Instruction Manual/Supplement
Parameter Setting
Page 8
Modbus Extension Module NF Energy Saver - rev. 00 / 24.04.2019
7 Parameter Setting
Set the parameters of the Modbus Extension Module by using the menu of the NivuFlow
Energy Saver.
Preconditions
•
The Modbus Extension Module is correctly connected to the transmitter.
•
The Modbus Extension Module is connected to the power supply module.
•
The metal carrier rail is earthed.
Procedure
Set Pump(s) Parameters
1. Open the >Application< / >Pump< menu and check the “Active” checkbox for
pump 1.
The other pumps can be selected by clicking “Tab”.
Fig. 7-1
Open and activate pump
2. In “Type” use the pulldown menu to select the pump type >WAGO I/O-
Expander<.
Fig. 7-2
Select pump type and open the settings
3. Open the settings for the selected pump.
Select the (current) input range (0-20 mA or 4-20 mA) each for power and
frequency (pulldown menu).
4. In power and frequency specify the values for 0 mA or 4 mA and 20 mA.