Nordyne *MQ 97%+ Upfl ow/Horizontal User Manual Download Page 7

7

STARTUP AND SHUTDOWN

INSPECTION

FREQUENCY

The furnace should be inspected annually by a licensed 
HVAC technician. Table 1 (page 8) contains suggested 
inspections and frequency of maintenance.

VENTING SYSTEM

•  Existing masonry chimneys should be inspected and 

relined if necessary. Vent pipe must slope upwards 
and be physically sound without holes or corrosion. 
Any corroded section of vent pipe must be replaced, 
and any obstruction or blockage must be removed by 
a licensed HVAC technician.

•  Flue passageways, the vent system, and the burners 

should be inspected and cleaned (if required) by a 
licensed HVAC technician annually to ensure continued 
safe operation.

BLOWER AND FILTER

It is recommended that the blower compartment be 
cleaned of dirt or lint that may have accumulated in the 
compartment or on the blower and motor as part of the 
annual inspection.

AIR FOR COMBUSTION

•  For proper and safe operation, the furnace needs air for 

combustion and ventilation. 

Do Not

 block or obstruct 

air openings on the furnace, or any air openings where 
the furnace may be installed, including any surrounding 
spaces.

•  Direct vent furnaces pull combustion air from the 

outdoors and vent combustion products back outside. 
Combustion air coming from the outside needs to be 
clean of chemicals that can cause corrosion, such as 
pool chlorinating products.

AIR FOR COMFORT

•  Keep air fi lters cleaned. It is recommended that the 

furnace air fi lter be checked at least once a month. 
Clean or replace fi lter to maintain proper airfl ow  and 
achieve maximum effi ciency.

•  Furniture  and drapery should be arranged so that 

the supply air registers and return grilles are not 
obstructed.

Figure 2. Gas Valves

IN

TWO - STAGE VALVE

ON

OFF

SINGLE STAGE VALVE

MODULATING VALVE

STARTING THE  FURNACE:

1.  Make sure the fi lter is clean and in place.

2.  Make sure the vent system is properly installed.

3.  Set the thermostat to the lowest setting.

4.  Close the manual gas valve outside the furnace.

5.  Turn off all electric to the furnace.

6.  Remove the door from the burner compartment.

7.  Set the gas valve switch or knob to the OFF position. 

See Figure 2 for gas valve switch or knob location.

8.  Wait 5 minutes. If there is any smell of gas, see “WHAT 

TO DO IF YOU SMELL GAS” on page 5.

9.  Set the gas valve switch or knob to the ON position.

10. Turn on all electric to the furnace.

11. Open the manual gas valve.

12. Turn the thermostat back up to force ignition.

13. Observe operation, including burners. If burners fail 

to ignite, call a licensed HVAC technician.

14. Replace the door on the burner compartment.

SHUTTING DOWN THE FURNACE:

Should you ever need to shut down your furnace for 
service or maintenance, follow these steps:

1.  Set the thermostat to the lowest setting.

2.  Close the manual gas valve outside the furnace.

3.  Turn electric to the furnace off.

4.  Open the door to the burner compartment.

5.  Set the gas valve switch or knob to the OFF 

position.

6.  Replace the door on the burner Compartment.

Summary of Contents for *MQ 97%+ Upfl ow/Horizontal

Page 1: ...YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier from a neigh...

Page 2: ...2...

Page 3: ...ce and Air Ducts 8 TROUBLESHOOTING 8 LOCATION OF SINGLE STAGE FURNACE COMPONENTS 9 LOCATION OF TWO STAGE FURNACE COMPONENTS 10 LOCATION OF MODULATING FURNACE COMPONENTS 11 Congratulations on the purch...

Page 4: ...the air return on the furnace or in an air return register in your habitable space If the filter becomes dirty it should be cleaned or replaced SAFETY INFORMATION Safety markings are used frequently...

Page 5: ...in serious personal injury or death SHUTTING DOWN THE FURNACE Shouldyoueverneedtoshutdownyourfurnaceforservice or maintenance shut off the gas valve to the furnace before shutting off the electrical...

Page 6: ...an iQ thermostat available through your dealer CAUTION Do not reduce the supply of fresh air to the furnace It is extremely important that the furnacereceivesanunobstructedflowofclean fresh air to pr...

Page 7: ...s cleaned It is recommended that the furnace air filter be checked at least once a month Clean or replace filter to maintain proper airflow and achieve maximum efficiency Furniture and drapery should...

Page 8: ...se The return air duct connection s is secured and sealed to the furnace cabinet and terminates outside the area containing the furnace Any signs of damage or loose connections should be repaired by a...

Page 9: ...PONENT ITEM COMPONENT ITEM COMPONENT 1 Blower Assembly 5 Flame Rollout Switch 9 Gas Valve 13 Pressure Switch 2 Blower Door Switch 6 Flame Sensor 10 Igniter 14 Transformer 3 Burner Assembly 7 Furnace C...

Page 10: ...Motor Choke 2 Blower Door Switch 6 Flame Sensor 10 Igniter 14 Motor Control Board 3 Burner Assembly 7 Furnace Control Board 11 Inducer Assembly 15 Pressure Switch 4 Combustion Tube 8 Gas Manifold 12 L...

Page 11: ...Flame Roll Out Switch 6 Flame Sensor 7 Furnace Control Board 8 Gas Manifold 9 Gas Valve 10 Igniter 11 Inducer Assembly 12 Inducer Limit Switch 13 Motor Choke C and D cabinets only 14 Motor Control Bo...

Page 12: ...7089670 Specifications and illustrations subject to change without notice or incurring obligations Printed in U S A 10 08 O Fallon MO 708967 708967...

Reviews: