NIVELCO PJK-100 User Manual Download Page 2

pjk1024a0600h_01 

 2 / 2

5.2. W

IRING

See: 2. Technical Data and 4. Electrical connection

5.3. I

NSTALLATION

5.3.1 P

OWER 

ON 

AND 

S

ELF TEST

After correctly wiring and switching the device on, it runs a few self tests whose results are shown with
LED indications.

’COM.

’ LED-s

STATUS

’ LED-s

S

EQUENCE OF SELF TESTS

1.

2.

1.

2.

1.

Test of red LED-s:

Red

Red

2.

Test of green LED-s:

Green

Green

DIP switch test:

Blinking green

Dark

Dark

Dark

3.

  result:

Green: OK.

Red: Error

Dark

Dark

Dark

RESET button test:

Blinking green

Dark

Dark

4.

  result:

Green: OK.

Red: Error

Dark

Dark

Detecting Relay on 1. unit:

Blinking green

Dark

5.

  result:

Green: Exists

Red: Error

Dark: Doesn’t

exist

Dark

Detecting Relay on 2. unit:

Blinking green

6.

  result:

Green: Exists

Red: Error

Dark: Doesn’t

exist

Detecting Current output on 1. unit,
(if relay doesn’t exists):

Blinking green

7.

  result:

Green: Exists

Red: Error

Dark: Doesn’t

exist

Detecting Current output on 2. unit,
(if relay doesn’t exist):

Blinking green

8.

  result:

Green: Exists

Red: Error

Dark: Doesn’t

exist

9.

Peripheral self test results for 1sec:

EEPROM block test result
(block1, block2):

Green: OK.

Red: Error

Green: OK.

Red: Error

10.

If content of one block is erroneous, it
is corrected from the other one, if both
are erroneous, they are corrected by
loading default values:

Green: OK.

Green: OK.

Device is ready:

Pale green

Pale green

Device is ready:

Pale green

Pale green

Dark

Dark

11.

RAM, ROM,
EEPROM
tests and their
results:

Device is unable to
operate:

Red blinking together

5.3.2 O

PERATION

-

 

After the self test sequence, if the device is ready for operation, states and operation of the module and

its units are shown as follows:

-

 

‘COM’ LED

 – indicates the communication with the unit that belongs to it, (all LED-s flash in case of

communication with the module), it also indicates the operation state of the device.

-

 

‘STATUS’ LED

 – indicates the state of the unit that belongs to it.

O

PERATION STATES

LED:

D

ISPLAY

:

C

OMMENT

:

PALE GREEN

Device is ready

GREEN FLASH

Successful communication

RED FLASH

Communication failure

COM.

RED

Communication cycle time-out

R

ELAY UNIT

C

URRENT GENERATOR UNIT

GREEN

Energised

Current in linear range

DARK

De-energised

-

RED

-

Error (signal) current

STATUS

BLINKING RED

Relay error

Current generator error

5.3.3. P

ROGRAMMING

SETTING THE CURRENT GENERATOR AND RELAY OPERATION

Depending on the application, re-programming of the device may be needed. Programming can be done
with either a PC that controls the communication network via HART or MODBUS protocol, or a

MultiCONT

 (see MultiCONT’s User Manual). Parameters determining the operation:

P

ARAMETERS AVAILABLE FOR ALL UNITS

:

F

ACTORY

SETTING

Communication watchdog

Off

R

ELAY UNIT PARAMETERS

:

F

ACTORY

SETTING

C

URRENT GENERATOR UNIT

PARAMETERS

:

F

ACTORY

SETTING

-

 

0...25.5 s pulse time

(non restartable)

-

 

Configurable energised or

de-energised error state:

-

 

for device hardware error

-

 

for comm. cycle time-out

0.1s

Off
Off

-

 

Configurable error-current

3,6 mA or 

22 mA:

-

 

for device hardware error

-

 

for comm. cycle time-out

-

 

Scaling values at 4 and 20 mA

Off
Off
Calibrated

5.3.3.1 MODBUS 

COMMUNICATION PROTOCOL

Physical format: RS485, Slave, RTU, 9600 Baud, 1-8-Odd-1. Registers of the device can be accessed
(read or write) with command 3 (Read Holding Registers) and command 16 (Preset Multiply Registers).
Device address is adjustable in 1...31 range only. Detailed description of registers can be found in a
separate document.

