Nordyne M1B 066 Installation Instructions Manual Download Page 26

26

TROUBLESHOOTING

Direct Ignition Furnaces (M1M Models) & 
Gas Gun Furnaces (M1B Models)

High Gas Bills

a.  Verify the proper orifi ce is being used.
b. Check the return air system. Is it clear and free of 

blockage?

c.  Check the furnace fi lter. Is it clean or need replacing?
d. Verify the home is insulated, windows and doors fi t 

tightly, and there are no leaks in the heating duct system.

e.  Check the room thermostat. Is the setting higher than 

necessary? Low humidity requires higher temperatures 
for the same level of comfort. Check for proper humidity 
level in the home.

Burner Motor won’t Run - T-stat Calls for Heat

1.  Check the electrical supply to the furnace.
2.  Verify the furnace furnace On-Off switch is in the ON 

position.

3.  Defective thermostat circuit - white and red thermostat 

low voltage leads (M1/M5M, M1/M5B models). If the 
burner motor or combustion fan runs, check:
• Thermostat connections
• Thermostat

4.  No voltage to control module - determine if 24 volts (or 

120 volts) is available to the control module. If voltage 
is not available check for:

•  Blown fuse, defective transformer, circuit breaker, 

no electrical supply.

•  Limit switch open.
•  Loose connections.

Combustion Blower Runs - No Flame

1.  Defective centrifugal switch (M1B Model).

•  Check the operation of centrifugal switch by removing 

end bell of the burner motor.

•  Clean contacts of motor.
•  If the contacts are closed, replace the motor.

2.  Defective pressure switch (M1M - 077 & 090 Models) 

- check air tube and electrical connections.

3. Burner in purge mode - allow 75 seconds for fl ame 

establishing period.

4.  Check for proper electrical connections at purge timer, 

control box, or gas valve.

5.  Check for gas supply - gas line valve on, control lever 

on.

120 VAC Is Available At AMP Plug -
Ignitor Does Not Heat Up

1.  Disconnect power to the furnace.
2.  Disconnect AMP plug to the ignitor, and check ignitor 

resistance with an ohm meter. Set on RX1 scale.
•  Normal reading should be 40 - 75 ohms.
• If above or below this rating at room temperature 

change ignitor.

3.  Check for continuity from ignitor receptacle to burner.

Control Module is Powered - Ignitor won’t Heat 
Up

1.  Disconnect ignitor leads at AMP receptacle and check 

for 120 volts at the plug during ignition sequence.

2.  Replace ignition control if 120 volts is not available at 

AMP plug during ignition sequence.

Main Flame Ignites - Burner Locks Out

•  Ignition control is not properly grounded.
•  Defective ignition control.
•  Improper polarity of 120 volt power supply.
•  Ignitor has hairline crack.
•  Improper gas pressure or burner air adjustment is not 

allowing fl ame to contact ignitor tip for fl ame rectifi cation.

•  Misaligned ignitor does not allow fl ame to contact ignitor 

tip for fl ame rectifi cation.

Burner Short Cycling - Thermostat Calls
for Heat, Limit Switches Closed

•  Check for polarity.
• Check ground.
• Check fl ue.
•  Check combustion air.
•  Check gas pressure.
• Check orifi ce.
•  Check the position of ignitor, a normal reading should 

be 40-75 ohms.

24 Volts Supplied To Gas Valve During Ignition 
- No Main Gas Flow

•  Gas valve may be defective. Replace if necessary.
•  Gas piping may be plugged. Check for adequate gas 

supply to gas valve at union. 

Burner Operates - Insuffi cient Heat

• Check thermostat for proper setting and location. 

Thermostat should not be located where it will be affected 
by another heat source.

•  Check for clean fi lter and proper air fl ow.
•  Check burner for proper gas fi ring rate.
•  Be sure unit is not undersized for its thermal load.
• Check thermostat anticipator. The nominal setting is 

0.4.

