20
Model
number
P6sP-
nominal unit
Voltage
High static
Kit #
single circuit (unit + Heater Kit) see note
Mca
MoP
Factory unit Electrical Data:
9 kW
18 kW
30 kW
35 kW
9 kW
18 kW
30 kW
35 kW
-072C
208 - 230 V
Factory Std.
30 - 31
50 - 57
80 - 91
- n/a -
45 - 45
50 - 60
80 - 100
- n/a -
-072D
460 V
17
29
46
- n/a -
20
30
50
- n/a -
-090Ca
208 - 230 V
Factory Std.
39 - 39
51 - 58
81 - 92
97 - 110
50 - 50
60 - 60
90 - 100
100 - 110
-090Da
460 V
19
30
46
55
20
30
50
60
-120Ca
208 - 230 V
Factory Std.
45 - 45
51 - 58
81 - 92
97 - 110
60 - 60
60 - 60
90 - 100
100 - 110
-120Da
460 V
22
30
46
55
25
30
50
60
Medium & High static Drive Electrical Data:
-072C
208 - 230 V
920609
32 - 33
51 - 58
81 - 92
- n/a -
50 - 45
60 - 60
90 - 100
- n/a -
-072D
460 V
920560
18
30
46
- n/a -
25
30
50
- n/a -
-090Ca
208 - 230 V
921481
40 - 40
53 - 60
83 - 94
99 - 112
50 - 50
60 - 60
90 - 100
100 - 125
-090Da
460 V
19
31
47
56
25
35
50
60
-120Ca
208 - 230 V
921645
47 - 47
53 - 60
83 - 94
99 - 112
60 - 60
60 - 60
90 - 100
100 - 125
-120Da
460 V
23
31
47
56
30
35
50
60
notE:
Nordyne specifically recommends the use of the 917468 Dual Circuit adapter kit for all applications of H5HK 30kW & 35kW Electric
Heat Kits.
table 3. P6sP Electrical Data - single supply circuits