Industrial gear units – Operating and Assembly Instructions
58
B 1050 en-1819
Pos: 125 /Anleitungen/Getri ebe/4. Inbetriebnahme/Interne Kühlanlag e_01_(Inbetri ebnahme) [B1050, B2050] @ 28\mod_1551349755431_388.docx @ 2492796 @ 2 @ 1
4.5 Internal cooling system (Option: CC)
Pos: 126 /Anleitungen/Getri ebe/4. Inbetriebnahme/Interne Kühlanlag e_02_(Inbetri ebnahme) [B1050] @ 31\mod_1552992188351_388.docx @ 2513499 @ @ 1
NOTICE!
Gear unit damage
The gear unit may be damaged by overheating.
• The drive may only be commissioned after the cooling spiral has been connected to the cooling circuit, and
the cooling circuit has been put into operation.
Pos: 127 /Anleitungen/Getri ebe/4. Inbetriebnahme/Interne Kühlanlag e_03_(Inbetri ebnahme) [B1050, B2050] @ 31\mod_1552992003255_388.docx @ 2513423 @ @ 1
The coolant must have a similar thermal capacity as water (specific thermal capacity at 20 °C
c=4.18 kJ/kgK). Industrial water without any air bubbles or sediments is recommended as a coolant.
The hardness of the water must be between 1 dH and 15 dH; the pH value must be between pH 7.4
and pH 9.5. No aggressive liquids may be added to the coolant!
The
coolant pressure
must not exceed
8 bar
. The necessary
quantity of coolant
is
10 l / min.
The
maximum permissible
coolant temperature
is defined during the planning phase and can be found
in
the order data
.
We also recommend fitting a pressure reducer at the coolant inlet to avoid damage due to excessive
pressure.
Pos: 128 /Anleitungen/Getri ebe/4. Inbetriebnahme/Interne Kühlanlag e_04_(Inbetri ebnahme) [B1050] @ 31\mod_1552992011876_388.docx @ 2513461 @ 8 @ 1
If there is a danger of frost the operator should add a suitable anti-freeze solution to the cooling water.
The temperature of the cooling fluid and the cooling fluid flow rate must be monitored and ensured by
the operator.
Information
Thermostat
With a thermostat in the cooling water inlet, the volume of cooling water can be adjusted to the actual
requirements.
Pos: 129 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uch kompakt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
Summary of Contents for B 1050 Series
Page 1: ...B 1050 en Industrial gear units Operating and Assembly Instructions...
Page 5: ...Publisher B 1050 en 1819 5...
Page 87: ...7 Appendix B 1050 en 1819 87 Gear units SK 5207 SK 10507 M3 oil screw holes...
Page 89: ...7 Appendix B 1050 en 1819 89 Gear units SK 5207 SK 10507 M5 oil screw holes...
Page 93: ...7 Appendix B 1050 en 1819 93 Gear units SK 11207 SK 15507 M3 oil screw holes...
Page 95: ...7 Appendix B 1050 en 1819 95 Gear units SK 11207 SK 15507 M5 oil screw holes...
Page 112: ...6052902 1819...