NIVELCO UNICONT PDF-401-A EX Installation And Programming Manual Download Page 1

 

BKI15ATEX0013X/1 

 pdf4012a0600p_06 

 1 / 20 

Manufacturer:

H-1043 Budapest, Dugonics u. 11.

Phone: (36-1)  889-0100          Fax: (36-1) 889-0200

sales

       

NIVELCO  Process Control Co.

E-mail: @nivelco.com

www.nivelco.com

UNICONT

PDF - loop indicator and

converter to HART

Summary of Contents for UNICONT PDF-401-A EX

Page 1: ...df4012a0600p_06 1 20 Manufacturer H 1043 Budapest Dugonics u 11 Phone 36 1 889 0100 Fax 36 1 889 0200 sales NIVELCO Process Control Co E mail nivelco com www nivelco com UNICONT PDF loop indicator and...

Page 2: ...G INTO OPERATION PROGRAMMING 10 5 1 DEFAULT 11 5 2 DISPLAY OF THE SAP 202 AND KEYS OF THE UNIT 11 5 3 PROGRAMMING 12 5 3 1 STEPS OF PROGRAMMING 12 5 3 2 PARAMETERS DESCRIPTION AND PROGRAMMING 14 5 4 E...

Page 3: ...o HART signals and so enable devices that have analogue outputs only to be integrated into HART multidrop systems The ratio between the input and output current can be programmed The intelligent elect...

Page 4: ...r displayed values over 10000 Temperature coefficient 0 05 10 K Output 4 20 mA and or HART for 4 20mA current limit values 3 9 20 5 mA terminal resistor for HART Rtmin 250 Error indication on the curr...

Page 5: ...tic M20x1 5 for cable diameter 6 12 mm Metal M20x1 5 for cable diameter 7 13 mm Metal M20x1 5 for cable diameter 8 12 mm Ambient temperature 25 C 70 C TYPE P F 501 8 EX P F 401 8 EX P F 601 8 EX P F 4...

Page 6: ...ts Installation and programming manual Warranty Card Declaration of Conformity Sticker set of engineering units HART os k sz l kn l CDROM az EView2 programmal 4 INSTALLATION AND ELECTRIC CONNECTION Th...

Page 7: ...the flameproof device is allowed to remove only when the unit is de energized The housing cover can be removed after unscrew the M2 size hex socket set screw or after dismounting the safety locking bo...

Page 8: ...Wiring of a HART capable 3 wire Unicont in the current loop of a 4 wire transmitter HART L L SH Us 4 20mA 4 20mA Transmitter Ex 1 P F 01 8 B D Ex Ex Ex HART 6 1 6 1 Transmitter Ex 2 R 250 P F 01 8 B D...

Page 9: ...0 20mA 4 20mA 0 20mA HART 6 6 1 1 P F 01 4 Transmitter 1 Transmitter 15 R 250 Figure 6 Wiring of 3 wire Uniconts with Multicont controller and 4 wire transmitters 1 6 R 5 Figure 7 Internal wiring of...

Page 10: ...dow of intrinsical safe equipment with metallic enclosure exceeds the limit thus the devices must be protected against electrostatic charges Equipment with plastic housing are susceptible to electrost...

Page 11: ...put current appears on the display of the 2 wire models While pressing the key the output current appears on the display of the 3 wire models 5 2 DISPLAY OF THE SAP 202 AND KEYS OF THE UNIT Symbols on...

Page 12: ...of PROGRAMMING mode It is also used in programming mode This is represented in the manual with the symbols of the two keys and the sign in between them That is E getting into PROGRAMMING mode This pro...

Page 13: ...er values to default LOAD is be displayed for warning Reset default value of the relevant parameter LOAD will be displayed for warning GET VALUE function for automatic setting of P0 and P1 Actual meas...

Page 14: ...current value is to be entered in P0 or P1 it can automatically be set by the GET VALUE function To do so the above described procedure should be performed but pressing instead of step 4 Successful se...

Page 15: ...e set for 0 20 mA P9 a Current generator test for 3 wire models only In this parameter the actual current output is displayed Going to the parameter value the output current of 3 6 22 mA can be set by...

Page 16: ...ut current to be the error indication of the Unicont For 3 wire models only Attention character a is at the right end this is the first to blink a Range selection d Error indication on the current out...

Page 17: ...S 3 cm in VOL C 4 l gal FLOW 5 t 6 F P13 00ba HART short address for 3 wire models only FACTORY DEFAULT 00 The short address of the unit for the multidrop system HART network is to be given here Pleas...

Page 18: ...cm2 35 Kelvin 61 kg 87 LTon h 126 152 ft3 lb 10 kg cm2 36 mV 62 MetTon 88 LTon d 127 kW 153 pF 11 Pa 37 ohm 63 lb 89 128 kWh 154 mL L 12 kPa 38 Hz 64 STon 90 129 hp 155 uL L 13 torr 39 mA 65 LTon 91...

Page 19: ...ess E to go to the address and E again to return to value Enter the new secret code or 0000 If there is no secret code or it is not active the PROG symbol is blinking 5 4 ERROR INDICATIONS 5 4 1 VALID...

Page 20: ...ned All repairs will be carried out only on the premises of the Manufacturer 7 STORAGE Ambient temperature 25 C 60 C Relative humidity max 98 8 WARRANTY NIVELCO provides warranty of 3 three years in c...