37
*TC/TL FURNACES WITH VARIABLE SPEED BLOWERS
“B” CABINET
Switch Settings
(0 = OFF, 1 = ON)
CFM
Nominal A/C and HP
Capacity
HEAT
COOL
1-4
5
6
7
8
LOW
HIGH
1
0
0
0
0
485
700
2 T
O
N
1
0
0
0
1
525
760
1
0
0
1
0
565
820
2.5 T
O
N
1
0
0
1
1
605
880
1
0
1
0
0
650
940
1
0
1
0
1
690
1,000
1
0
1
1
0
730
1,060
3 T
O
N
1
0
1
1
1
775
1,120
1
1
0
0
0
815
1,180
1
1
0
0
1
855
1,240
3.5 T
O
N
1
1
0
1
0
895
1,300
1
1
0
1
1
940
1,360
1
1
1
0
0
980
1,420
1
1
1
0
1
1,020
1,480
1
1
1
1
0
1,065
1,540
1
1
1
1
1
1,105
1,600
*TC/TL FURNACES WITH VARIABLE SPEED BLOWERS
“C” CABINET
*TC/TL FURNACES WITH VARIABLE SPEED BLOWERS
“D” CABINET
Switch Settings
(0 = OFF, 1 = ON)
CFM
Nominal A/C and
HP Capacity
Switch Settings
(0 = OFF, 1 = ON)
CFM
Nominal A/C and HP
Capacity
HEAT
COOL
HEAT
COOL
1-4
5
6
7
8
LOW
HIGH
1-4
5
6
7
8
LOW
HIGH
#
0
0
0
0
705
1,025
2.5 T
O
N
#
0
0
0
0
965
1,400
3.5 T
O
N
#
0
0
0
1
750
1,090
3 T
O
N
#
0
0
0
1
995
1,440
4 T
O
N
#
0
0
1
0
795
1,155
#
0
0
1
0
1,020
1,480
#
0
0
1
1
840
1,220
#
0
0
1
1
1,050
1,520
#
0
1
0
0
885
1,285
3.5 T
O
N
#
0
1
0
0
1,075
1,560
#
0
1
0
1
930
1,350
#
0
1
0
1
1,105
1,600
#
0
1
1
0
975
1,415
4 T
O
N
#
0
1
1
0
1,130
1,640
#
0
1
1
1
1,020
1,480
#
0
1
1
1
1,160
1,680
#
1
0
0
0
1,065
1,545
#
1
0
0
0
1,185
1,720
5 T
O
N
#
1
0
0
1
1,110
1,610
#
1
0
0
1
1,215
1,760
#
1
0
1
0
1,155
1,675
5 T
O
N
#
1
0
1
0
1,240
1,800
#
1
0
1
1
1,200
1,740
#
1
0
1
1
1,270
1,840
#
1
1
0
0
1,245
1,805
#
1
1
0
0
1,295
1,880
#
1
1
0
1
1,290
1,870
#
1
1
0
1
1,325
1,920
#
1
1
1
0
1,335
1,935
#
1
1
1
0
1,350
1,960
#
1
1
1
1
1,380
2,000
#
1
1
1
1
1,380
2,000
# Switch not used - can be 0 or 1
Table 10. Nominal Cooling/Heat Pump Airfl ows (CFM) for Variable Speed Furnaces