2.3. UPS Positioning
The UPS should be installed in the environment with free ventilation, less
dust, optimum ambient temperature and humidity.
The recommended ambient temperature is 20°C~25°C with 50% humidity.
•
Ambient temperature: 0°C~+40°C
•
Storage temperature: -15ºC ~ 60ºC
•
Relative humidity: 0 ~ 95%
•
Altitude: If the UPS is installed within 1000m, the UPS power will not be
derated. When the altitude is over 1000m, the output power will be derated
by following the table.
•
Vertical: No vibration and the degree of deviation from vertical shouldn’t
be more than 5°.
•
Space: It’s requested to have a clearance of approx. 50 cm to the front
and back of the unit and approx. 50 cm to the side.
Caution!
It’s NOT allow to have flammable, explosive or corrosive gas or liquid in
installation environment. It is forbidden to install in a metal conductive dust
environment.
Altitude(m)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Coefficient
100%
95%
91%
86%
82%
78%
74%
70%
67%
Diagram 1: Front door open
view HV 180KT
Diagram 2: Terminal
view HV 180KT