4.4.2  Rotary dip code switches for locking time 

With the help of two 10-step rotary dip code 
switches, the user can select the locking time for 
direct direction reversal. Both electronic power 
switches are locked for this time. The switch (P1) is 
used to select the desired time range. The switch 
(P2) allows a fine adjustment in 1/10 steps 
depending on the respective time range selected. 

 

 

 

 

 

 

Step 

10 

P 1 

0-0.2 s  0.2-0.5 s  0.5-1 s 

1-2 s 

2-5 s 

5-10 s 

10-15 s  15-30 s  30-60 s  60-120 s

2 1/10 2/10 3/10 4/10 5/10 6/10 7/10 8/10 9/10 10/10 

 

Example 1: 

Switch P1 on  

Step 1: Time range 0-200 ms 

Switch P2 on  

Step 1 = 20 ms, step 2 = 40 ms, step 3 = 60 ms,..., step 10 = 200 ms 

Example 2: 

Switch P1 on  

Step 5: Time range 2-5 s 

Switch P2 on  

Step 1 = 2.3 s, step 2 = 2.6 s, step 3 = 2.9 s,..., step 0 = 5 s 

Because of the digital processing, the time accuracy is very high and can be exactly set again even if a device 
is replaced. 

 

 

4.4.3  Slide switch for automatic operation 

The slide switch is used to switch the automatic operation on or off. It refers to the behavior of switching on 
again after the motor starter has cut off because of excess temperature of the motor. 

[ON] 

Switching off:

   

OK message (signal OK at low) is removed in case of excess temperature. The motor is 

 

 

 

automatically switched off by SK 160E. 

Switching on again:

  The drive will not start automatically if excess temperature is no longer present.  

The control signal [RUN] must first be switched off and then on again or, alternatively,  
the slide switch is pushed to [OFF] and again to [ON]. 

Attention:

 The drive starts 

immediately! 

[OFF]

 

Switching off:

  

OK message (signal OK at low) is removed in case of excess temperature. The motor is 

  

not switched off by SK 160E. 

Switching on again:

   The OK message is switched high again when the excess temperature is no longer  

 

 

present. The motor would start-up even in case of excess temperature! 

 

Rotary dip code switches 

P1           P2 

Summary of Contents for NORDAC SK 1 E Series

Page 1: ...Manual NORDAC SK 1xxE Series SK 140E Electronic motor starter SK 150E Electronic soft starter SK 160E Electronic reversing starter BU 0100 GB Getriebebau NORD GmbH Co KG...

Page 2: ...60E 18 4 1 Principle of function 18 4 2 Device design 19 4 2 1 SK 160E 1 O C 3D T125 20 4 2 2 SK 160E 1 BSG2 C 3D T125 20 4 2 3 SK 160E 1 x C MS 20 4 2 4 SK 160E AS1 x C MS 20 4 3 Electrical connectio...

Page 3: ...itches are used to set a locking time to protect the installation against damage caused by too quick a reversal The entire power range of the motor starter series is covered by one component size The...

Page 4: ...nection from system power ATTENTION Touching open or exposed terminals can lead to serious injuries or death Always use insulated screw drivers on these terminal panels Make sure that the input voltag...

Page 5: ...thermally monitored through temperature probes acting as overload cutout There are 2 monitoring modes that can be selected by means of a slide switch During automatic operation slide switch set to ON...

Page 6: ...ted fast acting brake rectifier has the designation SK 140E 1 BSG2 Mat No 275101405 With this device design a fast acting brake rectifier has been added to the basic function to directly control a bra...

Page 7: ...ple circuit diagram L L O N 1 O FF 2x L3 L2 L1 24V DC OK RUN GND Bremsspule Kaltleiter oder Temperaturw chter Br cke f r langsames Abschalten Motorklemmen Terminal Function Data Power unit System pote...

Page 8: ...sed to switch the automatic operation on or off This refers to the characteristics of switching on again after the motor starter has cut off because of excess motor temperature ON Switching off OK mes...

Page 9: ...leased o During the entire operation the motor can be thermally monitored through temperature probes PTC resistor or temperature control thereby acting like an overload cut out There are 2 monitoring...

Page 10: ...s the designation SK 150E 1 BSG2 Mat No 275101505 With this device design a fast acting brake rectifier has been added to the basic function to directly control a brake mounted to the motor Consequent...

Page 11: ...ptional M12 plug Principle circuit diagram Terminal Function Data Power unit System potential L1 L2 L3 System connection 4 mm 2 200 380 480 V 50 60 Hz PE Housing ground 4 mm 2 L Bridge L 1 5 mm 2 BR B...

Page 12: ...h maximum torque Motor receives full voltage red LED ON a fault is present green LED Blinking 1 x Pause RUN RIGHT was already active before applying the 24 VDC Blinking 2 x Pause Automatic feature is...

Page 13: ...he principle of the phase control must always be observed by which the variable torque is merely determined by the voltage applied to the motor This does not allow ramp times and torques to be realize...