Burner Flame Without Motor Running

• Gas valve stuck open, check gas valve for proper 

operation (replace if necessary) and inspect heat 
exchanger.

• Check for 115 volts to the combustion blower motor; 

replace if necessary.

•  If no power to combustion blower then check wiring and 

control module; replace if necessary.

Circulation Air Blower Will Not Operate
Even Though The Burner Does Operate

• Check thermostat 

G

 connection.

•  Check wiring to motor.
•  Check for a defective motor.

Summary of Contents for M1B 066

Page 1: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit...

Page 2: ...pling 20 STARTUP ADJUSTMENTS 21 Operating Instructions Direct Ignition M1M 22 How to Shut Off Gas Direct Ignition 22 Operating Instructions Oil Gun M5S 22 Operating Instructions Gas Gun M1B 22 How to...

Page 3: ...the current revision of the National Fuel Gas Code NFPA54 ANSIZ223 1 ortheNaturalGasandPropane Installation Code CAN CGA B149 1 CE g n rateur d air chaud doit tre install conform ment aux instructions...

Page 4: ...equipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used and if applicable a product approved air intake must be used Installation...

Page 5: ...he overall size of the furnace and the installation clearances listed in Table 1 and in Figure 4 page 6 Alcove installations minimum 18 clearance at front of furnace shall be provided for future servi...

Page 6: ...e 0 Side Clearance to Furnace Cabinet Provide min 235 sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide...

Page 7: ...n the floor or ceiling registers serving the return air duct system must be at least 235 in2 At least one register should be located where it is not likely to be covered by carpeting boxes and other o...

Page 8: ...ellineholesmustbecarefullylocated to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 9 For round ducts see Figure 7 1 Measure 10 from the rear wall or alco...

Page 9: ...es X FLOOR OPENING FLOOR CAVITY SUPPLY AIR DUCT Figure 9 Floor Cavity Alternate Attachment Method The standard duct connector is designed for use on ducts 12 in width However if there is insufficient...

Page 10: ...urn air distributionsystemasshowninFigures14 15 page11 1 Remove furnace outer door s and bottom fuel line knockout 2 Placefurnaceontoductconnectorandcenterwithfloor opening 3 Slideontomountingplate Bo...

Page 11: ...in the minimum and maximum range of the Roof Jack listed in Table 4 Application Notes FAW FAWT SAW and SAWT Series Roof Jacks with a 5 diameter inner vent pipe may be used with all models of M1 Series...

Page 12: ...ve along the center line of furnace and floor opening See Figure 19 2 Cut ceiling and roof holes Ceiling 8 3 4 222 mm diameter Roof 9 3 8 238 mm diameter Installing The Roof Jack 1 Apply caulking comp...

Page 13: ...inent location inside manufactured home until on site installation 4 The four warning tags supplied must be installed as follows To weather cap To fuel line connection point Gas or furnace burner Oil...

Page 14: ...operly connected as shown in Figure 25 Route all electrical wiring to the left side of the furnace See Figure 24 For installation of A Cabinet furnaces allow sufficient slack in the wiring if an optio...

Page 15: ...above the control panel 2 Connectthethermostatwirestothefurnacelowvoltage pigtails see Figure 25 3 Connect low voltage circuit to the wall thermostat 4 A hole may be made in the furnace cabinet to eas...

Page 16: ...or property damage This furnace may be installed with left right or bottom gas entry When connecting the gas supply provide clearance between the gas supply line and the entry hole in the furnace casi...

Page 17: ...t pressure Pressure is reduced to 3 1 2 W C by the pressure regulator in the gas valve The maximum inlet pressure for the valve is 7 W C and the minimum inlet pressure is 4 5 W C For L P gas pressure...

Page 18: ...o Line system should only be used if vertical lift exceeds 8 feet 1 Install the oil feed line as outlined in steps 1 6 below 2 Install the oil pump bypass plug in the bottom return port 3 Route the re...

