Problem

Possible errors

Action

There is smoke emission during igni-
tion.

The fan is turned off.

Press ( start new firing ).

Smoke is seeping through the doors.

A gasket is leaking.

Adjust the doors.

The fan will not start.

An electronics malfunction.
Thermal protection switched on.

Contact the factory.

The fan will not stop.

The boiler has not had a flue gas 
temperature higher than 100°C during 
firing. 

The boiler will stop within 1 hour.

Tar in the convection section.

A sooty loading compartment.
The Lambda sensor needs cleaning.
Damper motor defective.

Clean the boiler.
Clean the Lambda sensor.
Contact the factory.

Little or no heat is transferred to the 
accumulator tank.

Probably air in the system.
Poor quality wood.

Fill the system thoroughly.
Change to dryer wood, or chop the 
wood into smaller pieces.

The boiler has a low output and is 
sluggish.

Moist wood or too little draught in the 
chimney.
The boiler may need to be cleaned.

Try drier wood.
Clean the boiler and fan.

The charge pump creaks or thumps, 
and sometimes stops pumping.

Probably air in the system.
Low system pressure.

Follow the Laddomat instructions.
Increase the pressure.

The pressure drops in the system.

There is a leak in the system. The wa-
ter in the vessel has evaporated.
Wrong first pressure in the pressure 
vessel.

Fill up with water and ventilate.
Adjust the pressure.

The CO ² level is abnormally high.

The lift dampers have shifted.

Adjust the dampers.

The CO ² level is abnormally low.

The lift dampers have shifted, the fire is 
extinguished.

Adjust the dampers, check the fire.

The air dampers do not start regulat-
ing.

Flue gas temperature is below 100°C, 
and the fire is extinguished. Deficient 
flue gas sensor.

Check the fire. 

Noise from the fan.

The cooling wing scrapes against the 
boiler. The bearings in the fan have run 
out.

Check the cooling wing on the shaft 
between the motor and fan. Contact 
your installer.

The display is blinking.

Low or high voltage to the circuit board. Adjust the converter.

High flue gas temperature.

Soot in the tubes.

Clean the boiler.

▀  

Troubleshooting

Converter

Under the middle roof of the boiler there is a converter which 

supplies the circuit boards with power. The power level is preset 

at the factory, but sometimes an adjustment may be needed. If so, 

the light flashes on the display. Features such as fan can also be 

affected at low voltage. Adjust the brightness using the knob (1.) 

located on the converter clockwise 1-3 mm. If the LED (2.) is not lit, 

the converter is probably not functioning.

▀  

Converter

Summary of Contents for EFFECTA LAMBDA 35

Page 1: ...INSTALLATION MAINTENANCE SERVICE ASSEMBLY EFFECTA LAMBDA 35 Rev EA 012 05 30...

Page 2: ...a user of an ecolabeled product you will contribute to a better environment around you Wood system In order to fulfil the Nordic Ecolabel the accumulator tank volume must be at least 2 000 litres Thi...

Page 3: ...unction Laddomat 21 60 12 Sleeve placement Accumulator BBS 13 First firing 14 Firing cycle 14 Menus 15 Electrical installation 16 Cleaning and service 17 Cleaning 18 Lever cleaning 19 Adjusting the do...

Page 4: ...nd serial number Otherwise in the case of a complaint the HVAC industry s current regulations apply Warranty conditions The warranty requires that Installation of the product and the heating system ha...

Page 5: ...environmental value and thus the best efficiency Normally the preset values do not need to be adjusted for different wood types and humidity levels System description Effecta Lambda has a recommended...

Page 6: ...The boiler room or boiler house must be equipped with a fresh air intake with the minimum dimensions 150 x 150 5 mm or with a sufficiently large free sectional area to avoid low pressure in the boile...

Page 7: ...n vessel can normally withstand a pressure of 6 bar Maximum operating temperature is 99 C The volume of a pressure vessel is 10 12 litres depending on the system s overall volume An open vessel must c...

Page 8: ...ator tank 35 mm pipes are recommended Remember to insulate the pipes between the accumulators to avoid large losses from the system Accumulator tank Effecta Lambda must always work with some sort of h...

Page 9: ...ould be mixed with the largest at the top of the loading compartment Do not fire with only finely chopped wood or conversely if you heat only using small blocks of wood the boiler may end up at a high...

Page 10: ...2 Incoming pipe 3 Soot door 3 Wing nut for detaching fan 3 Smoke connection 4 Air intake 4 Splice connector fan 4 Cover plate for soot door 5 Damper motors behind plate 5 Fan 5 Sensor boiler temp 6 H...

