Noritz N-0931M-ASME Installation Manual Download Page 14

14

Gas Meter

Select a gas meter capable of supplying the entire
btuh demand of all gas appliances in the building.

Gas Connection

• Do not use piping with a diameter smaller than

the inlet diameter of the water heater.

• Gas flex lines are not recommended unless they

are rated for 250,000 btuh.

• Install a gas shutoff valve on the supply line.
• Use only approved gas piping materials.

Follow the instructions from the gas supplier.

Gas Pressure

Size the gas line according to total btuh demand
of the building and length from the meter or
regulator so that the following supply pressures
are available even at maximum demand:

Natural Gas Supply Pressure

Min. 5" WC
Max. 10.5" WC

LP Gas Supply Pressure

Min. 10.5" WC
Max. 14" WC

9.

 

Gas Piping

The appliance and its individual shutoff valve must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures in excess of 

1

2

 psig (3.5 kPa).

The Appliance must be isolated from the gas supply piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 

1

2

psig (3.5 kPa).

The appliance and its gas connections must be leak tested before placing the appliance in operation.

The inlet gas pressure must be within the range specified. This is for the purposes of input adjustment.

In order to choose the proper size for the gas line, consult local codes or the National Fuel Gas Code ANSI
Z223.1.

Natural Gas

Meter

**See next page for the pipe capacity charts.

Noritz Tankless Gas Water Heater

(250,000 Btuh)

Clothes Dryer
(35,000 Btuh)

Barbecue

(50,000 Btuh)

Gas Range Stove

(65,000 Btuh)

10'

10'

10'

10'

5'

5'

5'

5'

Gas Fireplace

(25,000 Btuh)

Instructions

1. Size each outlet branch starting from the furthest
    using the Btuh required and the length from the 
    meter.
2. Size each section of the main line using the
    length to the furthest outlet and the Btuh
    required by everything after that section. 

Sample Gas Line

Sample Calculation

Outlet A: 45' (Use 50'), 50,000 Btuh requires 1/2"
Outlet B: 40',  65,000 Btuh requires 1/2"
Section 1: 45' (Use 50'), 115,000 Btuh requires 3/4"
Outlet C: 30', 35,000 Btuh requires 1/2"
Section 2: 45' (Use 50'), 150,000 Btuh requires 3/4"
Outlet D: 25' (Use 30'), 25,000 Btuh requires 1/2"
Section 3: 45' (Use 50'), 175,000 Btuh requires 1"
Outlet E: 25' (Use 30'), 250,000 Btuh requires 1"
Section 4: 45' (Use 50'), 425,000 Btuh requires 1-1/4"   

 

Section 3 Section 2

Section 1

Outlet A

Outlet B

Outlet C

Outlet D

Outlet E

5'

5'

Section 4

Measuring Gas Pressure

In order to check the gas supply pressure to the unit, a
tap is provided on the gas inlet.  Remove the hex head
philips screw from the tap, and connect a  manometer
using a silicon tube.

In order to check the gas manifold pressure, a pair of
taps are provided on the gas valve inside the unit.
The pressure can be checked either by removing the hex
head philips screw and connecting a manometer with a
silicon tube, or by removing the 1/8" NPT screw with an
allen wrench and connecting the appropriate pressure
gauge.

Summary of Contents for N-0931M-ASME

Page 1: ...customer along with the Owner s Guide WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or death Installation mus...

Page 2: ...er s Guide Warranty Installation Manual this document 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation Outdoor Vent Cap VC4 1 1...

Page 3: ...een the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent heat...

Page 4: ...he water with approved methods in order to ensure full warranty coverage CAUTION Check the Gas Check that the rating plate indicates the correct type of gas Check that the gas supply line is sized for...

Page 5: ...e Dust may block the air supply opening causing the performance of the device fan to drop and incomplete combustion to occur as a result Avoid installation in places where special chemical agents e g...

Page 6: ...re the unit will be exposed to excessive winds Before installing make sure that the vent termination or the vent cap in an outdoor installation will have the proper clearances according to the Nationa...

Page 7: ...ave 8 or more on either side of the unit to facilitate inspection If possible leave 24 or more in front of the unit to facilitate maintenance and service if necessary If possible leave 3 or more above...

Page 8: ...lk or paved driveway located on public property Under veranda porch deck or balcony 7 M indicates clearances required in Canada Maintain clearances in accordance with local installation codes and the...

Page 9: ...he outdoor vent cap If it is necessary to vent above the roof line in an outdoor installation also use the base of the vent cap for rain protection Vent Clearances When Heater is In stalled Outdoors W...

Page 10: ...be done to prevent the transfer of vibration Do not drop or apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a ve...

Page 11: ...ting system Vent Piping Use only UL listed category III vent materials Follow the vent pipe manufacturer s installation instructions Make the vertical section of the exhaust vent as short as possible...

Page 12: ...anufacturer s instructions Slope the horizontal vent 1 4 for every 12 to wards the drain tee Do not vent straight upwards Always have a horizontal section of venting Install a condensation drain in th...

Page 13: ...is installed in a mechanical closet provide a 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 90 cubic feet of fresh air per m...

Page 14: ...s line consult local codes or the National Fuel Gas Code ANSI Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Tankless Gas Water Heater 250 000 Btuh Clothes Dryer 35 000 Btu...

Page 15: ...in Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 10 20 30 40 50 60 70 80 90 100 150 200 206 383 614 1261 2934 147 269 418 8...

Page 16: ...em or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mixin...

Page 17: ...wet the floor If neces sary provide drain piping or use a drain hose to remove the water Hot water piping Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or ot...

Page 18: ...Optional Sediment Filter Water Treatment Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush Frequency Soft 0 1 gpg 1...

Page 19: ...pump 4 Set the flow switch to deactivate the Air Handler when the domestic hot water flow reaches 3 GPM Adjust as necessary to prevent cycling 5 If the system requires water for space heating at a hig...

Page 20: ...e water heater Putting the redundant length of cord inside the water heater may cause electrical interference and faulty operation Ground To prevent electrical shock provide a ground with resistance l...

Page 21: ...emote controller according to the instructions in the Installation Guide p 31 The Noritz Tankless Gas Water Heater can be programmed so that it will default to one of four tempera tures if the remote...

Page 22: ...and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of sl...

Page 23: ...hich 120VAC will be supplied directly from a wall circuit to the pump 5 Replace the front cover Supplies Power for Circulating Pump Use a Relay for Larger Pumps Pump Wiring This feature is not availab...

Page 24: ...lack 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3...

Page 25: ...r a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do...

Page 26: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Page 27: ...WAY 120VAC VIEW FROM TOP 14 4 11 7 7 120VAC WIRING THOROUGHWAY COLD WATER INLET 3 4 WIRING THOROUGHWAYS HOT WATER OUTLET 3 4 16 Multi System A Installation without a recirculation system Insulate or a...

Page 28: ...Pipe Hot Water Return Line Size the water supply piping to allow for maximum flow rates of the units Hot Water 1 1 4 2 Water supply Also disconnect this connector on units 2 6 Disconnect this Connecto...

Page 29: ...ontrol When installing 2 pumps in parallel The system controller will stop the units from heating when the tank is up to temperature and the unit will cut the flow through it to 2 6 GPM Install the pl...

Page 30: ...onnect this Connector Disconnect this Connector Disconnect for system controller Disconnect for system controller Disconnect this Connector Remote Controller Cord PCB Power PCB PCB Power PCB Disconnec...

Page 31: ...otes on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locat...

Page 32: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Page 33: ...he wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wa...

Reviews: