NORDAC SK 700E Operating Manual
108
Subject to technical alterations
BU 0700 EN
Display
Error
Cause
¾
Remedy
Group
Detail in
P700 / P701
E003
3.0
Inverter overcurrent
I
2
t limit has triggered, e.g. > 1.5 x I
n
for 60s (please also note
P504)
¾
Continuous overload at inverter output
3.1
Overcurrent chopper
I
2
t limit for braking resistance has triggered (please note P555,
P556, P557)
¾
Avoid overcurrent in braking resistance
¾
Switch on flying start P250 for fan drives
3.2
Inverter overcurrent
Derating at f < 2 Hz
E004
4.0
Overcurrent module
Error signal from module (short duration)
¾
Short-circuit or earthing at inverter output
¾
Use external output choke (motor cable is too long)
4.1
Overcurrent pulse switch-off
Pulse switch-off P537 has triggered
¾
FI is overloaded
¾
Check motor data
E005
5.0
Overvoltage DC link
Inverter link voltage is too high
¾
Reduce energy return by means of a braking resistance
¾
Extend braking time (P103)
¾
If necessary, set switch-off mode (P108) with delay (not for
lifting equipment)
¾
Extend emergency stop time (P426)
5.1
Overvoltage mains
Mains voltage is too high
¾
Please check (380V-20% to 480V+10%)
E006
6.0
DC link circuit undervoltage
(charging error) )
Inverter mains / link voltage too low
¾
Check mains voltage (380V-20% to 480V+10%)
6.1
Mains undervoltage
E007
7.0
Mains phase failure
One of the three mains input phases was or is interrupted.
¾
Check mains phases (380V -20% to 480V +10%), possibly too
low?
¾
All three mains phases must be symmetrical.
OFF
Note:
OFF appears in the display when the three mains phases are uniformly reduced, i.e. when
a normal mains switch off occurs during operation.
E008
8.0
EEPROM parameter loss
Error in EEPROM data, EMC interference (see also E020)
Software version of the stored data set not compatible with the
software version of the FI.
Note:
Faulty parameters are automatically reloaded (default
data).
8.1
Invalid inverter type
¾
EEPROM
faulty
8.2
External EEPROM copy error
(ControlBox)
¾
Check ControlBox for correct position.
¾
ControlBox EEPROM faulty (P550 = 1).