3-14
Part ID Cable Connections
The PD1 cable plugs into the receptacle on the back of the console or bottom of the
pedestal. Use a liquid-tight cord grip to bring the cable into the PEJB.
Connect the cable to the terminal block in the PEJB, using Table 3-3.
Table 3-3 Part ID Cable PD1 Pinouts, Wire Colors, and Functions
Pin Number
Wire Color
Function
1
Black
Zone 1
2
Brown
Zone 2
3
Red
Zone 3
4
Orange
Zone 4
5
Yellow
Zone 5
6
Green
Zone 6
7
Blue
Zone 7
8
Violet
Zone 8
9
Gray
Part ID bit 1
10
White
Part ID bit 2
11
White/Black
Part ID bit 3
12
White/Brown
Part ID bit 4
13
White/Red
Part ID bit 5
14
White/Orange
Part ID bit 6
15
White/Yellow
Part ID bit 7
16
White/Green
Part ID bit 8
17
White/Blue
Trigger Bank 0
18
White/Violet
Trigger Bank 1
19
White/Gray
Trigger Select
20
White/Black/Brown
Encoder A
21
White/Black/Orange
spare
22
White/Black/Yellow
spare
23
White/Black/Green
spare
24
White/Black/Red
+24 Vdc
N/C
White/Black/Blue
−−
Using Trigger Banks
For information on how to use Trigger Banks, see
Using Zone Inputs for Direct Triggering
in the iControl 2 Software Manual. The customer must bring additional wiring into the
junction box and wire them to terminals 17, 18, and 19. Note that the factory default
configuration for these inputs is sinking. If a sourcing configuration is required, refer to
Switching Inputs to Sourcing
on the following page.
Summary of Contents for Encore HD iControl 2
Page 6: ...2022 Nordson Corporation 1609758 04 iv Table of Contents...
Page 8: ...2022 Nordson Corporation 1609758 04 ii Change Record...
Page 84: ...2022 Nordson Corporation 1609758 04 4 34 Troubleshooting...
Page 102: ...2022 Nordson Corporation 1609758 04 6 12 Parts...
Page 104: ...2022 Nordson Corporation 1609758 04 7 2 Drawings...
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 113: ......
Page 114: ......