background image

10

important! On variable speed models when the unit is 
used in an air conditioning system, connect the o terminal 
to the Y terminal. See Figure 9 (page 20).

control Board
The control board in the air handler controls the timing 
sequence of the elements. Depending on the thermostat 
connection, there are multiple timing sequence variations 
that can be chosen. The board also is equipped with a 3 
second blower on delay and a 15 second blower off delay. 
See Figures 10 - 13 (pages 22 & 23) for control board layout  
and Tables 10 & 11 (pages 27-29) for element sequences.

Twinning
MB7 air handlers are not supplied with a built in twinning 
capability. To connect two air handlers to a common single 
stage AC condensing unit or heat pump, a twinning kit 
is available for field installation. iMPortant: Variable 
speed air handlers cannot be twinned. Please follow 
the instructions supplied with the kit.

Heater Kits
Field-installed electric heater kits are available. Instructions 
for installing the electric heaters are included with the 
heaters. Additional heater kit information can be found in 
the units Technical Specifications.

Air handlers set up with 15 kw or more of electric heat will 
normally be configured for multiple-circuit power supply. 
They may, however, be connected to a single-circuit power 
supply with the addition of a single circuit accessory 
kit. Select the wire size and over-current protection 
in accordance with the minimum circuit ampacity and 
maximum over-current protection shown in Table 9. See 
also the units Technical Specifications.

When electric heat packages with circuit breakers are 
field-installed, the circuit breaker may be used as a 
disconnecting means in most applications. Reference the 
NEC and local codes for disconnect requirements.

If a heater kit is installed:
The MB7 air handler is shipped from the factory without 
an electric heater kit installed. If Electric heat is desired, 
the H6HK heater kit may be purchased separately and 
field installed. Determine the correct size heater kit for your 
unit by referring to the list below or the units rating label. 

A Size Cabinet ............................................... 15Kw max
B Size Cabinet ............................................... 20Kw max
C Size Cabinet ............................................... 20Kw max

1. Connect the 2 wire plug of the air handler to the mating 

2 wire plug of the heater kit.

2. Connect the line voltage leads to the circuit breaker or 

terminal block provided.

3. Connect the heater kit plug with the mating receptacle 

on the air handler control board.

If a heater kit is not installed:
1. Remove the 2 wire plug of the air handler by cutting the 

wires and discarding the plug.

2. Strip the ends of the 2 air handler wires and connect 

to the line-voltage leads with the 2 wire nuts provided. 

electronic air cleaner (eac)
The unit has an output to power an electronic air cleaner 
when the blower is running. This output is rated to 1.0 
amp at 208/240V.

Humidifier
The unit has an output to power a humidifier when the 
blower is running. This output is rated to 1.0 amp at 
208/240V.

optional Humidistat
(MB7EM or MB7VM Models Only)
The optional humidistat may be installed in the return air 
duct to provide excellent humidity control when needed 
and maximum system capacity and energy efficiency when 
humidity levels are normal. The humidistat senses when 
humidity in the return air stream is above a preset level 
(field adjustable) and sends a signal to the motor to reduce 
the airflow so that more moisture may be removed until the 
humidity level drops. The air handler is pre-programmed 
for humidistat operation.

Install the humidistat in the return air duct as directed in 
the installation instructions included with the kit. Wire the 
humidistat through the low-voltage wire entrance in the 
air handler to the control board terminal marked deHuM
Wire the humidistat to open on rise in humidity.

Grounding

 WarninG:

the unit cabinet must have an uninterrupted or 
unbroken electrical ground to minimize personal 
injury if an electrical fault should occur. do not 
use gas piping as an electrical ground!

This unit must be electrically grounded in accordance 
with local codes or, in the absence of local codes, with 
the National Electrical Code (ANSI/NFPA 70) or the CSA 
C22.1 Electrical Code. Use the grounding lug provided in 
the control box for grounding the unit.

Summary of Contents for MB7BM Series

Page 1: ...nt role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in ser...

Page 2: ...ing 11 Turning the Blower Off 11 Blower Configurations 11 Selecting minimum Electric Heat Airflow 11 Determining Nominal System Capacity 11 3 speed Units 11 High Efficiency Units 12 Selecting Basic He...

Page 3: ...ment Do not store any of the following on or in contact with the unit Rags brooms vacuum cleaners or other cleaning tools spray or aerosol cans soap powders bleaches waxes cleaning compounds plastics...

Page 4: ...dbesetintopositionbeforerouting the refrigerant tubing Operation of an Air Handler During Construction CAUTION Failure to follow these instructions will void the factory warranty and may significantly...

Page 5: ...tments must be constructed and installed in accordance with NFPA and SMACNA construction standards Consult with local codes for special requirements For best sound performance be sure to install all t...

Page 6: ...nts air handler INSTALLATION The MB7 Series air handler is shipped ready for vertical upflow installation and is approved for attic basement alcove closetorcrawlspaceinstallationwithzeroclearance to c...

Page 7: ...ne gasket tape to the top of the air handler NOTE The blowers flanged surface is now beneath the air handler and will connect with the supply air duct 4 Carefully place the cased coil on top of the mo...