Page 14: ...he value set at P1 The starting ramp begins here and reaches the maximum moment full voltage at motor after the time set in P2 This time also applies to the run down ramp after removing the release RU...

Page 15: ...1 and 10 but without run down time or engagement time of the brake Dip switches 3 and 4 Time basis for potentiometers P2 and P4 00 This setting is used to determine which time range applies for the po...

Page 16: ...code or switch position 0 0 P3 Run down moment P4 Run down time P1 Start up moment P2 Start up time 0 1 P3 Initial breakaway moment P4 Initial breakaway time P1 Start up Run down moment P2 Start up R...

Page 17: ...peration The slide switch is used to switch the automatic operation on or off It refers to the characteristics of switching on again after the motor starter has cut off because of excess temperature o...

Page 18: ...can be thermally monitored through temperature probes acting like an overload cut out There are 2 monitoring modes that can be selected through a slide switch During automatic operation slide switch s...

Page 19: ...SK 160E AS1 BSG2 MS 275101625 with with with Protection class IP 66 SK 160E 1 O C 3D T125 275151600 without external without without SK 160E 1 BSG2 C 3D T125 275151605 with without without SK 160E 1 O...

Page 20: ...ith a Harting HAN 10E plug connector The configuration in the terminal box is described in Section 5 3 According to the version without or with an integrated brake rectifier the corresponding designat...

Page 21: ...lten Schaltlogik Reversier steuerung RUN RIGHT Kaltleiter oder Temperaturw chter OK GND L3 L2 L1 2x 2x L R Motorklemmen Terminal Function Data Power unit System potential L1 L2 L3 System connection 4...

Page 22: ...ches is active see chapter 0 Permanently on Electronic switch is active ON motor turns red LED ON a fault is present green LED Blinking 1 x Pause RUN RIGHT or RUN LEFT was already active before applyi...

Page 23: ...the time accuracy is very high and can be exactly set again even if a device is replaced 4 4 3 Slide switch for automatic operation The slide switch is used to switch the automatic operation on or of...

Page 24: ...rately installed brake rectifier must be used for supply voltages smaller than 380 V The bridge L allows conversion to a gradual switch off Bridge L open Direct current switch off quick cut in Bridge...

Page 25: ...is mounted in the immediate vicinity of the drive and is not attached directly to the motor The optional Wall mounting kit is required for this and contains the pertaining mounting plate for the respe...

Page 26: ...ed below Type designation SK 140E 1 O MS Mat No 275101410 SK 140E 1 BSG2 MS Mat No 275101415 Harting plug for SK 150E SK 160E The placement of the Harting plug is always on the opposite side of the sc...

Page 27: ...n of the signals RUN and OK This plug in connection facilitates a quick replacement of a drive without problems The signal plug M12 is inserted into the M16 screwed cable gland of the terminal box Pin...

Page 28: ...xxE is included in the table below Apart from the motor activation up to 3 additional sensors can be connected to M12 sockets and read Together they may draw max 130 mA current AS1 Assignment of M12 s...

Page 29: ...at No 275101920 5 5 2 AS interface as additional optional assembly For the SK 160E with the use of the assembly MS Harting HAN 10E plug connector there is alternatively the possibility of leading out...

Page 30: ...monitoring PTC or bimetallic switch assessment applied to system potential Interface 24 VDC M12 plug optional AS Interface optional Electrically separated Control logic digital input against system vo...

Page 31: ...e SK 1xxE SK 140E SK 150E SK 160E g o g1 m n p g1 m n p BG 63 123 192 158 9 153 108 167 8 185 139 BG 71 138 214 167 17 176 0 BG 80 156 236 159 26 169 9 BG 90 176 276 164 30 174 14 BG 100 194 306 175 3...

Page 32: ...Co KG Rudolf Diesel Str 1 22941 Bargteheide For questions regarding the repair please contact Getriebebau NORD GmbH Co KG Telephone 04532 401 515 Telefax 04532 401 555 If a NORDAC SK 1xxE is returned...

Page 33: ...cking time 23 M maintenance 32 motor starter 3 5 O operating modes 13 options 24 P plug M12 27 potentiometer 13 17 power supply 3 protection class 30 R rectifier 24 reversing starter 3 18 rotary dip c...

Page 34: ...om Indonesia Indonesien PT NORD Indonesia Jln Raya Serpong KM 7 Kompleks Rumah Multi Guna Blok D No 1 Pakulonan Serpong Tangerang West Java Indonesia Fon 62 21 5312 2222 Fax 62 21 5312 2288 info nord...

Page 35: ...fo nord hg com Italy Italien NORD Motoriduttori s r l Via Newton 22 IT 40017 San Giovanni in Persiceto BO Fon 39 051 6870 711 Fax 39 051 6870 793 info nord it com Netherlands Niederlande NORD Aandrijv...

Page 36: ...911 67 24 71 NL Nuernberg nord de com Agency Hans Hermann Wohlers Handelsgesellschaft mbH Ellerbuscher Str 179 32584 L hne Telephone 05732 40 72 Telefax 05732 123 18 NL Bielefeld nord de com Sales off...

Reviews: