E V A T IO N D IS C O N N E C T Si...

Page 107: ...e l vent pas assez loin trop loin Amoncellement de neige Arbre vitez d installer la bouche l o elle sera bloqu e par des obstacles Coudes Coude Bouche de l vent inclin vers le bas Tuyau d entr e Tuyau...

Page 108: ...talement sur mur lat ral Reportez vous au Technical Bulletin TB 010606 pour des instructions compl tes d installation Ne stockez pas de substances dangereuses ou inflammables proximit de la bouche de...

Page 109: ...vent Tuyau d chappement Terminez au moins 1 8m 6 de l entr e d air comburant d un appareil et 0 9m 3 d une ouverture d un b timent compteur gaz r gulateur de gaz etc Enfermez les syst mes d vent ext r...

Page 110: ...en connectant un manom tre avec un tube en silicone soit en retirant la vis 1 8 NPT avec une cl six pans m les et en connectant la jauge de pression appropri e Compteur gaz S lectionnez un compteur g...

Page 111: ...e en pied cubique par heures de gaz naturel Gravit sp cifique 0 60 Perte de pression 0 5 WC 3 4 1 1 1 4 1 1 2 2 3m 10 6m 20 9m 30 12m 40 15m 50 18m 60 21m 70 24m 80 27m 90 30m 100 45m 150 60m 200 3m 1...

Page 112: ...ifi e de la soupape Les conduites et pi ces raccord es au chauffe eau doivent convenir une utilisation avec de l eau potable Des produits chimiques nocifs comme ceux utilis s dans l entretien des chau...

Page 113: ...sol Au besoin placez une tuyauterie de vidange ou utilisez un flexible de vidange pour retirer l eau Conduite d eau chaude N utilisez pas de plomb PVC acier ou de tuyaux trait s au chromate scellement...

Page 114: ...d eau Niveau de duret Niveau de duret Appareil de traitement Fr quence de purge Appareil de traitement Fr quence de purge Type d eau Doux 0 1 gpg 1 3 gpg 0 17 mg L Aucun Aucun Aucun Aucun Aucun Aucun...

Page 115: ...utilis e Si le signal de commande de la pompe n est pas utilis un aquastat doit tre utilis pour commander la pompe 3 Utilisez un aquastat si le chauffe eau ne commande pas la pompe R glez l aquastat...

Page 116: ...moment de l installation de l appareil AVERTISSEMENT L alimentation requise par le chauffe eau est de 120VCA 60 Hz La consommation lectrique peut tre sup rieure ou gale 250W lors de l utilisation d ac...

Page 117: ...indiqu en dessous La temp rature par d faut est 50 C 122 F lorsque le c ble de s lection de temp rature n est pas branch 4 Remettez le couvercle avant du chauffe eau en place 4 vis 5 R tablissez l ali...

Page 118: ...en cuivre peut rouiller et provoquer des probl mes Veillez serrer la main lors du serrage sur le bornier de raccordement Des outils peuvent endommager le bornier de raccordement 1 Assurez vous que le...

Page 119: ...nn que le signal pour fermer un relais normalement ouvert par lequel 120VCA sera appliqu directement d un circuit mural la pompe 5 Remettez en place le couvercle avant Etiquette du c ble de commande d...

Page 120: ...sez un cordon de raccordement rapide vendu s par ment Branchement du cordon de raccordement rapide aux deux unit s 1 Mettez hors tension 2 D posez le couvercle avant du chauffe eau 4 vis 3 Faites pass...

Page 121: ...uli rement pour une couleur bleue et une consistance ad quates Si la flamme ne semble pas normale le br leur a peut tre besoin d tre nettoy Si le br leur a besoin d tre nettoy ce doit tre effectu par...

Page 122: ...le devant du chauffe eau 2 Coupez compl tement l alimentation lectrique de l unit 3 Ne tentez pas d allumer le br leur manuellement 4 Tournez la soupape manuelle d admission du gaz externe l unit dan...

Page 123: ...5 4 159mm 6 3 175mm 6 9 155mm 6 1 100mm 3 9 195mm 7 7 73mm 2 9 170mm 6 7 140mm 5 5 100mm 3 9 70mm 2 8 36mm 1 4 665mm 26 2 170mm 6 7 140mm 5 5 100mm 3 9 70mm 2 8 36mm 1 4 40mm 1 6 95mm 3 7 77mm 3 586mm...

Page 124: ...z l interrupteur DIP 3 sur OFF Voir Manuel d installation SC 201 6M Tuyau de gaz Calibrez la tuyauterie d eau pour permettre les vitesses d coulement maximales des unit s Alimentation en eau 1 1 4 2 P...

Page 125: ...r Alimentation en eau chaude T l commande Lors de l installation de deux pompes en parall le Le r gulateur du syst me emp chera les unit s de chauffer lorsque le r servoir augmente de temp rature et l...

Page 126: ...system controller Disconnect for system controller Cordon de t l commande PCI PCI d alimentation PCI PCI d alimentation Disconnectforsystemcontroller Bornier de raccordement de la t l commande PCI PC...

Page 127: ...ex benz ne d tergents gras ou huileux sont utilis s Evitez de l installer l ext rieur ou encore l int rieur dans un endroit o elle serait expos e aux rayons du soleil Ne d sassemblez pas la t l comman...

Page 128: ...bomb e cruciforme Ancrage pour mur 3 Retirez le couvercle de la t l commande marquez l emplacement des trous de vis et percez les trous pour les ancrages pour mur 4 Ins rez les ancrages pour mur visse...