Page 8: ...ion of the unit in a suspended horizontal application is shown in Figure 5 When mating the blower and coil for horizontal left or right applications reference the upflow instructions on page 6 Make su...

Page 9: ...gures 14 16 Use only copper wire for the line voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Aluminum suppl...

Page 10: ...erkitforyour unit by referring to the list below or the units rating label A Size Cabinet 15Kw max B Size Cabinet 20Kw max C Size Cabinet 20Kw max 1 Connect the 2 wire plug of the air handler to the m...

Page 11: ...Disconnect all electrical power to the unit and remove the upper door 2 Remove the black and red wires from the blower motor jumping terminal Discard the blower motor jumping terminal Startup Adjustme...

Page 12: ...ch nominal system capacity When operating in the heat pump mode a higher basic airflow setting will increase the energy efficiency and capacitybutwillalsodecreasethesupplyairtemperature For maximum ca...

Page 13: ...eate excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life It is recommended that the blower compartment be cleaned of dirt or lint that may ha...

Page 14: ...mension B Dimension C A 12 3 4 24 3 4 14 1 4 B 12 3 4 24 3 4 17 1 2 C 18 1 4 27 1 2 21 B A 12 7 8 3 4 TYP 1 3 4 1 7 8 K O 3 1 4 1 1 4 C 22 1 1 7 8 3 1 2 5 1 2 2 5 8 1 1 8 K O TYP 1 1 4 2 7 8 TOP VIEW...

Page 15: ...ount Kit Blower Motor Blower Wheel Blower Housing Transformer Control Board Coil Assembly Outlet Heater Box Lower Front Bracket Blower Door Motor Control Board Rear Bracket Front Joining Bracket Figur...

Page 16: ...0 845 780 705 610 530 Corrected ESP1 0 08 0 19 0 31 0 42 0 54 0 65 0 76 Med 1335 1290 1235 1175 1100 1015 925 805 Corrected ESP1 0 10 0 22 0 34 0 46 0 59 0 71 High 1470 1425 1360 1300 1225 1135 1050 9...

Page 17: ...685 0 1 1 0 1095 1040 995 950 900 850 805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 12...

Page 18: ...0 1 0 650 0 0 1 1 2 TON 1300 0 0 1 1 4 TON 700 0 1 0 0 1350 0 1 0 0 750 0 1 0 1 1400 0 1 0 1 800 0 1 1 0 2 5 TON 1450 0 1 1 0 850 0 1 1 1 1500 0 1 1 1 875 1 0 0 0 1550 1 0 0 0 950 1 0 0 1 1600 1 0 0 1...

Page 19: ...0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 N A 1 0 1 1 1 850 1 30 N A 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400 1 1 1...

Page 20: ...1 7 68 1 50 25 70 020H XX 53 1 103 1 60 110 46 5 43 3 89 8 50 45 90 C 2000CFM None 5 5 15 15 5 5 15 15 005H XX 30 30 35 35 26 7 26 7 30 30 008H XX 44 6 44 6 45 45 39 3 39 3 40 40 010H XX 55 55 60 60 4...

Page 21: ...Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with Variable Speed Air Handler Typical 2 Stage Heat Pump with Variable Speed Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air C...

Page 22: ...age Control Board MB7BM Models Figure 11 Two Stage Control Board MB7EM VM Models LED 1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2...

Page 23: ...W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B GREEN RED STATUS NOT USED TEST PORT BLOWER MOTOR R C Y1 TWIN DEHUM...

Page 24: ...PLUG HOUSING WHEN HEATER KIT NOT INSTALLED BLACK RED WHITE BROWN BROWN BLACK WHITE RED GRAY YELLOW WHITE GREEN GRAY RED NOTES 1 The blower motor speed tap connection may not be as shown See the Insta...

Page 25: ...2 3 4 5 6 9 PIN HOUSING 9 PIN PLUG 6 PIN PLUG HARNESS BLACK WHITE GRAY RED BLACK RED WHITE BLACK MOTOR 6 PIN PLUG HARNESS WHITE BLACK BLUE GREEN YELLOW ORANGE RED BROWN BLUE GREEN ORANGE RED BROWN YE...

Page 26: ...R BLACK WHITE 6 PIN PLUG 6 PIN PLUG BLACK WHITE BLACK WHITE GRAY RED BLACK HARNESS HARNESS GREEN BROWN RED ORANGE YELLOW GREEN BLUE BROWN RED ORANGE YELLOW GREEN BLUE RED CUT WIRES TO REMOVE PLUG HOU...

Page 27: ...delay W Y AUX HEAT On 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on instantly Cool blower on after 3 second delay Stage 2 Heat on after 5 seconds delay 15 KW...

Page 28: ...ly Blower off after 15 second delay W1 W2 EHEAT On 5 KW Stage 1 Heat on instantly Heat blower on after 3 second delay 10 KW Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 2 Heat o...

Page 29: ...off instantly Heat blower turns off after 40 second delay W1 W2 Y Y2 AUX HEAT On 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on instantly Cool blower on afte...

Page 30: ...30...

Page 31: ...31...

Page 32: ...Replaces 7091750 ATTENTION INSTALLERS It is your responsibility to know this product better than your customer This includes being able to install the product according to strict safety guidelines and...

Reviews: