Introduction     

4.

Product Guide 

     VISI-SWITCH

®

INSULATION SYSTEM

VISIBLE BREAK WINDOW

The insulation system consists of the conductor system 
embedded in solid dielectric.  External insulation is 
provided by silicone bushings outside of the powder 
coated stainless steel tank. Silicone Rubber Boots fitted 
over the bushings provide the necessary clearances 
and creepages required for the various ratings.  

Surge Arrestors can be mounted on all six (6) bushings 
and earthed through the tank. Explosive tail surge 
arrestors may be used and there are mounting options 
for the surge arrestors both at the top and bottom of 
the switch.

The viewing window allows a clear view of the state of 
the switch from an operator standing on the ground. The 
isolator contact is coated with an iridescent/reflective 
paint in the colour red and can be easily seen through 
the window even at night with the use of a torch. 

The window is designed to remain transparent during 
the entire life of the switch, without any discolouration. 
It is scratch resistant and can withstand extreme 
temperatures and weather conditions such as hailstorms 
and sandstorms.  IK08 impact ratings are met on all 
parts of the switch including the viewing window.

VISI-SWITCH

®

  WITH 

VISIBLE ISOLATOR

IN OPEN POSITION

VISI-SWITCH

®

  WITH TOP 

SURGE ARRESTORS 

ARRANGEMENT

VISI-SWITCH

®

  WITH 

BOTTOM SURGE 

ARRESTORS 

ARRANGEMENT

VISI-SWITCH

®

  WITH TOP 

SURGE ARRESTORS 

ARRANGEMENT

VISI-SWITCH

® 

 WITH 

VISIBLE ISOLATOR IN 

CLOSED POSITION

Summary of Contents for VISI-SWITCH OLB15-16-800

Page 1: ... VISI SWITCH VISI SWITCH OLB15 16 800 12KV MODEL PRODUCT GUIDE ...

Page 2: ...15 16 800 has a rated maximum voltage of 12 kV a rated continuous current of 800 A and a short time current withstand of 16 kA for 3 seconds Each phase is comprised of a vacuum interrupter with solid dielectric insulation and a built in isolator to provide physical isolation in accordance with the requirements of insulation coordination standards IEC 60071 1 Insulation co ordination Part 1 Definit...

Page 3: ... to isolate sections of feeders for maintenance work In recent years older air break switches which could not be operated while the feeder was under load have been replaced by gas switches While enclosed gas switches address the reliability deficiencies of air break switches it comes at a cost of compromised safety because maintenance staff can no longer visually check that all three phases are is...

Page 4: ...d with a single motion using either an extended hook stick which reaches directly to the switch or a shorter hook stick which connects to an insulated down rod extending from the switch The advantage of the switch is that the operator can view the isolator contacts through the viewing window thereby readily determining the state of the switch from the ground In particular the operator can confirm ...

Page 5: ...g window allows a clear view of the state of the switch from an operator standing on the ground The isolator contact is coated with an iridescent reflective paint in the colour red and can be easily seen through the window even at night with the use of a torch The window is designed to remain transparent during the entire life of the switch without any discolouration It is scratch resistant and ca...

Page 6: ...r facing toward the pole or away from the pole The switch assembly can be fixed to the pole via a crane pole mounted hoist or EPV Lifting points are provided to allow for lifting of the assembled switch The switch is to remain within 15 degrees of horizontal whilst lifting An M12 stud on the switch is provided for an earth connection A minimum thickness of 35mm2 copper conductor must be used Stand...

Page 7: ...PEN STATE 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 1082 3 46 2 879 4 34 6 1421 7 55 4 250 0 9 8 1179 0 46 4 333 0 13 3 333 0 13 3 VISI SWITCH SIDE VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS VISI SWITCH FRONT VIEW DIMENSIONS IN INCHES SHOWN IN BRACKETS An insulated down rod extending from the switch can be used to move the operating mechanism further down the ...

Page 8: ... Current Rated Distribution Line Closed Loop Breaking Current Short time current withstand Fault Make Capacity RMS Fault Make Capacity Peak Mainly Active Load Breaking Rated Cable Charging Breaking Current Rated Line Charging Breaking Current Rated Cable and Line Charging Breaking Current under Earth Fault Conditions Rated Earth Fault Breaking Current Mechanical Operations Full Load Operations Fau...