Page 19: ...P gas Use the following procedure for gas conversion of the burner Atmospheric Direct Ignition Furnaces 1 Follow the instructions How to Shut Off Gas page 22 2 Disconnect the gas pipe union and the el...

Page 20: ...nace installation A flue gas sample may be taken from the heat exchanger which is located behind the hole of the top front of blower compartment 1 Turn off all electric power to the appliance 2 Remove...

Page 21: ...sonne ne r pond appeler le service des incendies AVERTISSEMENT STARTUP ADJUSTMENTS PLEASE READ ALL SAFETY INFORMATION BEFORE LIGHTING THE FURNACE WARNING Before placing the furnace in service it must...

Page 22: ...est setting 2 Turn off all electric power to the appliance before servicing unit 3 Set the furnace On Off Switch to OFF Honeywell Figure 30 Turn gas control knob clockwise to OFF Robertshaw Figure 31...

Page 23: ...mbustion Air CAUTION Combustionairadjustmentmustbemadeonly by a qualified technician Improper air adjust ment may cause unsafe operation explosion and or fire asphyxiation If the input to the furnace...

Page 24: ...the gas valve 3 Aftera45secondpurge theignitorisenergizedfora30 second warm up period After warm up the gas valve opens NOTE The time for ignition is approximately 6 seconds after which the gas valve...

Page 25: ...ch must be set in the ON position for the furnace to operate If blower operation is not desired the furnace On Off switch may be set in the OFF position to cut the electrical power to the furnace See...

Page 26: ...RX1 scale Normal reading should be 40 75 ohms If above or below this rating at room temperature change ignitor 3 Check for continuity from ignitor receptacle to burner Control Module is Powered Ignito...

Page 27: ...attheigniterterminals andthere is no ignition the igniter is likely defective and needs to be replaced 3 If the stops flashing burner turns on but the control locks out again check the cad cell If the...

Page 28: ...L1 neutral reversed or L1 voltage not present on L1 Flame Status A Yellow LED labeled Flame is provided to indicate flame status When flame is sensed the flame LED is lit If flame sense is weak yello...

Page 29: ...roper furnace operation Excessive ice formation could restrict the combustion air supply to the burner causing inefficient burner operation If excessive ice has formed on the air inlet or exhaust port...

Page 30: ...26 43 0 3 x x 1 4 3 M1BC 066 66 53 26 43 0 3 x x 1 2 4 M1BB 086 86 68 18 37 0 3 x x 1 4 3 M1BC 086 86 68 18 37 0 3 x x 1 2 4 M5SB 066 66 56 0 3 50 Gph x Burner Model AF 10 1 4 3 M5SC 066 66 56 0 3 50...

Page 31: ...45 4 41 8 40 1 38 5 37 0 35 5 34 1 32 7 31 4 30 2 M1M 070 Orifice Size Nat Gas 24 25 26 27 27 28 28 29 29 30 Orifice Size LP 42 42 43 43 43 44 44 45 46 47 Output MBTUH 56 7 52 3 50 2 48 2 46 2 44 4 42...

Page 32: ...84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 3...

Page 33: ...is required for M1MA models and M1MB 090 A C Heating Speeds Refer to Table 12 A C Blower Selection in the manual BLACK WHITE WHITE BLACK BLACK GREEN RED GRAY WHITE RED LO BLACK HIGH BLUE MED HI ORANGE...

Page 34: ...RD TERMINAL BUSHING BUSHING BUSHING BUSHING W C IGNITER FROM C WIRE GRAY BLACK BLACK FROM W WIRE BLUE GAS GUN BURNER GV PSO FSG C IND L 1 HSI HSIG L 2 W PSI FSI CONTROL MODULE IGNITER L2 MOTOR L2 L2 L...

Page 35: ...35...

Page 36: ...ATE UNIT MODEL UNIT SERIAL Minimum clearances per Table 1 page 6 YES NO Has the owner s information been reviewed with the home owner YES NO Has the literature package been left near the furnace YES N...

Reviews: