5.  INSTALLING DRAIN PIPES

•  Install the drain pipe with downward gradient (1/100 to 1/50) 

and so there are no rises or traps in the pipe. Unsmooth 
draining caused by accumulated water 

fl

 ow in the pipe may 

cause clogged drain.

•  Use general hard polyvinyl chloride pipe (VP25) [outside 

diameter 32 mm].

•  When the pipe is long, install supporters.

•  Do not perform air bleeding. Drainage may be blown out.

•  Always heat insulate the indoor side of the drain pipe.

•  If it is impossible to have suf

fi

 cient gradient of pipe, perform 

drain lift-up.

Pipe size

Drain pipe

VP25 (O.D. 32 mm)

Hanging 

fi

 ttings

1.5 to 2 m

VP25 (O.D. 32 mm)

Downward gradient 1/100 to 1/50

Rise

PROHIBITED:

Trap

Air bleeding

When lifting up drain:

•  Height of inclined pipe should be less than 850 mm from the 

ceiling. A rise dimension over this range will cause leakage.

•  Lift up the pipe vertically at the position of 300 mm or less from 

the unit.

300 mm or less

VP25 (O.D. 32 mm) 

local arrangement

850 mm or less

Horizontal or 

upward gradient

Downward gradient 

1/100 to 1/50

VP30 (O.D. 38 mm) or more 

Downward gradient 1/100 to 1/50

850 mm or less

 

WARNING

• Do not insert the drain piping into the sewer where sulfurous 

gas occurs. (Heat exchange erosion may occur)

• Insulate the parts properly so that water will not drip from the 

connection parts.

• Check for proper drainage after the construction by using the 

visible portion of transparent drain port and the drain piping 

fi

 nal outlet on the body.

 

CAUTION

• Do not apply adhesive agent on the drain port of the body. 

(Use the attached drain hose and connect the drain piping)

Working procedure

(1) Install the attached drain hose to the drain port of the body. 

Install the hose band from the top of the hose within the 
graphic display area. Secure 

fi

 rmly with the hose band. 

(2) Use vinyl adhesive agent to glue the drain piping (PVC pipe 

VP25) which is prepared on site or elbow socket.

 

(Apply color adhesive agent evenly until the gauge line and 
seal)

(3) Check the drainage. (See separate diagram)

(4) Install the heat insulation.

(5) Use the attached heat insulation to insulate the drain port 

and band parts of the body.

Install the knob 

faces upward 

(Accessories)

Attached drain hose 

heat insulation 

(Accessories)

Locally 

arranged 

vinyl pipe

Attached 

drain hose 

(Accessories)

Attached 

hose band

Attached heat 

insulation

9371022208-02_IM_EN.indd   9

9371022208-02_IM_EN.indd   9

8/31/2012   2:42:12 PM

8/31/2012   2:42:12 PM

Summary of Contents for VRF SYSTEM

Page 1: ...INSTALLATION 4 1 Selecting the pipe material 7 4 2 Pipe requirement 7 4 3 Flare connection pipe connection 7 4 4 Installing heat insulation 8 5 INSTALLING DRAIN PIPES 9 6 ELECTRICAL WIRING 6 1 Electri...

Page 2: ...cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leakage make sure that it does not exceed the concentration limit If...

Page 3: ...or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fall or the unit...

Page 4: ...he figure Strong and durable ceiling 3 000 mm or more H 1 800 mm or more 256 mm or more AUXD18 24 298 mm or more AUXA30 36 45 54 Obstruction 1 000 mm or more Floor 1 500 mm or more H The maximum heigh...

Page 5: ...20 45 mm 20 45 mm 20 45 mm 20 45 mm 130 mm 130 mm 80 mm 699 mm Hanging bolt pitch 950 mm Panel frame 860 910 mm Ceiling opening 840 mm Body frame 200 mm 130 mm 50 mm 50 100 mm 10 mm 40 mm 140 145 mm B...

Page 6: ...of at least 490 N per bolt Hole in anchor Hole in plug Concrete Insert Hanging bolt M10 3 3 3 Body installation 1 Install the attached washer and nut prepared on site onto the hanging bolt 2 Hook the...

Page 7: ...tion Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance...

Page 8: ...gainst the port on the indoor unit and then turn the flare nut by hand Connection pipe Liquid Connection pipe Gas 3 When the flare nut is tightened properly by your hand hold the body side coupling wi...

Page 9: ...wnward gradient 1 100 to 1 50 850 mm or less WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat exchange erosion may occur Insulate the parts properly so that water...

Page 10: ...tch the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the termina...

Page 11: ...acity Recommended cable size mm2 Cable type Remark Power supply cable 2 5 Type245 IEC57 or equivalent 1 50 Hz 198 264 V 2 Cable ground Transmission cable 0 33 LONWORKS compatible cable 22 AWG LEVEL 4...

Page 12: ...the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Strip 10 mm Sleeve Screw with special washer Screw with special washer Ring terminal Cable Cable Terminal...

Page 13: ...minal board Remote controller connecting port Cure the wiring connecting port and remote controller connecting port with paste or heat insulation so that insects or dust will not enter the unit Wiring...

Page 14: ...evice 2 Load resistance Load resistance 1 DC power supply 12 24V connected unit a a P C B CN6 b 1 Make the power supply DC12 to 24V Select a power supply capacity with an ample surplus for the connect...

Page 15: ...ggered indoor unit stops and Start Stop operation by a remote controller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoo...

Page 16: ...or address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote contr...

Page 17: ...Rotary Switch Setting Refrigerant circuit REF AD SW Indoor unit IU AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9...

Page 18: ...etting 02 01 Adjust 1 02 Adjust 2 Hot air tem perature trigger 31 00 Default Adjust the hot air trigger temperature To lower the trigger temperature by 6 degrees C use setting 01 To lower the trigger...

Page 19: ...Installation Manual for the outdoor unit if the PCB for the outdoor unit is to be used for the test operation 9 2 Test operation using Remote Controller Refer to the Installation Manual for the remote...

Page 20: ...ller Error CODE Error contents OPERATION lamp green TIMER lamp orange FILTER lamp red 1 2 Remote controller communication error 1 4 Anomalous network communications 1 6 Parallel communication error 3...

Reviews: