6 Operating status messages
BU 0180 en-4118
161
SimpleBox - display
The SimpleBox
displays an error with its number and the prefix "E". In addition, the current fault can
be displayed in array element [-01] of parameter (P700). The last error messages are stored in
parameter P701. Further information on inverter status at the time that the error occurs can be found
in parameters P702 to P706 / P799.
If the cause of the error is no longer present, the error display in the SimpleBox flashes and the error
can be acknowledged with the Enter key.
In contrast, warning messages are prefixed with "C" ("Cxxx") and cannot be acknowledged. They
disappear automatically when the reason for them is no longer present or the frequency inverter has
switched to the "Error" state. Display of the message is suppressed if the warning appears during
parameterisation.
The present warning message can be displayed in detail at any time in array element [-02] of
parameter (P700).
The reason for an existing disabled switch on cannot be displayed with the SimpleBox.
ParameterBox display
The ParameterBox displays the messages in plain text.
6.2 Diagnostic LEDs on device
The device generates operating status messages. These messages (warnings, errors, switching
statuses, measurement data) can be displayed with parametrisation tools (
Section 3.1 "Control and
parametrisation options ") (Parameter group
P7xx
).
To a limited extent, the messages are also indicated via the diagnostic and status LEDs.
Diagnostic LEDs
LED
Name
Colour
Description
Status signal
1)
Meaning
DS
red/green Device status
Off
Device not ready for operation
• No control voltage
green on
Device ready for operation
green
flashing
0.5 Hz
Device ready for switching on
4 Hz
Device in switch-on block
red/green
4 Hz
Warning
Alternating 1..25 Hz Degree of overload of switched-on device
green on +
red
flashing
Device not ready for operation
red
flashing
Error, flashing frequency represents error
number
ASi
red/green Status of AS-i
Details (
Section 4.5.4.2 "Displays")
1)
Signal status = specification of LED flashing frequency (switch-on frequency per second), example "red flashes, 2 Hz" = red LED
switches on and off 2x per second
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...