5.3.3.2 HART 

COMMUNICATION PROTOCOL

Physical format: RS485, Slave, RTU, 9600 Baud, 1-8-Odd-1. Device address is adjustable in 1…31
range. Detailed description of HART (standard 5) commands can be found in a separate document.

Logical set-up of the device:

Interpreted commands:

A

DDRESSING

C

OMMAND

CODE

S

HORT

L

ONG

Module-level HART commands

0

Read Unique ID

6

Write Polling Address

7

Read Polling Address

12

Read Message

13

Read Tag, Descriptor, Date

16

Read Final Assembly Number

17

Write Message

18

Write Tag, Descriptor, Date

38

Reset ’Config Change Flag’

140

Write Device ID

200

Read Device Table

206

Read Firmware Version

Unit-level HART commands

13

-

Read Tag, Descriptor, Date

18

-

Write Tag, Descriptor, Date

201

-

Read Slot Output/Input

202

-

Write Slot Output

203

-

Read Slot Configuration

204

-

Write Slot Configuration

205

-

Write Slot Calibration

206

-

Read Firmware Version

5.3.4 O

THER OPERATING SERVICES

M

ODULE SERVICES

:

Operating time count

C

OMMON SERVICES OF THE UNITS

:

Communication watchdog (comm. cycle time-out)

R

ELAY UNITS

’ 

SERVICES

:

C

URRENT GENERATORS

’ 

SERVICE

:

-

 

Static or pulse output

-

 

Eligible pulse default state

-

 

Detection of coil splitting (error indication)

-

 

Sum of energised state times

-

 

Nr. of switching cycles

-

 

Life-time (max. numbers of switching cycles)

-

 

Monitoring correct operation of current
generator (error indication)

5.3.5. RESET,

 

TEST 

MODE

AND LOADING 

FACTORY DEFAULTS

The mentioned operations can be done, without restarting the device, with the small recessed
‘RESET(TEST)’ button on the front panel:

RESET:

- Press

Entering TEST mode:

- Press and Hold

Loading factory default settings: - Hold pressed while power on, and release when all LEDs flash red.

Attention! The current generator units should be recalibrated!

The HART long addresses will change!

T

EST MODE

Once in test mode by consecutive pressing the 

‘RESET(TEST)’

 button you can cycle through the

following tests. Pressing this button until all Red LED-s are flashing will exit the test mode, without
pressing the button the device quits test mode after 30 seconds.

C

ONSECUTIVE TESTS

:

COM

.’ LED-s:

(identifying tested unit)

STATUS

’ LED-s

correct operation:

energised

R

ELAY UNIT

de-energised

Red

3.6 mA
4 mA
12 mA
20 mA

C

URRENT

GENERATOR UNIT

22 mA

Flashing red together

As described in

 

5.3.2

DIP 

SWITCH

correct operation
-

 

switching to left:

-

 

switching to right:

Alternate flashing red

Red flashing
on 

1

st

 unit,

on 

2

nd

 unit.

6. MAINTENANCE, REPAIR

The device does not require regular maintenance.
Repair within and beyond the warranty period is carried out at the Manufacturer’s location.

7. STORAGE

Ambient temperature: -30 °C... +60 °C. Relative humidity: max. 98%

8. WARRANTY

All Nivelco products are warraned free of defects in materials or workmanship for a period of two years
from the date of purchase, as indicated in the Certificate of Warranty.

pjk1024a0700h_02

January, 2007.

Nivelco reserves the right of technical changes

M

ODUL

Factory: 151

Type: 50
ID: xxxxxx
Polling: 0..31

U

NIT 

1.

Factory: 151
Type: 51
ID: 1

U

NIT 

2.

Factory: 151
Type: 51
ID: 2