Summary of Contents for AT 3000 D

Page 1: ...Operating Instructions Steam bath Generators 2401897 EN Nordmann AT 3000 D NORDMANN E N G I N E E R I N G NORDMANN E N G I N E E R I N G Dampfluftbefeuchter econoVap NORDMANN E N G I N E E R I N G...

Page 2: ...eam hose 6 1 4 Perfume injection 6 2 Water connections 2 1 Quality of the water 7 2 2 Water intake and drainage 7 3 Electrical connections 3 1 Safety instructions 9 3 2 Control voltage 9 3 3 Heating v...

Page 3: ...bserve all national and local regulations Proper use The AT 3000 D steam bath generators are intended solely for indirect via a steam distribution pipe in a ventilation duct or direct with either a se...

Page 4: ...22 1 x 22 12 18 5 15 1 470 645 305 1 x 35 1 x 22 17 32 5 23 1 470 645 305 1 x 35 1 x 22 18 33 5 32 1 525 715 360 1 x 35 1 x 22 28 53 5 45 1 525 715 360 2 x 35 1 x 22 29 54 5 4 Breite Tiefe H he 1 Ins...

Page 5: ...n anti clockwise direction the door to the water componentry or the electrics then opens To close simply push back into place no screwing down is necessary Positioning the steam bath generator Ensure...

Page 6: ...utilized NORDMANN cannot be held responsible for any damage that may occur When laying the steam hose in pipes cable ducts etc you must verify their resistance to high temperature min 100 C All insula...

Page 7: ...ery hard without the need for prior treatment However for fairly hard water and above we recommend the use of the SC System NORDMANN s self cleaning system since this greatly reduces the amount of mai...

Page 8: ...the possibility of performing cleaning and maintenance The drainage pipe should have a decline to the drainage system of at least 5 A fine filter should be fitted at the water intake to the steam bat...

Page 9: ...ype of unit Each unit is supplied with the appropriate wiring diagram External fuses per phase A 3 2 Control voltage The standard control voltage is 220 240 V A fuse F1 6A and a spare fuse located in...

Page 10: ...262 32xx 45xx 4 10 4 10 6 16 10 35 10 16 2 5 4 2 5 2 x 2 5 2 5 2 x 4 2 x 2 5 2 x 4 2 x 2 5 2 x 4 3 3 Heating voltage The cross section of the electrical wires and the minimum fuse size should be chose...

Page 11: ...o this ability to set the optimum water concentration in the steam cylinder the smallest of adjustments to the water level can effect a change in the steam output Therefore the unit reacts quickly and...

Page 12: ...s reduced The serviceable life of a steam cylinder is dependent on both the quality of the water supply and the unit s actual operating hours Lifetime of a steam cylinder at 100 steam output A regular...

Page 13: ...heated up the production of steam begins During the start up phase or after a new replacement cylinder has been fitted the maximum water level or Niveau max can be attained When Niveau max has been re...

Page 14: ...ed steam production is switched on or off The red LED lights up upon switching on and keeps dark upon switching off T2 Key for the switching on or off of the cabin light The red LED lights up upon swi...

Page 15: ...een pressed the exhaust fan that is connected to terminals 45 and 46 is switched on automatically Ex factory a pre and post running time of 2 and 15 minutes respectively have been set The key SET enab...

Page 16: ...back into operation by means of the reset procedure cf Item 4 7 U 3 The steam bath generator fills continuously Either there is no heating phase or no water in the cylinder due to the water supply ha...

Page 17: ...eam bath generator can still be run for some time before you need to replace the steam cylinder Procedure for replacing the steam cylinder Select service level with key T4 Open the drainage valve in t...

Page 18: ...switched off The electronics unit comprises a processor pcb printed circuit board and a display pcb All pcbs have plug in connections which facilitates their replacement 5 4 Taking the steam bath gene...

Page 19: ...tight Check that the hoses are still in good condition Inspect and clean the inlet and outlet valves If worn or covered in scale deposits replace the valves Check the drainage cup and if necessary cle...

Page 20: ...roduce steam for all other functions steam production is interrupted You can return from function to function i S und SE by pressing SET Starting the service program Key T4 Select the servicing level...

Page 21: ...perfume is not energized r2 1 Relay perfume cuts in r3 0 Relay exhaust fan is not energized r3 1 Relay exhaust fan cuts in End End of the service program All components are in resting position If key...

Page 22: ...closed etc The filter or the nozzle in the inlet valve is blocked or damaged The cylinder needs replacing The steam bath generator is too small for the job The current transformer is either defective...

Page 23: ...umber of phases 1 3 1 3 3 3 3 Heating current A 13 0 7 5 26 5 15 3 28 6 43 9 61 0 Steam output kg h 4 4 8 8 15 23 32 45 Capacity range kg h steam 2 4 2 4 4 8 4 8 7 5 15 11 5 23 16 32 22 5 45 Nominal p...

Page 24: ...NORDMANN E N G I N E E R I N G NORDMAN E N G I N E E R I Dampfluftbefeuchter econ Reg No 40002 2 Manufacturer Nordmann Engineering Ltd www nordmann engineering com info nordmann engineering com...