Page 11: ...et tickness firebox Firebox volume Firebox depth Power fan Power Max operating temp Firebox opening Rec tankvolume 600 mm 1260 mm 1280 mm 350 kg 1 5 bar 150x150x630 mm 140 mm 1260 mm 90 liter 500 mm 1...

Page 12: ...tor tank Boiler water return temp is normally about 70 C At 90 C from the boiler the Laddo mat normally gives 66 C back to the boiler 3 Final phase When the ac cumulator tank is fully charged hot wate...

Page 13: ...se www effecta se 010 05 22 V50 05 67 E A EXPLANATION 1 SWEEP 1500 X 750 MM 2 1 1 4 70 MM CHARGE 3 1 2 45 MM THERMOMETER 4 1 2 45 MM SENSOR SOLAR 5 1 1 4 70 MM DOCKAGE FLOW RADIATOR 6 2 ELECTRICAL HEA...

Page 14: ...its own It is therefore not appropriate to stir the in the box during firing If you open the door during firing there is a risk of flashover in the box with poorer function as a result If you burn a l...

Page 15: ...ust be no fire in the boiler Total operating time for the boiler Displays the operating time after cleaning Press to reset C C A Fired with Running on pellets C No No B Yes Yes C C The pump stops when...

Page 16: ...t info effecta se www effecta se 011 12 20 50 12 08 E A L1 N Ground CHARGE PUMP OH 95 C POWER 230 V LAMBDA SENSOR BLACK GREY BLUE WHITE RED BROWN BROWN ORANGE YELLOW RED BROWN ORANGE YELLOW RED M M RE...

Page 17: ...loosen the wing nuts 2 that keep the soot door in place 3 Remove the 7 spirals from the tubes 4 and use the supplied brush to clean the tubes Loading compartment Start by removing the pin 1 located at...

Page 18: ...gs 2 from dust and soot If the fan is not cleaned the boiler will lose power resulting in slower heating and lower combustion Secondary air In the columns where the flame is drawn down there is a meta...

Page 19: ...rbulators and clean the tubes with the supplied brush As an extra option you can equip the Lambda 35 with lever cleaning Lever cleaning makes cleaning easier since you do not need to clean the tubes m...

Page 20: ...pproval of the door locking If the gasket does not seal tightly on the handle side loosen the two bolts 1 that hold the bracket in place Loosen around two turns and slide the latch inwards to tighten...

Page 21: ...lso loosen the two M12 bolts that hold the locking device in place The new lock is sup plied with boiler the existing is not to be used 3 Remove the two M12 bolts that hold the thermal insulation in p...

Page 22: ...RADIATOR RETURN BOILER 19 CUTOFF 21 COLD WATER IN 22 CONNECT TO 23 23 CONNECT TO22 24 HOT WATER OUT 25 EXPANSION VESSEL SOLAR 26 SAFETY GROUP SOLAR 27 PUMP SOLAR 28 EXPANSION VESSEL WITH SAFETY VALVE...

Page 23: ...ol panel Assembly Start by installing the pellets burner in the boiler by first installing the fitting plate 7 with the four wing nuts Then install the swing arm 6 in the fitting plate and outside the...

Page 24: ...ation in the chimney If flue gas levels are so low that condensation is formed you can remove one or more turbulators in order to increase the flue gas temperature Pellets burning Draft damper A draft...

Page 25: ...tom right 7 Afterburner chamber The ceramics tray is installed in the loading compartment The purpose of the ceramics is to separate the different combustion zones in the loading compartment It is imp...

Page 26: ...e that are in the loading compartment They are marked in red in the pictures Centre the lower blocks no 4 and no 5 laterally and fixate them as far forward as possible in the loading compartment Place...

Page 27: ...effecta se 1 Damper motor 5 Set screw 2 Stop pin 6 Motor shaft 3 Air damper 7 Bracket motor 4 Distance 8 Air box Air damper components To access the damper loosen the four screws holding the cover pla...

Page 28: ...ructions Increase the pressure The pressure drops in the system There is a leak in the system The wa ter in the vessel has evaporated Wrong first pressure in the pressure vessel Fill up with water and...

Page 29: ...2 12 2004 Erik Andersson Effecta AB Type plate Modell Model Typ Mod le Milj klass Emission class Emissionsklasse Classe d mission Max drifttryck Max pressure Max Betriebsdruck Pression maximum bar Max...

Page 30: ...30 Effecta AB V stra R gdalsv gen 21 SE 434 99 Kungsbacka 46 0 300 22320 info effecta se...

Page 31: ...31 Effecta AB V stra R gdalsv gen 21 434 99 Kungsbacka 46 0 300 22320 info effecta se...

Page 32: ...32 Effecta AB V stra R gdalsv gen 21 SE 434 99 Kungsbacka 46 0 300 22320 info effecta se...

Reviews: