© 2022 Nordson Corporation
3-6
iControl Console CAN Address and Termination Settings
The backplane address dipswitches are set at the factory:
1. Network terminator switch SW1-3 is set to CONTINUOUS for both backplanes.
2.
Network address switches SW1-1 and 2 are set to Spray Guns 1−16 for the lower
backplane and to 17−32 for the upper backplane (if used).
SW1-1
Closed
Closed
SW1-2
Closed
Open
SW1-3
Closed: End
Open: Continuous
Guns 1-16
Guns 17-32
Slide switch
Closed
(on)
Open
Closed
(top on)
Open
(bottom in)
Rocker switch
Upper Backplane
Spray Guns 17-32
Lower Backplane
Spray Guns 1-16
SW1
SW1
Open
Open
1
2
3
1
2
3
Figure 3-4 System Interconnect Cable Connections
Manual Spray Gun Controller Addresses
The manual spray gun controller addresses are set through software. Each controller
must have a unique address. Up to four manual spray guns can be included in a system.
Refer to the
Prodigy Manual Spray Gun Controller
manual for instructions.
NOTE:
For each HDLV pump choosen to supply powder to a manual spray gun, the
operator must enter the pump calibration numbers into the spray gun controller. Refer to
the
Prodigy Manual Spray Gun Controller
manual for instructions.
Manual Spray Gun Controller Termination
Manual spray gun controllers are shipped with their CAN termination switch set to ON.
For each manual spray gun controller in the system:
1. Open the controller enclosure and locate SW1 on the controller interface board.
2. Set the TERM switch on SW1 to OFF.
Summary of Contents for Encore HD iControl 2
Page 6: ...2022 Nordson Corporation 1609758 04 iv Table of Contents...
Page 8: ...2022 Nordson Corporation 1609758 04 ii Change Record...
Page 84: ...2022 Nordson Corporation 1609758 04 4 34 Troubleshooting...
Page 102: ...2022 Nordson Corporation 1609758 04 6 12 Parts...
Page 104: ...2022 Nordson Corporation 1609758 04 7 2 Drawings...
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 113: ......
Page 114: ......