Product parameters
Connection type
Type
ASD25DC
Pole
4P
Installation
Fixed
Rated current(A)
800A/1000A/1250A/1600A/2000A/2500A
Rated Maximum Volatge(V)
DC1500
Short circuit withstand current (kA)
120/150
Operating time(ms)
Max.openning time
Max.openning time
≤30
Max.closing time
Max.closing time
≤70
Life cycle(time)
Mechanical
12500
Electrical
2000
External dimensions
Inches(mm) H
×
W
×
D
800A-2000A
15.43
×
18.31
×
17.01 (392
×
465
×
433)
2500A
15.43
×
18.31
×
18.78 (392
×
465
×
477)
Enclosure dimensions
Inches(mm) H
×
W
×
D
21.73
×
23.62
×
13.86 (552
×
600
×
352)
Ventilation Area Top: 18183mm²
TypeC
Upper Supply
Lower supply
TypeD
Environmental conditions
Ambient temperature
Altitude
Humidity
Rated
Current(A)
Temperature(
℃
)
Horizontial type
Vertical type
<40
45
50
55
60
65
70
<40
45
50
55
60
65
70
800
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
1600
100%
100%
100%
100%
100%
95%
90%
100%
100%
100%
100%
100%
100%
100%
2000
100%
100%
100%
100%
95%
90%
85%
100%
100%
100%
100%
100%
95%
93%
2500
100%
100%
100%
95%
90%
85%
80%
100%
100%
100%
100%
95%
93%
90%
Altitude(m)
<2000
3000
4000
5000
Rated Voltage(V)
1xIn
0.9xIn
0.8xIn
0.7xIn
Rated Current(A)
1xIn
0.98xIn
0.96xIn
0.94In
ASD25DC air switch disconnector can operate in -40
℃
~ 70
℃
environmental conditions.
ASD25DC air switch disconnector can operate at higher temperatures than the reference temperature 40
℃
,in this case,the derating
coefficients shown in the table must be applied.
ASD25DC air switch disconnector do not undergo changes in rated performance up to 2000m.Beyond this altitude ,the derating
coefficients shown in the table must be applied.
The relative humidity does not exceed 85% at 40
℃
,the monthly average maximum of relative humidity in the wettest month
does not exceed 90%.
The effect of surface condensation caused by temperature changes on product performance should be taken into consideration.
*Configuration C for ungrounded system only
*Configuration D for either grounded or ungrounded in PV system
Load
+(-)
-(+)
Load
+(-)
-(+)
Load
+(-)
-(+)
Load
+(-)
-(+)